Table 3.7.3
Parameters and Equations Adopted
in the MOS Rail Noise Calculation
Parameters Adopted
|
(8-car train)
|
1. Maximum train frequency (number of trains
per hour per direction) during the off-peak hours (2300 to 0700)
|
10
|
2. Number of cars
|
8
|
3. Train Speed, V (kph)
|
80
|
4. Enclosure at crossover
|
Yes
|
Assessment Results
3.7.14 The unmitigated noise levels has been predicted and presented
in Table 3.7.4 and Annex C3. Comparison of the unmitigated noise levels
in Leq (30min) at NSRs with night-time noise criteria are also given in
Table 3.7.4.
3.7.15 Table 3.7.4 shows that without mitigation, exceedance of the noise
criteria would be experienced at future NSR 10-1 by up to 3 dB(A). Mitigation
measures are required to protect this NSR from train noise.
3.7.16 NSR 18-1 at Lok Wo Sha Development will be protected by the adequate
setback as the reserve of the main spine road and the landscape corridor
along the WKS Station. This reserve has been incorporated in the preliminary
PDO design.
Table 3.7.4
Unmitigated Noise Levels
WRNSR
|
No. of Floor
|
Shortest Horizontal Distance From the Assessment
Point to the Rail Track (m)
|
Worst Affected Floor
|
Rail Noise From the Track Leq
(30 min)
|
Total Noise Level Leq
(30 min)
|
Exceed noise criterion of 55 dB(A)
|
10-1
|
42
|
15
|
7
|
58
|
58
|
Yes
|
18-1
|
30
|
120
|
18
|
53
|
53
|
No
|
Mitigation Measures
3.7.17 To achieve a noise reduction of up to 3 dB(A), mitigation measures
in terms of additional semi-enclosure or installation of central plenum
on the twin viaduct section have been proposed and shown in Figure 3.7.2a
& b. The option of central plenum is preferred as it has no visual
impact. It should be noted that adequate allowance has been made on the
viaduct design to support possible additional barrier for protecting future
NSRs from rail noise. The mitigated noise level is shown in Table 3.7.5.
Table 3.7.5
Mitigated Noise Levels at NSR 10-1
WRNSR
|
No. of Floor
|
Additional Viaduct Edge Barrier (m)
|
Worst Affected Floor
|
Total Noise Level
Leq (30 min)
|
10-1
|
42
|
a) Semi-enclosure
|
7
|
53
|
|
|
b) Additional Central Plenum
|
7
|
54
|
3.7.18 According to MOS Rail EIA, "the Multi-plenum System provides
the flexibility for future enhancement as edge wall barrier heights can
be incrementally extended for increased noise attenuation from 1.2m up to
full enclosure". In other words, adequate allowance has been made
on MOS Rail's viaduct design to support possible additional barriers for
protecting future NSRs from rail noise. The proposed mitigation measures
will be further reviewed in the detailed design stage of the residential
development at Wu Kai Sha Station. The developers/ project proponents are
responsible for designing their own layouts as well as the railway noise
mitigation measures.
Summary
3.7.19 Railway noise assessment has been undertaken to investigate the
potential noise impact from operational trains of MOS Rail on the proposed
residential areas within the proposed development. It is predicted that
the proposed high rise residential developments in the vicinity of MOS
Rail will be subject to railway noise impacts. Based on worst case calculations
and mitigation at source, the required mitigation for various scenarios
are identified and summarised below.
Table 3.7.6
Summary of the Mitigation Measures for MOS Train Noise
Development
|
Mitigation Measures
|
Residential Development at WKS Station
|
Approximate 60m long semi-enclosure along twin viaduct section
OR
Approximate 60m long central plenum along twin viaduct section
|
3.7.20 With the implementation of the recommended noise mitigation measures,
the residential development at WKS Station would comply with the NCO noise
limits. The proposed mitigation measures are to be further reviewed in the
detail design stage of the residential development at WKS Station.
3.8 Operational Noise - Fixed-Noise Source
Introduction
3.8.1 The potential fixed-noise sources to be assessed are shown in Table
3.8.1 and their locations are shown in Figure 3.8.1.
Table 3.8.1
Categories of Fixed-Noise Assessment
Types of Fixed Noise
|
NSRs to be Assessed
|
Future fixed noise sources as a result of the development:
- Public Transport Terminus / Open coach parking
- Utility services (proposed salt water pumping station)
- Ventilation system of the proposed commercial centre and Indoor
Recreation Centre
|
Both existing and future NSRs including the proposed development
|
Existing / committed fixed noise sources
not part of the development:
- Existing sewage pumping station in Ma On Shan Area 108 near
Lee On Estate
- MOS Rail Wu Kai Sha Station
|
NSRs of the proposed development
|
3.8.2 There will be no future electric station or depot within the proposed
development.
3.8.3 An existing wooden jetty is located in To Tau Tsuen to the west
of Lok Wo Sha Development. According to on-site observation, the small
wooden jetty is primarily used for recreational purposes only (such as
leisure rowing and fishing). Noise impact from the jetty on the future
Lok Wo Sha Development (located more than 130 m away) is not expected.
3.8.4 The assessment of the fixed noise sources has employed standard
acoustic principles. The assessment has been based on the best available
data and information.
3.8.5 In the absence of detail design information of the fixed sources,
the maximum at-source noise levels were calculated to ensure compliance
with the relevant noise criteria as specified in the TMEIA (i.e. ANL -
5 dB(A)). These maximum noise levels should be used by the detailed design
team to workout the mitigation in order to meet the acceptable noise levels.
3.8.6 In any event, the ASR assumed in this EIA report is for indicative
assessment only. It should be noted that fixed-noise sources are controlled
under Section 13 of the NCO. Nothing in this EIA Report shall bind the
Noise Control Authority in assessing noise from these sources upon the
receipt of complaints. The Authority shall assess the noise impacts based
on the contemporary conditions / situations.
Existing Seweage Pumping Station at Lee On Estate
3.8.7 An existing sewage pumping station in Ma On Shan Area 108 is located
about 70m west of the proposed Wu Kai Sha Station development (Figure
3.8.1). A noise measurement has been conducted to identify the potential
fixed noise impact from this pumping station to the proposed development.
Noise Assessment Methodology
3.8.8 The noise assessment has been based on measured free-field noise
levels, and the details of assessment methodology are shown in Annex C4.
Monitoring Results
3.8.9 A noise monitoring has been undertaken on 8 October 2001 to measure
the noise generated due to the operation of the pumping station. The monitoring
location is about 3 m from the louvre at the pumping station. The monitoring
procedure follows the procedure stipulated in Technical Memorandum for
the Assessment of Noise from Places other than Domestic Premises, Public
Places or Construction Sites (TM2). The monitoring results are shown in
Table 3.8.2. The monitoring location is shown in Figure 3.8.1.
Table 3.8.2
Monitoring Results of Pumping Station
Time
|
Distance from Pumping Station
|
Leq (30 mins), dB(A)
|
10:00a.m.- 10:30a.m.
|
3 m from Pumping Station
|
65.0
|
10:30a.m.- 11:00a.m.
|
3 m from Pumping Station
|
65.3
|
11:00a.m.- 11:30a.m.
|
3 m from Pumping Station
|
65.2
|
Pumping Noise Impact Assessment
3.8.10 The predicted noise levels at NSR 10-1 is shown in Table 3.8.3.
The predicted result shows that the noise generated by the operation of
the existing sewage pumping station is below the planning noise criteria
of 50 dB(A) for night-time period. Therefore, it is expected that the
existing sewage pumping station will not pose any noise nuisance to the
proposed development. This is because the whole pumping station is fully
enclosed in a building and the noise generated by the pump is effectively
mitigated.
Table 3.8.3
Predicted Noise Levels generated from the Pumping Station at
Ground Level of NSR 10
NSR
|
Predicted SWL dB(A)
|
Distance (m)
|
Distance Correction
|
Facade Effect
|
Predicted Noise Level, dB(A)
|
10-1
|
82.7
|
70
|
44.9
|
+ 3 dB(A)
|
40.8
|
3.8.11 It is understood that the pumping station is likely to be upgraded
by other project. The future upgrading works on the pumping station should
ensure that the noise levels emitted from the pumping station will not exceed
the TMEIA night-time criteria for an area sensitivity rating of 'B' at NSR
10 (i.e. 50 dB(A)). Based on the noise limit of 50 dB(A) at a distance of
70 m (NSR 10), the maximum allowable sound power level emitting from the
exhaust of the future upgraded pumping station must not exceed 92 dB(A).
MOS Rail - Wu Kai Sha Station
3.8.12 A future MOS Rail Station (Wu Kai Sha) is being constructed. Noise
from fixed sources associated with the rail station likely includes ventilation
exhaust and plant room. According to KCRC information on the station,
passenger platform will be fully enclosed and air-conditioned, and so
the public announcement system which is inside the enclosed platform will
not have impact on the nearby sensitive receivers.
Assessment Methodology
3.8.13 The assessment of the fixed plant noise from the future WKS Station
has employed standard acoustic principles in the prediction of the maximum
at-source noise levels to ensure compliance with noise criteria specified
in the TMEIA. This includes a review of the likely location of the fixed
plant and the nearest NSR which could be potentially affected, a determination
of the acceptable noise limit of NSR based on the assigned Area Sensitivity
Rating (ASR) and a calculation of the maximum allowable total sound power
level of the fixed plant at-source. The maximum allowable sound power
level of the fixed plant was calculated based on the night-time noise
criteria stipulated in the TMEIA (i.e. TM2 -5 dB(A)) of the selected NSR,
the attenuation of noise due to separation distance and noise reflection
from building façade.
3.8.14 In the absence of any detailed information and noise specification
of the fixed-noise sources, detailed noise assessment cannot be accurately
undertaken. In this case, a quantitative approach to define the noise
limits of the fixed plant for the future detailed design of the fixed
plant installation and buildings has been conducted.
3.8.15 To simulate a worst case scenario, the fixed-noise sources were
assumed to be located at the boundary of the proposed service facilities
closest to the identified NSRs. The shortest possible separation distance
from identified NSRs to the noise sources was used in the calculation.
3.8.16 In general, the noise assessment has been based on free-field
noise level.
3.8.17 In the case of the public announcement system, it was assumed
that the station will be fully open without any screening effect from
the station structures. The assessment methodology is shown in Annex C4.
Assessment Results
3.8.18 The maximum allowable sound pressure level for the fixed noise
sources (ventilation exhaust and plant room) associated with MOS Rail
Wu Kai Sha Station is tabulated below in Table 3.8.4.
Table 3.8.4
Maximum Allowable Sound Pressure Level for Fixed-Noise Sources
Associated with MOS Rail Wu Kai Sha Station
Fixed Noise Sources
|
Worst Affected NSR
|
Approximate Separation Distance (m)
|
TMEIA Fixed Noise Limit (ANL ¨C 5 dB(A))* (dB(A))
|
Maximum Allowable Sound Pressure Level** (Design
Noise Limit) (dB(A))
|
Announcement System Ventilation exhaust and plant room of MOS Wu
Kai Sha Station
|
6
|
75
|
50
|
93
|
10
|
14
|
50
|
78
|
18
|
90
|
50
|
94
|
* Area Sensitivity Rating of "B" applied.
** The sound pressure level is 1m from façade of the source.
Façade correction of 3 dB(A) included.
Fixed-Noise Impact Assessment and Mitigation Measures
Ventilation Exhaust and Plant Room
3.8.19 No adverse noise impacts on the nearby NSRs would likely be expected
when the specifications (Table 3.8.4) are strictly adhered to in the detailed
design. In general, noise from the ventilation exhaust and plant room
of MOS Wu Kai Sha Station can be readily reduced by locating it as far
from the NSRs as possible, and by orientating the noise source away from
the NSRs. A design noise limit (i.e. 78 dB(A)) for the detailed design
of fixed noise source of Wu Kai Sha Station is recommended. Alternatively,
the future detailed design of any fixed noise sources of Wu Kai Sha Station
undertaking by KCRC will need to satisfy the TMEIA or findings of this
EIA report.
Proposed Public Transport Terminus and Open Coach
Parking
3.8.20 A Public Transport Terminus (PTT) is proposed within the sites of
Lok Wo Sha and Whitehead. The PTT would incorporate two franchised bus bays,
two green mini-bus bays, two taxi stands and one general pick-up / drop-off
bay. The open coach parking has a capacity of 20 numbers of coaches.
Assessment Methodology
3.8.21 The assessment of the noise from the future PTT has employed standard
acoustic principles in the prediction of the maximum at-source noise levels
to ensure compliance with noise criteria specified in the TMEIA. This
includes a review of the nearest NSR which could be potentially affected,
a determination of the acceptablenoise limit of NSR based on the assigned
Area Sensitivity Rating (ASR) and a calculation of the maximum allowable
total sound power level of the PTT at-source. The maximum allowable sound
power level of the PTT was calculated based on the night-time noise criteria
stipulated in the TMEIA (i.e. TM2 -5 dB(A)) of the selected NSR, the attenuation
of noise due to separation distance and noise reflection from building
façade.
3.8.22 A noise monitoring was undertaken on 11 January 2002 to measure
the noise generated from a similar PTT (bus stop outside HKUST). The monitoring
location is about 15 m from the PTT. The monitoring procedure follows
the procedure stipulated in Technical Memorandum for the Assessment of
Noise from Places other than Domestic Premises, Public Places or Construction
Sites (TM2). The monitoring results are shown in Table 3.8.5.
Table 3.8.5
Monitoring Results of PTT (HKUST Bus Stop)
No of vehicles
|
166
|
% heavy vehicles
|
79.5 %
|
Approximate distance from the PTT
|
15 m
|
Measured Leq (30 minutes)
|
65.2 dB(A)
|
Assessment Results
3.8.23 The area sensitivity rating for the NSRs at Whitehead site is
assumed to be "A". The acceptable noise levels based on TMEIA
(i.e. ANL - 5B(A)) are 55 dB(A) from 0700-2300 hours and 45 dB(A) from
2300-0700 hours.
3.8.24 The nearest NSR (NSR 33) at Whitehead site is located approximately
85 m from the boundary of the proposed PTT. Based on this distance, the
maximum allowable sound power level emitting from the PTT is tabulated
below in Table 3.8.6.
Table 3.8.6
Maximum Allowable Sound Power Level for the proposed PTT
Worst Affected NSR
|
Approximate Separation Distance (m)
|
TMEIA Fixed Noise Level (ANL-5dB(A)) (dB(A))
|
Maximum Allowable Sound Power Level (dB(A))
|
33
|
85
|
55 (for daytime and evening from 0700-2300 hours)
|
98.6
|
|
|
45 (for night time from 2300-0700 hours)
|
88.6
|
Note:
Area Sensitivity Rating of "A" is applied.
3.8.25 Applying the noise monitoring result taken in the HKUST PTT, the
sound power level of the proposed PTT is predicted to be 96.7 dB(A) which
is below the proposed maximum allowable sound power level.
3.8.26 It is expected that the heavy vehicle traffic using the PTT and
carpark during the night time is relatively light. It is likely that majority
of the recreational facilities except the restaurant will be closed by
11:00 p.m., therefore, the frequency of the public bus would be reduced.
Also, the operation of coach would be ceased. As a result, noise impact
arising from heavy vehicles during night time is expected to be minor.
Proposed Utility Services
3.8.27 A salt water pumping station is proposed west of the proposed
Whitehead Site 2 development and an indoor recreation center is proposed
at the eastern part of the PDO. The ventilation/ cooling systems of the
indoor recreation center and the pumping station are considered to be
fixed-noise sources.
Assessment Methodology
3.8.28 The assessment of the fixed plant noise from utility services
proposed under this Project has employed standard acoustic principles
in the prediction of the maximum at-source noise levels to ensure compliance
with noise criteria specified in the TMEIA. Where the fixed noise source
is generated as a result of the proposed development, these maximum noise
levels should be used by the detailed design team to workout the mitigation
in order to meet the TMEIA noise criteria.
3.8.29 The assessment assumption and methodology is essentially the same
as that for the MOS Wu Kai Sha Station calculation described previously.
Assessment Results
3.8.30 The maximum allowable sound power level of the proposed utility
services is tabulated in Table 3.8.7.
Table 3.8.7
Maximum Allowable Sound Pressure Level for Fixed Noise Sources
associated with the proposed Utility Services
Fixed Noise Sources
|
Worst Affected NSR
|
Approximate Separation Distance (m)
|
TM-EIA Fixed Noise Limit (ANL ¨C 5 dB(A)) (dB(A))
|
Maximum Allowable Sound Pressure Level# (Design
Noise Limit) (dB(A))
|
Salt Water Pumping Station west to Whitehead Site 2
|
24
|
25
|
45*
|
78
|
Ventilation system of the Indoor Recreation Centre
|
5
|
125
|
60**
|
107
|
Ventilation system of the Commercial Centre at Lok Wo Sha Development
|
18
|
6
|
60**
|
81
|
Notes:
* Area Sensitivity Rating of "A" is applied. For those education
uses, only daytime and evening noise limit is applied, 55 dB(A). For Residential
Development, nighttime noise limit is applied, 45 dB(A).
** Area Sensitivity Rating of "B" is applied. As the Indoor Recreation
Centre and the Commercial Centre will only operate from 07:00 to 23:00,
only daytime and evening noise limit is applied, 60 dB(A).
# The sound pressure level is 1m from façade of the source. Façade
correction of 3 dB(A) is included.
Fixed Noise Impact Assessment and Mitigation Measures
Salt Water Pumping Station
3.8.31 The main sources of fixed noise are from the pumps and ventilation
system. It is recommended that the exhaust of the ventilation system and
any opening of the building should be located facing away from any NSRs,
i.e. facing west, to avoid noise nuisance to the nearby NSRs. Louver or
other acoustic reduction system should also be applied to the exhaust
exit of the building.
3.8.32 Given the fully enclosed design with louver at the exhaust system,
operational noise from the pumping station is not expected to pose any
adverse impact to the proposed development.
Ventilation System of Indoor Recreation Centre and Commercial Centre
3.8.33 For the indoor recreation centre and commercial centre, the major
fixed noise source will be the ventilation system. No adverse noise impacts
on the nearby NSRs would likely be expected when the specifications are
strictly adhered to in the detailed design. In general, noise from the
ventilation/cooling system can be readily reduced by locating it as far
from the NSRs as possible, and by orientating the noise source away from
the NSRs. It is recommended that the ventilation/cooling system at the
indoor recreation centre should be located at the southern part of the
indoor recreation centre with opening facing towards south. For the commercial
centre, the ventilation system should be located at the southern part
of the commercial centre with opening facing towards either east or west.
Also, with incorporation of silencer and acoustic louver, the noise emitted
out from the ventilation system to the surrounding environment will be
greatly reduced.
Existing Industrial Establishments
3.8.34 According to the findings of site surveys, there are currently
no industrial establishments within 300 m of the Study Area.
3.9 Conclusion
Construction Noise
3.9.1 Noise from the use of powered mechanical equipment during construction
activities and the haulage of material may potentially cause exceedance
of construction noise standard at the nearby existing noise sensitive
receivers (NSRs) if construction noise is not appropriately mitigated.
Adequate mitigation measures will be required for the construction works
to meet the noise standard.
3.9.2 The construction noise assessment shows that unmitigated noise
levels might exceed EPD's recommended maximum noise levels for day-time
construction work when construction activities occur in close proximity
to NSRs or when several construction works occur simultaneously.
3.9.3 Exceedance of noise level is unavoidable because of the close proximity
between the construction works and some of the NSRs. Adequate mitigation
measures will be required for the construction works to meet the criteria.
3.9.4 The use of quiet plant and working methods, reducing the number
of equipment, restricting the number of works and the use of temporary
noise barriers to protect the closest residences, and schools has been
recommended and would be sufficient to reduce noise levels to compliance
levels at the NSRs.
3.9.5 A noise monitoring programme is proposed to ensure that construction
noise is within the recommended criteria throughout the construction stage.
Operational Noise
Traffic Noise
3.9.6 Traffic noise impact assessment for the proposed development has
been conducted. Most of the sensitive receivers within the proposed development
will not be subject to traffic noise nuisance with the introduction of
environmentally friendly layout design, except for some of the façades
at the Wu Kai Sha Station Development due to the technical inapplicability
of direct noise mitigation measure such as noise barrier at Sha On Street.
Provision of window insulation and air-conditioning or special layout
design has been proposed to resolve the traffic noise nuisance.
3.9.7 For those school-type NSRs exceeding the noise criterion, noise
mitigation measures have been proposed in the form of boundary wall.
3.9.8 All the proposed measures are subject to the configuration of the
development layout plans. The developers/project proponents are responsible
for designing their own layouts with the recommendation stipulated in
this EIA report. In the event that an alternative layout is proposed,
the relevant developer/project proponents should prove that the new layout
could meet the equivalent or better environmental standards as given in
this EIA report. In addition, the relevant developer/project proponents
should be aware of the site constraints assumed in this EIA.
3.9.9 Residual impacts may arise at some units of the Symphony Bay and
one village house at Lok Wo Sha. Eligibility test on these façades
has been conducted, but none of these façades qualify for the noise
insulation works under ExCo directive.
3.9.10 An operational traffic noise monitoring is proposed to check the
effectiveness of the proposed mitigation measures such as boundary wall
and environmentally friendly design layout.
Rail Noise
3.9.11 Rail noise assessment has been undertaken to investigate the potential
noise impact from operational trains of MOS Rail on the residential areas
within the proposed development.
With the implementation of the recommended noise mitigation measures
such as central plenum or equivalent on the concerned viaduct section
of MOS Rail, the nearby noise sensitive uses will not be subject to train
noise level above the NCO noise limit.
Fixed-Noise
3.9.13 No existing industrial noise sources were identified during site
surveys. An existing sewage pumping station is found to be located near
Lee On Estate. With the enclosure and sufficient buffer distance, the
fixed-noise generated from the sewage pumping station will not pose any
noise nuisance to the proposed development.
3.9.14 Potential fixed noise sources assessed include noise from public
transport terminus / open coach parking, ventilation system of the proposed
commercial centre within the proposed development and that of the indoor
recreational centre, proposed salt water pumping station, ventilation
exhaust and plant room of MOS Rail Wu Kai Sha Station. Noise impacts on
the nearby NSRs from these fixed noise sources will not be insurmountable
provided that the noise levels from the different fixed plants do not
exceed the maximum allowable sound pressure level (design noise limit)
predicted in the assessment.
|