Table 4.1 Locations for Construction Noise Monitoring
NSR |
Location |
N1 |
Village
house - No. 165A Lung Mei |
N2 |
Village
house - No. 103 Lung Mei |
N3 |
Village house - No. 70 Lo Tsz Tin |
N4 |
Village house - No. 79 Lo Tsz Tin |
4.1.1
Noise Parameters
The construction noise level shall be measured in terms of the A-weighted
equivalent continuous sound pressure level (Leq). Leq(30
min) shall be used as the monitoring parameter for the time period between
0700-1900 hours on normal weekdays. For all other time periods, Leq(5 min) shall be employed for
comparison with the NCO criteria.
4.1.2 Monitoring Equipment
As
referred to in the Technical Memorandum (TM) issued under the Noise Control
Ordinance (NCO), sound level meters in compliance with the International Electrotechnical Commission Publications 651: 1979 (Type 1)
and 804: 1985 (Type 1) specifications shall be used for carrying out the noise
monitoring. Immediately prior to and
following each noise measurement the accuracy of the sound level meter shall be
checked using an acoustic calibrator generating a known sound pressure level at
a known frequency. Measurements may be accepted as valid only if the calibration
level from before and after the noise measurement agrees to within 1.0 dB.
Noise measurements should not be made in accordance with standard acoustical
principles and practices in relation to weather conditions.
The ET Leader is responsible for the availability of monitoring equipment. He
shall ensure that sufficient noise measuring equipment and associated
instrumentation are available for carrying out the baseline monitoring, regular
impact monitoring and ad hoc monitoring. All the equipment and associated
instrumentation shall be clearly labelled.
4.1.3
Monitoring Locations
When alternative monitoring locations are proposed, the
monitoring locations shall be chosen based on the following criteria:
a)
at locations close to the major site
activities which are likely to have noise impacts;
b)
close to the noise sensitive
receivers (N.B. For the purposes of this section, any domestic premises, hotel,
hostel, temporary housing accommodation, hospital, medical clinic, educational
institution, place of public worship, library, court of law, performing art
centre shall be considered as a noise sensitive receiver); and
c)
for monitoring locations located in
the vicinity of the sensitive receivers, care shall be taken to cause minimal
disturbance to the occupants during monitoring.
The monitoring station shall normally be at a point 1m from the exterior of the
sensitive receivers building facade and be at a position 1.2m above the ground.
If there is a problem with access to the normal monitoring position, an
alternative position may be chosen, and a correction to the measurements shall
be made. For reference, a correction of +3 dB(A)
shall be made to the free field measurements. The ET Leader shall agree with the IEC on
the monitoring position and the corrections adopted. Once the positions for the
monitoring stations are chosen, the baseline monitoring and the impact
monitoring shall be carried out at the same positions.
4.1.4
Impact Monitoring
Weekly noise monitoring shall be carried out at all the designated monitoring
stations to obtain one set of 30-minute measurement between 0700-1900 hours.
General construction work carrying out during restricted hours is controlled by
CNP system under the NCO.
In
case of non-compliance with the construction noise criteria, more frequent
monitoring as specified in the Action Plan in Table 4.3 shall be carried out. This additional monitoring shall be
continued until the recorded noise levels are rectified or proved to be
irrelevant to the construction activities.
4.1.5
Event and Action Plan for Noise
The Action and Limit levels for construction noise are defined in Table 4.2.
Should non-compliance of the noise quality criteria occur, actions in accordance
with the Action Plan in Table 4.3 shall be carried out.
Table 4.2 Action and Limit Levels for Construction Noise
Monitoring
Time Period |
Action |
Limit |
0700-1900 hrs on normal weekdays |
When one documented compliant is received |
75* dB(A) |
Table 4.3
Event and Action Plan for Noise
EVENT |
ACTION |
|||
ET |
IEC |
ER |
Contractor |
|
Action Level |
1.
Notify IEC and Contractor;
2.
Carry out investigation;
3.
Report the results of investigation to the IEC and
Contractor;
4.
Discuss with the Contractor and formulate remedial
measures;
5.
Increase monitoring frequency to check mitigation
effectiveness |
1.
Review the analysed results submitted by the ET;
2.
Review the proposed remedial measures by the Contractor and
advise the ER accordingly;
3.
Supervise the implementation of remedial measures |
1.
Confirm receipt of notification of failure in writing;
2.
Notify Contractor;
3.
Require Contractor to propose remedial measures for the
analysed noise problem;
4.
Ensure remedial measures are properly implemented |
1.
Submit noise mitigation proposals to IEC;
2.
Implement noise mitigation proposals |
Limit Level |
1.
Notify IEC, ER, EPD and Contractor;
2.
Identify source;
3.
Carry out investigation;
4.
Report the results of investigation to the IEC and
Contractor;
5.
Discuss with the Contractor and formulate remedial
measures;
6.
Increase monitoring frequency to check mitigation
effectiveness |
1.
Review the analysed results submitted by the ET;
2.
Review the proposed remedial measures by the Contractor and
advise the ER accordingly;
3.
Supervise the implementation of remedial measures |
1.
Confirm receipt of notification of failure in writing;
2.
Notify Contractor;
3.
Require Contractor to propose remedial measures for the
analysed noise problem;
4.
Ensure remedial measures are properly implemented |
1.
Submit noise mitigation proposals to IEC;
2.
Implement noise mitigation proposals |
Results of operational noise assessment indicate
that the NSRs will not be affected by fixed plant
noise sources and therefore operational phase noise monitoring is not required.