· to identify the extent of construction dust impacts on sensitive receivers;
· to determine the effectiveness of mitigation measures to control fugitive dust emission from activities during construction phase;
· to audit the compliance of the Contractor with regard to dust control, contract conditions and the relevant dust impact criteria;
· to recommend further mitigation measures if found to be necessary;
· to comply with Action and Limit (A/L) Levels for air quality as defined in this Manual.
· The Hong Kong Air Quality Objectives (AQOs) for TSP, 24-hour TSP levels of 260 mg m-3; and
· The statutory 1-hour TSP limit of 500 mg m-3.
·
0.6 -
1.7 m3 per minute (20 - 60 standard cubic feet per minute)
adjustable flow range;
·
equipped
with a timing / control device with ±
5 minutes accuracy for 24 hours operation;
·
installed
with elapsed-time meter with ± 2
minutes accuracy for 24 hours operation;
·
capable
of providing a minimum exposed area of 406 cm2 (63 in2);
·
flow
control accuracy: ± 2.5% deviation over 24-hour sampling
period;
·
incorporated
with an electronic mass flow rate controller or other equivalent devices;
·
equipped
with a flow recorder for continuous monitoring;
·
provided
with a peaked roof inlet;
·
incorporated
with a manometer;
·
able
to hold and seal the filter paper to the sampler housing at horizontal
position;
·
easy
to change the filter;
·
capable
of operating continuously for 24-hour period.
Table 2.1 Air Monitoring Stations during Construction Phase
Project
Classification |
Identification No. |
Air Monitoring Location |
Non-designated
Project |
LWT2 |
Pui O Lo Wai Tsuen facing South Lantau Road |
Non-designated
Project |
PG1 |
Children’s Playground next
to Chi Ma Wan Road |
Designated
Project |
SHWAB |
Siu Ho Wan WTW
Administration Building |
·
monitoring at sensitive receivers close to the major
site activities which are likely to have air quality impacts;
·
monitoring at the air sensitive receivers as
defined in the Technical Memorandum;
· a horizontal platform with appropriate support to secure the samplers against gusty wind shall be provided;
· no two samplers shall be placed less than 2 m apart;
· the distance between the sampler and an obstacle, such as buildings, must be at least twice the height that the obstacle protrudes above the sampler;
· a minimum of 2 m separation from walls, parapets and penthouses is required for rooftops samplers;
· a minimum of 2 m separation from any supporting structure, measures horizontally is required;
· no furnace or incinerator flue is nearby;
· airflow around the sampler is unrestricted;
· the sampler is more than 20 m from the dripline;
· any wire fence and gate to protect the sampler, shall not cause any obstruction during monitoring;
· permission must be obtained to set up the samplers and to obtain access to the monitoring stations; and
· a secured supply of electricity is needed to operate the samplers.
Table 2.2 Impact Monitoring Programme (TSP)
Sampling duration |
Frequency |
1 hour |
·
3 times every 6 days (as required in case of
complaints) |
24 hours |
·
Once every 6 days |
Table 2.3 Proposed Action and Limit Levels for Impact Monitoring
Parameter |
Action Level (1) |
Limit Level |
TSP
(24 hour average) |
·
BL £ 200 mg
m-3, AL = (BL * 1.3 + LL)/2 ·
BL > 200 mg m-3, AL = LL |
260
mg
m-3 |
TSP
(1 hour average) |
·
BL £ 384 mg
m-3, AL = (BL * 1.3 + LL)/2 ·
BL > 384 mg m-3, AL
= LL |
500
mg
m-3 |
(1) BL
= Baseline level, AL = Action level, LL = Limit level.
Table 2.4 Event
/ Action Plan for Ambient Air Quality Monitoring (Construction)
ACTION |
||||
ET |
IC(E) |
ER |
CONTRACTOR |
|
ACTION LEVEL |
||||
1. Exceedance for one sample |
1. Identify source, investigate the causes of complaint and propose
remedial measures; 2. Inform IC(E) and ER; 3. Repeat measurement to confirm finding; 4. Increase monitoring frequency to daily. |
1.
Check monitoring data submitted by ET; 2.
Check Contractor’s working method. |
1. Notify Contractor. |
1. Rectify any unacceptable practice; 2. Amend working methods if appropriate. |
2. Exceedance for two or more consecutive samples |
1.
Identify source; 2.
Inform IC(E) and ER; 3.
Advise the ER on the effectiveness of the
proposed remedial measures; 4.
Repeat measurements to confirm findings; 5.
Increase monitoring frequency to daily; 6.
Discuss with IC(E) and Contractor on remedial
actions required; 7.
If exceedance continues, arrange meeting with
IC(E) and ER; 8. If exceedance stops, cease additional monitoring. |
1.
Check monitoring data submitted by ET; 2.
Check Contractor’s working method; 3.
Discuss with ET and Contractor on possible
remedial measures; 4.
Advise the ET on the effectiveness of the
proposed remedial measures; 5.
Supervise Implementation of remedial
measures. |
1. Confirm receipt of
notification of exceedance in writing; 2.
Notify Contractor; 3.
Ensure remedial measures properly
implemented. |
1. Submit proposals for remedial to ER within three working days
of notification; 2. Implement the agreed proposals; 3. Amend proposal if appropriate. |
LIMIT LEVEL |
||||
1. Exceedance for one sample |
1. Identify source, investigate the causes of exceedance and
propose remedial measures; 2. Inform IC(E), ER, Contractor and EPD; 3. Repeat measurement to confirm finding; 4. Increase monitoring frequency to daily; 5. Assess effectiveness of Contractor’s remedial actions and
keep IC(E), EPD and ER informed of the results. |
1.
Check monitoring data submitted by ET; 2.
Check Contractor’s working method; 3.
Discuss with ET and Contractor on possible
remedial measures; 4.
Advise the ER on the effectiveness of the
proposed remedial measures; 5.
Supervise implementation of remedial
measures. |
1.
Confirm receipt of notification of exceedance
in writing; 2.
Notify Contractor; 3.
Ensure remedial measures properly
implemented. |
1.
Take immediate action to avoid further
exceedance; 2.
Submit proposals for remedial actions to
IC(E) within three working days of notification; 3.
Implement the agreed proposals; 4. Amend proposal if appropriate. |
2. Exceedance for two or more consecutive samples |
1. Notify IC(E), ER, Contractor and EPD; 2. Identify source; 3. Repeat measurement to confirm findings; 4. Increase monitoring frequency to daily; 5. Carry out analysis of Contractor’s working procedures to determine
possible mitigation to be implemented; 6. Arrange meeting with IC(E) and ER to discuss the remedial actions to
be taken; 7. Assess effectiveness of Contractor’s remedial actions and keep IC(E),
EPD and ER informed of the results; 8. If exceedance stops, cease additional monitoring. |
1.
Discuss amongst ER, ET, and Contractor on the
potential remedial actions; 2.
Review Contractor’s remedial actions whenever
necessary to assure their effectiveness and advise the ER accordingly; 3.
Supervise the implementation of remedial
measures. |
1. Confirm receipt of notification of exceedance in writing; 2. Notify Contractor; 3. In consultation with the IC(E), agree with the Contractor on the
remedial measures to be implemented; 4. Ensure remedial measures properly implemented; 5. If exceedance continues, consider what portion of the work is
responsible and instruct the Contractor to stop that portion of work until
the exceedance is abated. |
1. Take immediate action to avoid further exceedance; 2. Submit proposals for remedial actions to IC(E) within three
working days of notification; 3. Implement the agreed proposals; 4. Resubmit proposals if problem still not under control; 5. Stop the relevant portion of works as determined by the ER
until the exceedance is abated. |
·
watering on the work sites at Siu Ho
Wan and Pui OWTW and at
Pui O twice a day;
· skip hoist for material transport should be totally enclosed by impervious sheeting;
· vehicle washing facilities should be provided at every vehicle exit point;
· the area where vehicle washing takes place and the section of the road between the washing facilities and the exit point should be paved with concrete, bituminous materials or hardcores;
· every main haul road should be scaled with concrete and kept clear of dusty materials or sprayed with water so as to maintain the entire road surface wet;
· every stock of more than 20 bags of cement should be covered entirely by impervious sheeting placed in an area sheltered on the top and the three sides;
· all dusty materials should be sprayed with water prior to any loading, unloading or transfer operation so as to maintain the dusty materials wet;
· every vehicle should be washed to remove any dusty materials from its body and wheels before leaving the construction sites;
· the dusty materials stockpiled on site should be covered;
· the load of dusty materials carried by vehicle leaving a construction site should be covered entirely by clean impervious sheeting to ensure dust materials do not leak from the vehicle.