3. NOISE
3.1 NOISE PARAMETERS
3.1.1 |
The construction noise level shall be measured in terms of the A-weighted equivalent continuous sound pressure level (Leq). Leq(30 min) shall be used as the monitoring parameter for the time period between 0700-1900 hours on normal weekdays. For all other time periods, Leq(5 min) shall be employed for comparison with the Noise Control Ordinance (NCO) criteria. |
3.1.2 |
As supplementary information for data auditing, statistical results such as L10 and L90 shall also be obtained for reference. A sample data record sheet is shown in Appendix B2 for reference. |
3.2 MONITORING EQUIPMENT
3.2.1 |
As referred to in the Technical Memorandum (TM) issued under NCO, sound level meters in compliance with the International Electrotechnical Commission Publications 651: 1979 (Type 1) and 804: 1985 (Type 1) specifications shall be used for carrying out the noise monitoring. Immediately prior to and following each noise measurement the accuracy of the sound level meter shall be checked using an acoustic calibrator generating a known sound pressure level at a known frequency. Measurements may be accepted as valid only if the calibration level from before and after the noise measurement agree to within 1.0dB. |
3.2.2 |
Noise measurements should not be made in the presence of fog, rain, wind with a steady speed exceeding 5 m/s or wind with gusts exceeding 10 m/s. The wind speed shall be checked with a portable wind speed meter capable of measuring the wind speed in m/s. |
3.2.3 |
The ET is responsible for the provision of the monitoring equipment. He shall ensure that sufficient noise measuring equipment and associated instrumentation are available for carrying out the baseline monitoring, regular impact monitoring and ad hoc monitoring. All the equipment and associated instrumentation shall be clearly labelled. |
3.3 MONITORING LOCATIONS
3.3.1 |
Based on the EIA findings there may be residual impacts therefore potential noise sensitive receptors have been identified. The locations of noise monitoring stations are shown in Figure 3.1 |
3.3.2 |
Owing to the nature of the works under the project, construction activities will shift from one location to another from time to time. The ET shall select the monitoring locations from those in Figure 3.1 based on the locations of the construction activities and seek approval from ER and agreement from the IEC and EPD of the proposal. The monitoring locations should be chosen based on the following criteria : |
3.3.3 |
The monitoring station shall normally be at a point 1 m from the exterior of the sensitive receivers building facade and be at a position 1.2 m above the ground. If there is problem with access to the normal monitoring position, an alternative position may be chosen, and a correction to the measurements shall be made. For reference, a correction of +3dB(A) shall be made to the free field measurements. The ET shall agree with the IEC and EPD on the monitoring position and the corrections adopted. Once the positions for the monitoring stations are chosen, the baseline monitoring and the impact monitoring shall be carried out at the same positions. |
3.4 IMPACT MONITORING
3.4.1 |
Noise monitoring shall be carried out at all the designated monitoring stations. The monitoring frequency shall depend on the scale of the construction activities. The following is an initial guide on the regular monitoring frequency for each station on a per week basis when noise generating activities are underway: |
3.4.2 |
General construction work carrying out during restricted hours is controlled by Construction Noise Permit (CNP) system under the NCO. |
3.4.3 |
In case of non-compliance with the construction noise criteria, more frequent monitoring as specified in the Action Plan in Section 3.5 shall be carried out. This additional monitoring shall be continued until the recorded noise levels are rectified or proved to be irrelevant to the construction activities. |
3.4.4 |
A schedule on the compliance monitoring shall be submitted to the ER, EPD and IEC for approval before the monitoring starts. |
3.5 EVENT AND ACTION PLAN FOR NOISE
3.5.1 The Action and Limit levels for construction noise are defined in Table 3.1. Should non-compliance of the criteria occur, action in accordance with the Action Plan in Table 3.2, shall be carried out.
Table 3.1 Action and Limit Levels for Construction Noise
Time Period |
Action Level |
Limit Level |
0700-1900 hours on normal weekdays |
When one documented complaint is received |
75* dB(A) |
* Reduce to 70 dB(A) for schools and 65 dB(A) during school examination periods
Note : If works are to be carried out during restricted hours, the conditions stipulated in the construction noise permit issued by the Noise Control Authority have to be followed.
Table 3.2 Event / Action Plan for Construction Noise
EVENT |
ACTION |
|||
ET |
IEC |
ER |
CONTRACTOR |
|
Action Level |
Identify source, investigate the causes of exceedance and propose remedial measures; Notify IEC and Contractor; Report the results of investigation to the ER and Contractor; Discuss with the Contractor and formulate remedial measures; Increase monitoring frequency to check mitigation effectiveness; |
1. Review the analysed results submitted by the ET; Review the proposed remedial measures by the Contractor and advise the ER accordingly; Supervise the implementation of remedial measures. |
Confirm receipt of notification of failure in writing; Notify Contractor Require Contractor to propose remedial measures for the analysed noise problem; Ensure remedial measures are properly implemented.
|
1. Submit noise mitigation proposals to IEC; 2. Implement noise mitigation proposals. |
Limit Level |
Identify source; Inform IEC, ER, EPD and Contractor; Repeat measurements to confirm findings; Increase monitoring frequency; Carry out analysis of Contractor’s working procedures to determine possible mitigation to be implemented; Inform IEC, ER and EPD the causes & actions taken for the exceedances. Assess effectiveness of Contractor’s remedial actions and keep IEC, EPD and ER informed of the results; If exceedance stops, cease additional monitoring. |
Discuss amongst ER, ET, and Contractor on the potential remedial actions; Review Contractors remedial actions whenever necessary to assure their effectiveness and advise the ER accordingly; Supervise the implementation of remedial measures. |
Confirm receipt of notification of failure in writing; Notify Contractor; Require Contractor to propose remedial measures for the analysed noise problem; Ensure remedial measures properly implemented; If exceedance continues, consider what portion of the work is responsible and instruct the Contractor to stop that portion of work until the exceedance is abated. |
Take immediate action to avoid further exceedance Submit proposals for remedial to IEC within 3 working days of notification; Implement the agreed proposals; Resubmit proposals if problem still not under control; Stop the relevant portion of works as determined by the ER until the exceedance is abated. |
3.6.1 |
The EIA report has recommended construction noise control and mitigation measures during construction and operational phases. |
CONSTRUCTION PHASE
3.6.2 |
The Contractor shall be responsible for the design and implementation of these measures. The key measures are: |
3.6.3 |
The number and the type of plant for each construction activity to be used during the construction period are listed in Appendix H. |
3.6.4 |
In addition, good site practices are also recommended as follows: |
3.6.5 |
The implementation schedule for the mitigation measures is presented in Appendix C2. On the other hand, impact prediction review checklist (Appendix F2) should be employed to check the extent of discrepancy between the actual and the predicted impact at the designated monitoring stations. ET should estimate the efficiency of the proposed mitigation and plan carefully for the ongoing construction activities. |
3.6.6 |
If the above measures is not sufficient to restore the construction noise to an acceptable levels upon the advice of ET, the Contractor shall liaise with the ET and ER on some other mitigation measures, propose to IEC and EPD for approval, and carry out the mitigation measures. |
OPERATIONAL PHASE
3.7 OPERATIONAL PHASE NOISE MONITORING
3.7.1 |
As the noise sensitive receivers close to the proposed road will be exposed to traffic noise during the operational phase, a noise monitoring programme shall be developed to include noise measurements at noise sensitive receivers during the peak traffic hour. The programme shall be carried out by the Environmental Team (ET) to ensure that the traffic noise levels are comparable to those predicted in the EIA under the full provision of the mitigation measures recommended. The Territory Development Department (TDD) will be responsible for the operational phase monitoring. |
NOISE PARAMETERS
3.7.2 |
The traffic noise level shall be measured twice within the first year of the road opening. Measurement shall be made in terms of the A-weighted L10 over three half-hour periods during the peak traffic hour. Other metrics like Leq may be added as seen fit. A sample data record sheet is shown in the Appendix G. More details could be referred to Section 3.7.3. |
MONITORING EQUIPMENT
3.7.3 |
Sound level meters to be used shall be in compliance with the International Electrotechnical Commission Publications 651: 1979 (Type 1) and 804: 1985 (Type 1) specifications for carrying out the noise monitoring. Immediately prior to and following each noise measurement the accuracy of the sound level meter shall be checked using an acoustic calibrator generating a known sound pressure level at a known frequency. Measurements may be accepted as valid only if the calibration level from before and after the noise measurement agree to within 1.0 dB(A). |
3.7.4. |
Noise measurement should be made in accordance with standard acoustical principles and practices in relation to weather conditions |
3.7.5. |
The ET Leader is responsible for the provision and maintenance of the monitoring equipment. All the equipment and associated instrumentation shall be clearly labelled |
MONITORING LOCATIONS
3.7.6 |
The noise monitoring locations should be at NSRs located in the vicinity of recommended direct technical remedies. The recommended noise monitoring locations for the worst case scenario (with development to the south of Road D1) and the situation without development to the south of Road D1 are shown in Figures 3.2 and 3.3 respectively. The monitoring locations would be at the 10/F & 30/F of the selected residential building. Detail descriptions are summarised in Tables 3.3 and 3.4. However, the exact locations where the noise monitoring conducted shall be confirmed after the completion of Roads D1, D8 & D10 and shall be agreed with the EPD. In order to make an easy checking of the relationship between the predicted and measured noise levels, the suggested monitoring stations are same as the assessment points used in the EIA. |
Table 3.3 Noise Monitoring Stations during Operational Phase for Worst Case Scenario (With Development to the South of Road D1)
Noise Monitoring Station |
EIA Assessment Point |
Noise Monitoring Location |
OM1 |
NSR 271 |
Area 65B |
OM2 |
NSR 638 |
Area 65D (southern façade) |
OM3 |
NSR 207 |
Area 67B (southern façade) |
OM4 |
NSR 209 |
Area 67B (western façade) |
OM5 |
NSR 218 |
Area 72 |
OM6 |
NSR 825 |
Area 86 |
OM7 |
NSR 828 |
Area 86 |
OM8 |
NSR 102 |
Future Development to the south of Road D1 near Area 65D (facing Road D10) |
Note: * Monitoring point bases on the indicative layout which is required to be confirmed.
Table 3.4 Noise Monitoring Stations during Operational Phase for the Scenario Without Development to the South of Road D1
Noise Monitoring Station |
EIA Assessment Point |
Noise Monitoring Location |
OM1 |
NSR 271 |
Area 65B |
OM2 |
NSR 638 |
Area 65D (southern façade) |
OM3 |
NSR 207 |
Area 67B (southern façade) |
OM4 |
NSR 209 |
Area 67B (western façade) |
OM5 |
NSR 218 |
Area 72 |
OM6 |
NSR 825 |
Area 86 |
OM7 |
NSR 828 |
Area 86 |
3.7.7 |
When alternative monitoring locations are proposed, the monitoring locations shall be chosen based on the following criteria: |
3.7.8 |
The operational noise monitoring shall be carried out a distance of 1 m from the openable window and 1.2 m above the floor level of the noise sensitive receivers identified. The ET Leader shall agree with the IEC on any necessary corrections adopted. |
BASELINE MONITORING
3.7.9 |
No baseline operational noise monitoring is required. |
IMPACT MONITORING
3.7.10 |
Traffic noise monitoring shall be carried out at all the designated traffic noise monitoring stations. The following is an initial guide on the traffic noise monitoring requirements during the operational phase: |
Measured noise levels should be compared with predicted noise levels by applying appropriate conversion corrections to allow for the traffic conditions at the time of measurement. Appendix G shows a sample data record sheet for operational noise monitoring.
3.7.11 |
Each set of measurements shall include three measurements of 30 minutes. The parameters L10, Leq, L90 and Lmax will be recorded for data auditing and reference. |
3.7.12 |
The exact timing shall be confirmed with the TDD and agreed with EPD |
NOISE MITIGATION MEASURES
3.7.13 |
As mentioned in the EIA report, two assessments (assuming with and without the possible future development) were undertaken to evaluate the traffic noise impacts from the proposed roads and recommended appropriate noise mitigation measures. The project proponent is responsible for the design and construction of these mitigation measures as follows : |
Assessment 1 – Worst Case Situation (With possible future development)
Road D1 (With the development to the South of Road D1)
Road D8 (With the development to the South of Road D1)
Road D10 (With the development to the South of Road D1)
Extended Road P2 (With the development to the South of Road D1)
Assessment 2 – Worst Case Situation (Without possible future development)
Road D1 (Without the development to the South of Road D1)
Road D8 (Without the development to the South of Road D1)
Road D10 (With the development to the South of Road D1)
Extended Road P2 (Without the development to the South of Road D1)
3.7.14 |
The design and construction of the mitigation measures for Road P2 south to the roundabout will be carried during Future Road P2 construction. |
3.7.15 |
The locations of the proposed noise barriers and cross-section of the noise barriers are shown in Figures C1 to C22. The implementation schedule for the mitigation measures is presented in Appendix C2. |
EVENT AND ACTION PLAN
3.7.16 |
The measured / monitored noise levels shall be compared with the predicted results and the predicted traffic flow conditions (calculated noise levels based on concurrent traffic census obtained). In case discrepancies are observed, explanation should be given to justify the discrepancies. |