4.
WATER QUALITY
4.1.1
The EIA identified activities
and locations during the construction of the KT13 that may have potential
impacts on water quality. The EIA recommended a number of mitigation measures
that should be implemented to control the potential impacts to within
acceptable limits. A monitoring programme is recommended for baseline
conditions and during the construction phase to assess and ensure the
performance of the proposed measures.
4.1.2
This section of the Manual
lists all the recommended mitigative and preventive measures in the EIA for the
protection of water quality during construction phase, and the up to date
requirements for baseline and construction phase water quality monitoring. The
Contractor is required to implement these listed measures and to undertake
water quality monitoring as specified in this section, in addition to complying
with all the water quality related legislation of HKSAR.
4.2.1
The
selection of water quality monitoring parameters shall be based on the
recommendations in the EIA report. The monitoring shall be carried out by the
ET to ensure that any deteriorating water quality can be readily detected and
action be taken in time to rectify the situation.
4.2.2
In
addition to the water quality parameters, selected relevant data shall also be
measured, such as monitoring location/position, time, water depth, water
temperature, salinity, DO saturation, weather conditions, tidal stage, and any
special phenomena and work underway at the construction site.
4.2.3
The
data format of the water quality monitoring record and a sample monitoring
record sheet are shown in Appendix B for reference.
4.3
Sampling Procedures and Monitoring
Equipment
4.3.1
Water
samples for all monitoring parameters shall be collected, stored, preserved and
analysis according to the Standard Methods, APHA 17 ed. and/or methods agreed
by the Director of Environmental Protection. In-situ measurements at monitoring locations including DO,
turbidity, salinity and water depth shall be collected using equipment with the
characteristics and functions listed in the following sections.
Dissolved oxygen and temperature
measuring equipment
4.3.2
The
equipment shall have the following characteristics and functions.
(a)
The
instrument shall be a portable, weatherproof dissolved oxygen measuring
instrument complete with cable, sensor, comprehensive operation manuals, and
with the use of a DC power source. (e.g. YSI model 59 meter, YSI 5739 probe,
YSI 5795A submersible stirrer with reel and cable or an approved similar instrument).
It shall be capable of measuring:-
-
a
dissolved oxygen level in the range of 0-20 mg/l and 0-200% saturation; and
-
a
temperature of 0-45 degree Celsius.
(b)
It
shall have a membrane electrode with automatic temperature compensation
complete with a cable. Sufficient stocks of spare electrodes and cables shall
be available for replacement where necessary.
(c)
Should
salinity compensation not be built-in to the DO equipment, in-situ salinity
shall be measured to calibrate the DO equipment prior to each DO measurement.
Turbidity Measurement Instrument
4.3.3 The instrument shall be a portable, weatherproof turbidity-measuring instrument complete with comprehensive operation manual. The equipment shall use a DC power source. It shall have a photoelectric sensor capable of measuring turbidity between 0-1000 NTU (e.g. Hach model 2100P or an approved similar instrument).
Suspended Solids
4.3.4
The
equipment shall have the following characteristics and functions.
(a)
Sampling
shall be carried out using a water sampler which comprises a transparent PVC
cylinder, with a capacity of not less than 2 litres, and can be effectively
sealed with latex cups at both ends. The sampler shall have a positive latching
system to keep it open and prevent premature closure until released by a
messenger when the sampler is at the selected water depth (e.g. Kahlsico Water
Sampler or an approved similar instrument).
(b)
Water
samples for suspended solids measurement shall be collected in high density
polythene bottles, packed in ice (cooled to 4°C without being frozen), and
delivered to the laboratory as soon as possible after collection.
Water Depth Detector
4.3.5 A portable, battery-operated echo sounder shall be used for the determination of water depth at each designated monitoring station. This unit can either be handheld or affixed to the bottom of the work boat, if the same vessel is to be used throughout the monitoring programme.
4.4
Laboratory Measurement/Analysis
4.4.1
Analysis
of suspended solids, ammonia, and zinc concentration, shall be carried out in a
HOKLAS or other international accredited laboratory. Water samples of about
1000ml shall be collected at the monitoring stations for carrying out the
laboratory SS determination. The detection limit shall be 1 mg/L or better. The
SS determination work shall start within 24 hours after collection of the water
samples. The SS determination shall follow APHA 17ed 2540D or equivalent
methods subject to approval of EPD.
4.4.2
If
a site laboratory is set up or a non-HOKLAS and non-international accredited
laboratory is hired for carrying out the laboratory analysis, the laboratory
equipment, analytical procedures, and quality control shall be approved by the
EPD. All the analysis shall be witnessed by the ET. The ET Leader shall provide
the ER with one copy of the relevant chapters of the “Standard Methods for the
Examination of Water and Wastewater” updated edition and any other relevant
document for his reference.
4.4.3
For
the testing methods of other parameters as recommended by EIA or required by
EPD, detailed testing methods, pre-treatment procedures, instrument use,
Quality Assurance/Quality Control (QA/QC) details (such as blank, spike
recovery, number of duplicate samples per batch, etc.), detection limits and
accuracy shall be submitted to EPD for approval prior to the commencement of
monitoring programme. The QA/QC shall be in accordance with the requirement of
HOKLAS or international accredited scheme. The QA/QC results shall be reported.
EPD may also request the laboratory to carry out analysis of known standards
provided by EPD for quality assurance. Additional duplicate samples may be
required by EPD for inter laboratory calibration. Remaining samples after
analysis shall be kept by the laboratory for 3 months in case repeat analysis
is required. If in-house or non-standard methods are proposed, details of the
method verification may also be required to submit to EPD. In any circumstance,
the sample testing shall have comprehensive quality assurance and quality
control programmes. The laboratory shall prepare to demonstrate the programmes
to EPD or his representatives when requested.
4.5.1
Locations
of the sites to be monitored during baseline and impact monitoring are shown in
Table 4.1 and Figures 4.1a and 4.1b. The status and locations of water quality
sensitive receivers may change after issuing this manual. In such a case, the
ET Leader shall propose updated monitoring locations and seek approval from the
IEC and EPD.
Proposed Monitoring Locations for Water Quality
Monitoring
Location |
Description |
Purpose of
Placing Sampling Location |
W1 |
Upstream of all works proposed under KT13 and of the
stream |
Establish background levels of parameters to be
monitored, control station |
W2 |
In a short section left unmodified to retain dry
weather flow |
Monitor and audit potential impacts from Section B
works to unmodified stream. |
W3 |
Upstream of the section to be left unmodified for
ecological benefits |
Monitor and audit potential impacts from Section B
works to unmodified stream section, to ensure quality of water supplying the
egretry and associated wetland habitats
|
W4 |
Upstream of the discharge point of a local brook
into the main KT13 stream |
Establish background levels of parameters to be
monitored for this incoming water, control station. |
W5 |
Upstream of the discharge point of a second local
brook into the main KT13 stream |
Establish background levels of parameters to be
monitored for this incoming water, control station. |
W6 |
Immediately above the discharge point to Kam Tin
Main Drainage Channel |
Monitor and audit potential impacts from all KT13
works, check water quality discharging to Kam Tin River Main Drainage
Channel. |
4.5.2
When
alternative monitoring locations are proposed, they shall be chosen based on
the following criteria:
(a)
at
locations close to and preferably at the boundary of the mixing zone of the
major site activities as indicated in the EIA final report, which are likely to
have water quality impacts;
(b)
close
to the sensitive receptors which are directly or likely to be affected;
(c)
for
monitoring locations located in the vicinity of the sensitive receptors, care
shall be taken to cause minimal disturbance during monitoring;
(d)
two
or more control stations which shall be at locations representative of the
project site in its undisturbed condition. Control station shall be located, as
far as is practicable, both upstream and downstream of the works area.
4.5.3
Control
stations are necessary to compare the water quality from potentially impacted
sites with the ambient water quality. Control stations shall be located within
the same body of water as the impact monitoring stations but shall be outside
the area of influence of the works and, as far as practicable, not affected by
any other works.
4.5.4
Measurements
shall be taken at 3 water depths, namely, 1m below water surface, mid-depth and
1m above stream or sea bed, except where the water depth less than 6m, the
mid-depth station may be omitted. Should the water depth be less than 3m, only
the mid-depth station will be monitored.
4.5.5
Duplicates
in-situ measurements and samples
collected from each independent sampling event are required for all parameters
to ensure a robust statistically interpretable dataset.
4.6.1
Baseline
conditions for water quality shall be established and agreed with EPD prior to
the commencement of works. The purpose of the baseline monitoring is to
establish ambient conditions prior to the commencement of the works and to
demonstrate the suitability of the proposed impact, control and reference
monitoring stations. The baseline conditions shall be established by measuring
the water quality parameters specified in Table 4.2. The measurement shall be
taken at all designated monitoring stations including control stations for 3
days per week for 4 consecutive weeks prior to commencement of the works.
4.6.2
There
shall not be any construction activities in the vicinity of the stations during
the baseline monitoring.
4.6.3
In
exceptional cases when insufficient baseline monitoring data or questionable
results are obtained, the ET Leader shall seek approval from the IEC and EPD on
an appropriate set of data to be used as baseline reference.
4.6.4
Baseline
monitoring schedule shall be faxed to EPD 1 week prior to the commencement of
baseline monitoring. The interval between 2 sets of monitoring shall not be
less than 36 hours.
Water Quality Monitoring Locations, Parameter,
Frequency
and Duration for Baseline
Locations |
Parameters |
Frequency |
Duration |
W1 W2 W3 W4 W5 W6 |
DO,
pH,
turbidity,
temperature,
suspended
solids, ammonia, zinc |
3
days per week |
Four
weeks |
4.7.1
During
the course of the construction works, monitoring shall be undertaken according
to the parameters, frequencies, and duration described in Table 4.3. The
interval between two sets of monitoring shall not be less than 36 hours except
where there are exceedances of
Locations, Parameters, Frequencies and Durations during Construction
Phases
Parameter |
Locations |
Frequency |
DO/pH/Temperature/Turbidity/ SS/Ammonia/Zinc |
W1, W2, W3, W4, W5, W6 |
3 days per week throughout
construction phase. |
4.7.2
The
proposed water quality monitoring schedule shall be faxed to IEC and EPD on or
before the first day of the monitoring month. EPD shall also be notified
immediately for any changes in schedule by fax.
4.8
Event and Action Plan for Water
Quality
4.8.1
The
Action and Limit levels for water quality are shown in Table 4.4. Should the
monitoring results at any designated monitoring stations indicate that the
Action and Limit levels are exceeded, the actions specified in Table 4.5 shall
be carried out.
Action and Limit Levels for Water Quality
Parameters |
Action |
Limit |
DO in mg/l (Surface, Middle & Bottom) |
Surface & Middle 5%-ile
of baseline data for surface and middle layer Bottom 5%-ile
of baseline data for bottom layer. |
Surface & Middle 4mg/l or 1%-ile
of baseline data for surface and middle layer Bottom 2mg/l
or 1%-ile
of baseline data for bottom layer |
pH, turbidity, SS, ammonia and Zinc
(depth-averaged) |
95%-ile of baseline data or 120% of upstream
control station’s SS Turbidity, ammonia, Zinc and pH at the same tide of the
same day |
99%-ile of baseline or 130% of upstream control station’s SS
Turbidity, ammonia, zinc and pH at the same tide of the same day |
Notes:
-
For DO, non-compliance of the water quality limits
occurs when monitoring result is lower than the limits.
-
For ammonia, zinc, SS and Turbidity, non-compliance of
the water quality limits occurs when monitoring result is higher than the
limits.
-
For pH, non-compliance of the water quality limits
occurs when monitoring result is outside the specified range.
-
All the figures given in the table are used for
reference only and the EPD may amend the figures whenever it is considered as
necessary
Table 4.5 Event and Action Plan for Water Quality
Event |
ET Leader |
IEC |
ER |
Contractor |
Action
level being exceeded by one sampling day |
Repeat
in-site measurement to confirm findings; Identify
Source(s) of impact; Inform IEC
an Contractor; Check
monitoring data, all plant, equipment and Contractor’s working methods; Discuss
mitigation measures with IEC and Contractor; Repeat
measurement on next day of exceedance |
Discuss
with ET and Contractor on the mitigation measures Review proposals
on mitigation measures submitted by Contractor and advise the ER accordingly Assess the
effectiveness of the implemented mitigation measures. |
Discuss
with IEC on the proposed mitigation measures; Make
agreement on the mitigation measures to be implemented; |
Inform the
ER and confirm notification of the non-compliance in writing; Rectify
unacceptable practice; Check al
plant and equipment; Consider
changes of working methods; Discuss
with ET and IEC and propose mitigation measures to IEC and ER; Implement
the agreed mitigation measures. |
Action
level being exceeded by more than one consecutive sampling days |
Repeat
in-situ measurement to confirm findings; Identify
source(s) of impact; Inform IEC
and Contractor; Check
monitoring data, all plant, equipment and Contractor’s working methods; Discuss
mitigation measures with IEC and Contractor; Ensure
mitigation measures are implemented; Prepare to
increase the monitoring frequency to daily; Repeat
measurement on next day of exceedance. |
Discuss
with ET and Contractor on the mitigation measures Review
proposals on mitigation measures submitted by Contractor and advise the ER
accordingly Assess the
effectiveness of the implemented mitigation measures. |
Discuss
with IEC on the proposed mitigation measures; Made
agreement on the mitigation measures to be implemented; Assess the
effectiveness of the implemented mitigation measures. |
Inform the
Engineer and confirm notification of the non-compliance in writing; Rectify
unacceptable practice; Check all
plant and equipment; Consider
changes of working methods; Discuss
with ET and IEC and propose mitigation measures to IEC and ER within 3
working days; Implement
the agreed mitigation measures. |
Limit
level being exceeded by one sampling day |
Repeat
in-situ measurement to confirm findings; Identify
source(s) of impact; Inform
IEC, contractor and EPD; Check
monitoring data, all plant, equipment and Contractor’s
working methods; Discuss
mitigation measures with IEC, ER and Contractor; Ensure
mitigation measures are implemented; Increase
the monitoring frequency to daily until no exceedance of Limit level. |
Discuss
with ET and Contractor on the mitigation measures Review
proposals on mitigation measures submitted by Contractor and advise the R
accordingly Assess the
effectiveness of the implemented mitigation measures. |
Discuss
with IEC, ET and Contractor on the proposed mitigation measures; Request
Contract to critically review the working methods; Made
agreement on the mitigation measures to be implemented; Assess the
effectiveness of the implemented mitigation measures. |
Inform the
Engineer and confirm notification of the non-compliance in writing; Rectify
unacceptable practice; Check all
plant and equipment; consider
changes of working methods; Discuss
with ET, IEC and ER and propose mitigation measures to IEC and ER within 3
working days; Implement
the agreed mitigation measures/ |
Limit
level being exceeded by more than one consecutive sampling days |
Repeat
in-situ measurement to confirm fundings; Identify
source(s) of impact; Inform
IEC, contractor and EPD; Check
monitoring data, all plant, equipment and Contractor’s working methods; Discuss
mitigation measures with IEC, ER and Contractor; Ensure
mitigation measures are implemented; Increase
the Monitoring frequency to daily until no exceedance of Limit level for two
consecutive days. |
Discuss
with ET and Contractor on the mitigation measures Review
proposals on mitigation measures submitted by Contractor and advise the ER
accordingly Assess the
effectiveness of the implemented mitigation measures. |
Discuss
with IEC, ET and Contractor on the proposed mitigation measures; Request
Contractor to critically review the working methods; Make
agreement on the mitigation measures to be implemented; Assess the
effectiveness of the implemented mitigation measures; Consider
and instruct, if necessary, the Contractor to slow down or to stop all or
part of the marine work until no exceedance of Limit level. |
Inform the
ER and confirm notification of the non-compliance in writing; Rectify
unacceptable practice; Check all
plant and equipment; Consider
changes of working methods; Discuss
with ET, IEC and ER and propose mitigation measures to IEC and ER within 3
working days; Implement
the agreed mitigation measures; As directed
by the Engineer, to slow down or to stop all or part of the marine work or
construction activities. |
4.9
Water Quality Mitigation Measures
4.9.1 The following paragraphs discuss the proposed mitigation measures for protection of water quality during construction phase.
General
4.9.2 The Contractor shall observe and comply with the Water Pollution Control Ordinance (WPCO) and its subsidiary regulations. The Contractor shall carry out the works in such a manner as to minimise adverse impacts on the water quality during execution of the works. In particular the Contractor shall arrange his method of working to minimise the effects on the water quality within and outside the site and on the transport routes.
4.9.3 The Contractor shall follow the practices, and be responsible for the design, construction, operation and maintenance of all the mitigation measures as specified in ProPECC PN 1/94 - Construction Site Drainage. The design of the mitigation measures shall be submitted by the Contractor to the Engineer for approval.
4.9.4 As part of the ecological mitigation measure to minimise impact on the existing stream course, a restriction to minimise the working area to 75m length of stream at any one time has been proposed. Such restriction would also reduce the likely water quality impact.
Site Formation
4.9.5 Temporary earth bunds and/or sand bag barriers should be used to direct stormwater run-off to temporary settlement area. The settlement area should be within the channel itself. A cofferdam should be formed to keep the working area dry. The channel will be dug out to a depth of around 1–2m for a length of approximately 12m, to form a sedimentation area. The volume will be approximately 50m3 (with a channel width of 3.5m).
4.9.6 Sediment flowing downstream should settle in this settlement pond, while run-off from the surface should be channel through a local site drainage system into the settlement area. The settlement area should be maintained and the deposited materials should be removed regularly, at the onset of and after each rainstorm to ensure proper functioning at all times. No sediment removal shall be allowed in rainy weather.
4.9.7 Open stockpiles susceptible to erosion should be covered with tarpaulin or similar fabric, especially during the wet season (Apr-Sep) or when heavy rainstorm is predicted.
Stream Diversion and Dredging of Streams
4.9.8 The Contractor should provide temporary drainage diversion during construction to ensure continuous water flow to the untouched portion of the stream.
4.9.9 The use of containment structure such as temporary earth bunds, sand bags, sheetpile barriers or other similar techniques is recommended to facilitate a dry or at least confined excavation within watercourses.
4.9.10 Excavated sediment from streams and channel is likely to be wet and contaminated. The material should be stored in covered impermeable skips and disposed on the same day, or within 1 day, to avoid both odour and inadvertent release of contaminants to nearby water bodies.
Concreting Work
4.9.11
Runoff should be carefully
channelled to prevent concrete-contaminated water from entering watercourses.
Adjustment of pH can be achieved by adding a suitable neutralising reagent to
wastewater prior to discharge. Re-use of the supernatant from the sediment pits
for washing out of concrete lorries should be practised.
4.9.12
Any exceedance of acceptable
range of pH levels in the nearby water bodies caused by inadvertent release of
site runoff containing concrete should be monitored and rectified under the
EM&A programme for this Project.
Site
Workshop or Depot
4.9.13
Any Contractor generating waste
oil or other chemicals as a result of his activities should register as a
chemical waste producer and provide a safe storage area for chemicals on site.
The storage site should be located away from existing water courses. Hard
standing compounds should drain via an oil interceptor. To prevent spillage of
fuels or other chemicals to water courses, all fuel tanks and storage areas
should be sited on sealed areas, within a bund of a capacity equal to 110% of
the storage capacity of the largest tank. Disposal of the waste oil should be
done by a licensed collector. Oil interceptors should be regularly inspected
and cleaned to avoid wash-out of oil during storm conditions. A bypass should
be provided to avoid overload of the interceptor's capacity. Good housekeeping
practices should be implemented to minimise careless spillage and to keep the
storage and the work space in a tidy and clean condition. Appropriate training
including safety codes and relevant manuals should be given to the personnel
who regularly handle the chemicals on site.
Presence of Additional Population (Workers)
4.9.14
Sewage arising from the
additional population of workers on site should be collected in a suitable
storage facility, such as portable chemical toilets. An adequate number of
portable toilets should be provided for the construction workforce. The
portable toilets should be maintained in a state that will not deter the
workers from using them. The collected wastewater from sewage facilities and
also from eating areas or washing facilities must be disposed of properly, in
accordance with the WPCO requirements. Wastewater collected should be
discharged into foul sewers and collected by licensed collectors.
4.9.15
Either chemical toilets or
other types of sewage treatment facilities without local discharge of
wastewater shall be used to handle the foul water effluent arising from the
project sites.
4.9.16
Proper waste handling, storage,
collection and disposal measures as recommended in the Waste chapter should be
implemented by the Contractor.
Summary
of Mitigation Measures for Construction Phase
4.9.17 The potential impacts on water quality during the construction phase of the Work and the associated recommendation of mitigation measures are summarized in Table 4.5.
Summary of Mitigation Measures for Construction
Impacts
Impact
from Construction |
Mitigation
Measures |
General water quality impacts. |
To strictly follow the requirements in
ProPECC PN 1/94. Minimise working area to 75m length of stream. |
Increase of suspended solids and
turbidity from silty site run-off during site formation. |
After diversion of stream water, section
of channel under construction will be used as a settlement area for
construction site runoff. Sediments will be cleared from this settlement area
before and after each rainstorm. No sediment removal will be allowed in rainy
weather. Open stockpiles will be covered with tarpaulin during wet season. |
Release of contaminated and
uncontaminated sediments into stream water during stream diversion and
dredging of the stream. |
Ensure continuous water flow to the
stream by providing temporary drainage diversion during construction. Use of containment structures during
excavation. Excavated material to be stored in covered impermeable skips and
transported away from site on the same day or within 1 day. |
Elevation of pH, ammonia and suspend solids
in water courses from concrete washings. |
Monitoring and control of pH levels in
nearby water bodies as part of the EM&A programme. |
Release of oil and grease washings used
in the site workshop. |
The Contractor shall register as chemical
waste producer if waste oil is generated. Waste oil and other chemical waste
shall be collected by licenced contractors. |
Increase of sewage and other wastewater
from additional workers. |
Provision of mobile chemical toilets and
the collection and disposal of sewage by licenced contractors to government
sewers. Implement proper on-site waste management. |