5          NOISE IMPACT ASSESSMENT

 

5.1              Introduction

 

This Section presents the potential noise impacts associated with the Proposed Beach Development at Lung Mei during the construction and operational phases.

 

5.2       Relevant Legislation and Guidelines

 

5.2.1    Construction Phase

 

The principal legislation relating to the control of construction noise is the Noise Control Ordinance (Cap 400) (NCO).  A number of technical memoranda (TMs) have been issued under the NCO to stipulate control approaches and criteria and those which may be relevant to the construction works of the Proposed Beach Development include the following:

 

·          Technical Memorandum on Noise from Percussive Piling (PP-TM); and

 

·          Technical Memorandum on Noise from Construction Work other than Percussive Piling (GW-TM).

 

Apart from the above, the Environmental Impact Assessment Ordinance (Cap 499) (EIAO) also provides means to assess construction noise impacts.  The Technical Memorandum on Environmental Impact Assessment Process (EIAO-TM), issued under the EIAO, provides guidelines and daytime noise criteria for evaluating construction noise impacts.

 

Percussive Piling

 

Under the PP-TM, percussive piling is prohibited at any time on Sundays and general holidays and during the weekday evening and night-time hours (1900-0700 hours, Monday through Saturday).  A Construction Noise Permit (CNP) is required for such works during weekday daytime hours (0700-1900 hours, Monday through Saturday). 

 

General Construction Works

 

Under the EIAO, noise impact arising from general construction works during normal working hours (ie 0700 to 1900 hours on any day not being a Sunday or general holiday) at the openable windows of buildings is to be assessed in accordance with the noise criteria as given in the EIAO-TM.  The EIAO-TM noise standards are presented in Table 5.1.

 

Table 5.1EIAO-TM Daytime Construction Noise Standard

Use

Noise Standard, Leq, 30 min dB(A)

Domestic Premises

75

Educational Institutions (normal periods)

Educational Institutions (during examination periods)

70

65

 

When assessing a CNP application for the use of Powered Mechanical Equipment (PME) during restricted hours, the Noise Control Authority will compare the Acceptable Noise Levels (ANLs), as promulgated in GW-TM, and the corrected noise levels (CNLs) (after accounting for factors such as barrier effects and reflections) associated with the proposed PME operations.  The ANLs are related to the noise sensitivity of the area in question and different Area Sensitivity Ratings have been established to reflect the background characteristics of different areas.  The relevant ANLs are shown in Table 5.2.

 

The Noise Control Authority will consider a well-justified CNP application, once filed, for construction works within restricted hours as guided by the relevant Technical Memoranda issued under the NCO.  The Noise Control Authority will take into account adjoining land uses and any previous complaints against construction activities at the site before making a decision in granting a CNP.  Nothing in this EIA Report shall bind the Noise Control Authority in making his decision.  The Noise Control Authority may include any conditions in a CNP that it considers appropriate.  Failure to comply with any such conditions may lead to cancellation of the CNP and prosecution action under the NCO.

 

Table 5.2:  Acceptable Noise Levels (ANL, Leq, 5 min dB(A))

Time period

Area Sensitivity Rating

A

B

C

All days during the evening (1900-2300 hours) and general holidays (including Sundays) during the day and evening (0700-2300 hours)

60

65

70

All days during the night-time (2300-0700 hours)

45

50

55

 

5.2.2    Operational Phase

 

Fixed plant noise is controlled under Section 13 of the NCO and the predictions are made in accordance with the Technical Memorandum on Noise from Places other than Domestic Premises, Public Places or Construction Sites (IND-TM).  The criteria noise limits are set out in the EIAO-TM as follows:

 

·          The total fixed source noise level at the facade of the nearest NSR is at least 5 dB(A) lower than the appropriate ANL (as shown in Table 5.3) as specified in the IND-TM; or

·          Where the prevailing noise level in the area is 5 dB(A) or more below the appropriate ANL, the total fixed source noise level must not exceed this noise level.  Future check of prevailing noise levels will be made during baseline noise measurement prior to operation of the Project.

 

The criteria noise limits stipulated in the IND-TM are dependent on the Area Sensitivity Rating (ASR) of the NSRs, as shown in Table 5.3.

 

Table 5.3ANLs to be used as Operational Noise Criteria

Time Period

Leq, 30min dB(A))

ASR "A"

ASR "B"

ASR "C"

Daytime 0700-1900

60

65

70

Evening 1900-2300

60

65

70

Night-time 2300-0700

50

55

60

 

As the Project Site is located in a rural area and no influencing factors affect the NSRs, an ASR “A” has been assumed for the NSRs located in the vicinity.  Baseline noise measurements were made to determine the prevailing noise levels at Lung Mei and to establish the noise limit for the assessment of the operational noise impact.  Details of the noise measurements are provided in Section 5.3.3.

 

The Area Sensitive Rating assumed in this Report is for the purpose of an indicative assessment only, given that there are currently no influencing factors assumed in the vicinity of the NSRs.  It should be noted that fixed noise sources are controlled under Section 13 of the NCO.  At the time of investigation, the Noise Control Authority shall determine noise impact from concerned fixed noise sources on the basis of prevailing legislation and practices being in force, and taking account of contemporary conditions / situations of adjoining land uses.  Nothing in this Report shall bind the Noise Control Authority in the context of law enforcement against all the fixed noise sources being assessed.

 

5.3       Baseline Conditions and NSRs

 

5.3.1    Baseline Condition

 

The Proposed Beach Development is located at Lung Mei in Tai Po (Figure 5.1).  Two villages, Lung Mei Tsuen and Lo Tsz Tin Tsuen, are located to the north of the Project Site.  The Plover Cove Reservoir and a number of water activity centres are located at Tai Mei Tuk at a distance of about 360 m to the east of the Proposed Beach Development.  The background noise environment is dominated by the road traffic noise from Ting Kok Road.

 

5.3.2    Noise Sensitive Receivers

 

Village houses at Lung Mei and Lo Tsz Tin have been identified as noise sensitive receivers (NSRs) that may be affected by noise associated with the construction and operation of the Proposed Beach Development (Figure 5.1).  The planned/committed noise sensitive developments and uses in the vicinity of the site have also been identified in the vicinity of the Project Site and are presented in Figure 5.1.  Photographs showing the identified NSRs are presented in Appendix D1.

 

Assessment points have been selected to represent the identified NSRs for carrying out the noise assessment (Appendix D1).  The village house at No. 103 Lung Mei has been used to represent an NSR instead of No. 101 Lung Mei as the latter has been converted to a restaurant and no longer considered as an NSR.  However, assessment has also been conducted at No. 101 Lung Mei considering its potential change to residential use in future.  The locations of the noise assessment points are shown in Figure 5.2 and presented in Table 5.4. 

 

Table 5.4Selected Noise Assessment Points

NSR

Location

Type of Uses

N1

Village house - No. 165A Lung Mei

Residential (3-Storey)

N2

Village house - No. 103 Lung Mei

Residential (3-Storey)

N2a

House - No. 101 Lung Meu

Residential converted to Commercial (3-storey)

N3

Village house - No. 70 Lo Tsz Tin

Residential (3-Storey)

N4

Village house - No. 79 Lo Tsz Tin

Residential (3-Storey)

 

5.3.3    Baseline Noise Measurement

 

To investigate the prevailing noise levels at the NSRs at Lung Mei, noise measurements were conducted on 4 March 2007 at two locations, as indicated in Figure 5.3 and Appendix D1.  The noise measurements were conducted using a 01 dB Solo Sound Level Meter (Type 1) which was calibrated using a B&K Sound Level Calibrator Type 4231 with a calibration signal of 94.0 dB(A) at 1kHz.  The measurement was logged at LAeq, in fast time weighting.  Calibration and measurement procedures in the IND-TM were followed.

 

The measurement results are summarised in Table 5.5. 

 

Table 5.5Measured Prevailing Free-field Noise Levels

Noise Measurement Location

Noise Measurement Period

Lmin, 30min,

 dB(A)

Leq, 30min,   

dB(A)

Lmax, 30min,

 dB(A)

M1

12:16:00 - 12:46:00

39.0

59.7

79

12:46:00 - 13:16:00

39.1

59.5

75.4

13:16:00 - 13:46:00

40.1

58

72.5

Average Leq, 30min = 59 dB(A)

M2

13:47:03 - 14:17:03

36.9

52.2

63.3

14:17:03 - 14:37:03

40.5

51.9

69.3

14:47:03 - 15:17:03

41.5

53.1

65.8

Average Leq, 30min = 52 dB(A)

 

A correction factor of 3 dB(A) for façade effect is applied to the free-field noise measurement results to represent the noise level at building facades.  With the inclusion of facade correction, the measured prevailing noise levels are in the range of 55 – 62 dB(A), and therefore a lower level of 55 dB(A) LAeq, 30min is adopted as the daytime noise limit for NSRs located at Lung Mei for the operational noise assessment.  

 

5.4       Potential Sources of Impacts

 

5.4.1    Construction Phase

 

Potential impacts to the NSRs during the construction phase of the Proposed Beach Development are expected to arise mainly from PME operating at construction work sites.  The key construction activities are as follows:

 

·          Site formation;

 

·          Localised widening of Ting Kok Road;

 

·          Construction of bathing facilities;

 

·          Construction of two groynes; and

 

·          Construction of culverts to the east and west of the Project Site.

 

To minimise the construction noise impacts, press-in piling method has been proposed to be used instead of percussive piling.  In the event of percussive piling being required as a result of geological constraints at the Project Site, a CNP should be applied for the percussive piling works in accordance with the PP-TM.  As the issuance of a CNP by the Noise Control Authority would depend on the information submitted in the CNP application by the Contractor, and the calculations to be conducted therein according to the PP-TM, the assessment of percussive piling noise has not been included in this assessment.

 

The normal working hours of the contractor will be between 0700 and 1900 hours from Monday to Saturday (except public holidays).  Given the constraints of the Project Site and scale of the concurrent construction activities, there will be a limited number of plant items operating on site at any one time.  The construction noise assessment has been undertaken based on the construction programme and the plant inventory presented in Appendices D2 and D3 respectively.  All the PMEs listed in the plant inventory are checked by the CEDD to be available in the market.  The validity of the inventory has also been reviewed by CEDD and confirmed to be practical and feasible for completing the works for the Proposed Beach Development within the scheduled timeframe.

 

5.4.2    Operational Phase

 

Noise associated with the operational phase of the Proposed Beach Development is expected to arise mainly from the fixed plant at the bathing facilities.  The dominant noise sources are expected to include the following equipment:

 

·          water and fire service pumps;

·          mechanical ventilation for plant rooms; and

·          public address (PA) systems.

 

The Proposed Beach Development will not have night-time operation and the operation hours of the PA systems will follow those of the Proposed Beach Development as indicated in Table 5.6. 

 

Table 5.6Operation Hours of the Proposed Beach Development

Period

Time

Remark

April, May, September and October

9:00 am - 6:00 pm

Daily

From June to August

9:00 am - 6:00 pm

Weekdays

8:00 am - 7:00 pm

Saturdays, Sundays &    Public Holidays

From November to March

8:00 am - 5:00 pm

Daily

 

As the detailed design of the fixed plant equipment associated with the operation of the Proposed Beach Development is not yet available at this stage, assumptions on the sound power levels (SWLs) of the equipment have been made for the operational noise assessment.  These assumptions are presented in Table 5.7.  The operational plant inventory is presented in Appendix D6.  The maximum allowable SWLs presented in Table 5.7 should be included in the tender specification to ensure the assumptions for the operational noise impact assessment remain valid.  The suppliers of equipment should guarantee the specified SWLs, with the characteristics of tonality, impulsiveness and intermittency accounted for, by providing certificate of measurement and verify the SWL during testing and commissioning in accordance with international standard procedures.  If necessary, the suppliers should apply attenuation measures (eg use of silencers) to achieve the guaranteed noise levels during the detailed design stage.

 

Table 5.7:  Assumption on the Sound Power Levels of the Operational Equipment

Operational Equipment

Maximum Allowable Sound Power Level, dB(A)

Pumps

92

Mechanical Fan

88

PA system

100 dB(A) for the loudspeaker cluster located at car park and lifeguard lookout

98 dB(A) for the loudspeaker cluster located at building facilities

 

5.5       Assessment Methodology

 

5.5.1    Construction Phase

 

The methodology for the noise impact assessment follows the procedures outlined in the GW-TM, and is summarised as follows:

 

·          Identify of a list of construction plant likely to be required for each construction activity;

 

·          Assign sound power levels (SWLs) to the PME proposed based on the GW-TM.  When the PME is not listed in the TMs, reference is made to SWLs provided in the document prepared by the Noise Control Authority (http://www.epd.gov.hk/epd/english/application_for_licences/guidance/files/OtherSWLe.pdf) and British Standard 5228, Noise and Vibration Control on Construction and Open Sites - Part 1 (BS5228: Part 1: 1997) ([1]);

 

·          Calculate the SWLs for each construction activity.  With the construction works which will not be carried out simultaneously according to the construction sequences, maximum SWL of each activity is selected to predict the maximum construction noise levels at the NSRs;

 

·          Calculate the correction factor, using a conservative approach, based on the horizontal distance between the NSRs and the notional noise source position of the work sites. The notional source position of the work site was established in accordance with the procedures stated in the GW-TM; 

 

·          Apply corrections in the calculations such as potential screening effects and acoustic reflection, if any; and

 

·          Predict the construction noise levels at NSRs in the absence of any mitigation measures.

 

Noise impacts at NSRs were subsequently evaluated by comparing the predicted noise levels with the EIAO-TM daytime construction noise limits (Leq, 30min dB(A)), as outlined in Section 5.2.1.

 

In reality, some of the PME will not be operating continuously within a work site.  Utilisation rates for the PME that have been adopted for the calculation of the SWL are summarised in Table 5.8.  The utilisation rates has also been reviewed by CEDD and confirmed to be practical and feasible to achieve the construction programme. 

 

Table 5.8:  Utilisation Rates for PME

PME

Utilisation Rate

Vibratory roller, timber sawing machine, bar ender and cutter, electrical drill, vibratory compactor

50%

Mobile crane, excavator, vibratory poker, concrete lorry mixer, silent piler, road roller, lorry, pneumatic breaker, backhoe, derrick lighter

80%

Diesel generator, grab dredger, water pump, air compressor, pelican barge

100%

 

5.5.2    Operational Phase

 

The methodology for the noise impact assessment follows the procedures outlined in the IND-TM.  The methodology for the fixed plant noise assessment is summarised as follows:

 

·          Identify types of equipment and the number of equipment;

 

·          Calculate the maximum SWL for each type of equipment;

 

·          Identify representative NSRs that may be affected by the fixed plant; 

 

·          Calculate the correction factor, using a conservative approach, based on the horizontal distance between the NSRs and the fixed plant sources; and

 

·          Present the results in terms of Leq, 30min dB(A), as specified in the TM.

 

Under normal circumstances, it is envisaged that the PA system will not be operated continuously.  As advised by Leisure and Cultural Services Department (LCSD), the typical operating time for the PA system is 2 minutes in every 15 minutes, and therefore it is assumed that the operating time of the PA system will be 4 minutes in every 30 minutes and an appropriate correction is included to account for this mode of operation.  The assessment has also taken into account the barrier correction and facade correction of +3 dB(A).  The predicted noise levels at the NSRs are compared with the criteria set out in Section 5.3.3.  Mitigation measures have been recommended in cases where an exceedance is predicted.  

 

5.6       Evaluation of Impacts

 

5.6.1    Construction Phase

 

Owing to the proximity of the NSRs to the Project Site, the NSRs would be adversely affected by the construction activities.  The unmitigated construction noise levels at the representative NSRs have been predicted and are summarised in Table 5.9.  Details of the calculations are presented in Appendix D4. 

 

Table 5.9:  Predicted Construction Noise Levels (Unmitigated)

NSR

Location

Predicted Construction Noise Levels,  dB(A)

N1

Village house - No. 165A Lung Mei

66 – 79

N2

Village house - No. 103 Lung Mei

68 – 76

N2a

House - No. 101 Lung Mei

69 – 77

N3

Village house - No. 70 Lo Tsz Tin

71 – 78

N4

Village house - No. 79 Lo Tsz Tin

67 – 80

Note:

 (a)   The construction noise criterion is 75 dB(A).

 

To mitigate the construction noise impact, practicable mitigation measures, including the use of quiet construction plant and movable noise barriers, are recommended to be implemented when works are undertaken close to the NSRs.  In addition, site hoardings at the particular work site boundary may be provided for achieving screening effect, provided that the hoardings have no openings or gaps and meet the same specifications for movable noise barriers.  The proposed movable noise barriers should be at least 3m high with a surface density of not less than 7 kg m-2, which could provide a minimum of 5 dB(A) attenuation.  Skid footing of movable noise barriers should be located at a distance not more than a few metres of stationary plant and mobile plant such that the NSRs would not have direct line of sight to the plant.  The length of the barriers should also be at least five times greater than its height.  The locations of the proposed movable noise barriers during construction phase are presented in Figure 5.4.  The contractor will ensure that the hoardings and movable noise barrier are properly maintained throughout the construction period.  Details of the recommended mitigation measures are presented in Tables 5.12 and 5.13.

 

The mitigated construction noise levels at the representative NSRs are summarised in Table 5.10. Details of the calculations are presented in Appendix D5.  The mitigated construction noise levels are below the daytime construction noise criterion of 75 dB(A) throughout the construction period. 

 

Table 5.10:  Predicted Construction Noise Levels (Mitigated)

NSR

Location

Predicted Construction Noise Levels,  dB(A)

N1

Village house - No. 165A Lung Mei

62 – 72

N2

Village house - No. 103 Lung Mei

64 – 70

N2a

House - No. 101 Lung Mei

65 – 70

N3

Village house - No. 70 Lo Tsz Tin

66 – 71

N4

Village house - No. 79 Lo Tsz Tin

63 – 72

Notes:

(a)     Mitigated with quiet construction plant and noise barriers.

(b)     Construction noise criterion is 75 dB(A).

 

The normal working hours of the contractor will be between 0700 and 1900 hours from Monday to Saturday (except public holidays).  Should evening and night work between 1900 and 0700 hours or work on public holidays (including Sunday) be required, the contractor should submit a CNP application for consideration by the Noise Control Authority.  Conditions stipulated in CNPs should be strictly followed.

 

5.6.2    Operational Phase

 

The predicted operational noise levels at the NSRs are summarised in Table 5.11. Details of calculation are presented in Appendix D6.  With the maximum specified SWLs for the fixed plant, the predicted operational noise levels at the representative NSRs comply with the daytime noise criteria as discussed in Section 5.3.3.   

 

Table 5.11:   Predicted Operational Noise Levels

NSR

Location

Predicted Operational Noise Levels, dB(A)

Operational Noise Criterion, dB(A)

N1

Village house - No. 165A Lung Mei

52

55

N2

Village house - No. 103 Lung Mei

53

55

N2a

House - No. 101 Lung Mei

54

55

N3

Village house - No. 70 Lo Tsz Tin

52

55

N4

Village house - No. 79 Lo Tsz Tin

49

55

 

It should be noted that the operational noise assessment presented above is based on a worst-case scenario in which the equipment are assumed to be operated simultaneously, which is unlikely to occur in real situation.

 

5.7       Mitigation Measures and Residual Impacts

 

5.7.1    Construction Phase

 

The contractor is required to adopt the recommended mitigation measures as specified in Tables 5.12 and 5.13 to mitigate the construction noise impact at different construction stages.

 

Table 5.12:    Use of Quiet PME

Quiet PME

Reference

SWL, dB(A)

Mobile Crane

SWL listed in the data base of quality powered mechanical equipment prepared by the Noise Control Authority

107

Tracked Loader

British Standard 5228 – Table C3, Reference No. 16

104

Pneumatic breaker

British Standard 5228 – Table C2, Reference No. 10

110

Concrete Lorry Mixer

British Standard 5228 – Table C6, Reference No. 23

100

Excavator

British Standard 5228 – Table C3, Reference No. 97

105

 

Table 5.13:   Summary of Recommended Use of Noise Barrier

ID

Task

Work Activity

Recommended Mitigation Measures

1a

Construction Works on Land

Site Formation, construction of seawall, ramp, staircase, retaining walls, sump tanks for grey water system and superstructure foundation

·          Movable noise barrier should be provided for excavator and mobile crane;

·          Timber sawing machine should be operated behind site hoarding/ movable noise barrier; and

·          Concrete lorry mixer should be operated behind site hoarding/movable noise barrier.

1b

Localised road widening along Ting Kok Road

·          Timber sawing machine should be operated behind movable noise barrier; and

·          Movable noise barrier should be provided for excavator and mobile crane.

2

Car Park Paving

·          Movable noise barrier should be provided for excavator.

3a

Building Works

Piling works

3b

Foundation and tanking

·          Movable noise barrier should be provided for excavator, mobile crane and earth auger; and

·          Timber sawing machine should be operated behind site hoarding/ movable noise barrier.

3c

Superstructure

·          Movable noise barrier should be provided for mobile crane; and

·          Timber sawing machine should be operated behind site hoarding/ movable noise barrier.

3d

Building finishes & internal fitting-out

·          Movable noise barrier should be provided for mobile crane.

4

Dredging for the Groynes

-

5

Rock filling for the Groynes

·          Movable noise barrier should be provided for excavator and derrick lighter.

6a

Box Culvert Construction

Construction of gabion channel

·          Movable noise barrier should be provided for excavator.

6b

Construction of western culvert

·          Movable noise barrier should be provided for excavator, mobile crane;

·          Concrete lorry mixer should be operated behind site hoarding/movable noise barrier.

6c

Construction of eastern culvert

·          Concrete lorry mixer should be operated behind site hoarding/movable noise barrier.

6d

Construction of 90m box culvert

·          Site hoarding should be provided for work site.

7

Sand Filling

·          Movable noise barrier should be provided for excavator.

Remark:

(1) Movable noise barriers and site hoarding should be at least 3m high with a surface density of not less than 7 kg m-2.

 

In addition to the recommended mitigation measures given in Table 5.12, good site practices should be implemented by the contractor to minimise the construction noise impact.  The site practices listed below should be adopted during the construction phase:

 

·          Only well-maintained plant should be operated on-site and plant should be serviced regularly during the construction programme;

·          Silencers or mufflers on construction equipment should be utilized and should be properly maintained during the construction programme;

·          Mobile plant, if any, should be sited as far from NSRs as possible;

·          Machines and plant (such as trucks) that may be in intermittent use should be shut down between work periods or should be throttled down to a minimum;

·          Plant known to emit noise strongly in one direction should, wherever possible, be orientated so that the noise is directed away from the nearby NSRs; and

·          Material stockpiles and other structures should be effectively utilised, wherever practicable, in screening noise from on-site construction activities.

 

With the implementation of recommended mitigation measures, no residual impact at the NSRs is anticipated. 

 

5.7.2    Operational Phase

 

Based on the specified maximum SWLs for the fixed plant, the predicted operational noise levels at the representative NSRs are expected to comply with the daytime criteria.  As discussed in Section 5.4.2, the suppliers of equipment should apply attenuation measures (eg silencers), if necessary, to achieve the guaranteed noise levels. 

 


5.8       Cumulative Impact

 

5.8.1    Construction Phase

 

As mentioned in Section 3.13, the construction works of Tolo Harbour Sewerage of Unsewered Areas Stage I Phase IIC (Agreement No. CE 18/94) (Phase IIC works) is anticipated to be from November 2008 to November 2010, which coincides with construction undertaken for the Proposed Bathing Beach Development, but the details of the construction programme and associated plant inventory are not available at this stage.  Phase IIC works is anticipated to involve mainly excavation and pipe laying works but will be in a smaller scale as a result of limited space at Lung Mei Village and Lo Tsz Tin Village.  Using a conservative approach, the construction noise impact from Phase IIC works is assumed to be of similar magnitude as that from the Proposed Bathing Beach Development, and therefore a correction of +3 dB(A) will be included to account for an additional noise source.  The maximum mitigated construction noise levels due to the construction of Proposed Bathing Beach is predicted to be 72 dB(A), with the inclusion of 3 dB(A), the cumulative noise level is 75 dB(A), which complies with the construction noise criterion.       

 

5.8.2    Operational Phase

 

No cumulative impact is anticipated during the operational phase.

 

5.9       Environmental Monitoring and Audit Requirements

 

5.9.1    Construction Phase

 

Noise monitoring is recommended during the construction phase to ensure compliance with the noise criterion at the NSRs.  Weekly noise monitoring should be undertaken at the representative NSRs (N1 – N4).  If house No. 101 Lung Mei (N2a) is changed to residential use, noise monitoring should be conducted at N2a instead of N2.  Regular site audits at the frequency of twice a month should be conducted to ensure that the recommended mitigation measures are properly implemented during the construction stage. 

 

5.9.2    Operational Phase

 

Results of operational noise assessment indicate that the NSRs will not be affected by fixed plant noise sources and therefore operational phase noise monitoring is not required. 

 

5.10     Conclusions

 

Owing to the proximity of the NSRs to the Project Site, mitigation measures are required to be implemented to mitigate the construction noise impacts.  Practicable mitigation measures, including use of quiet construction plant and movable noise barriers, have been recommended to be implemented for different work stages.  With the implementation of mitigation measures, the mitigated construction noise levels at the representative NSRs are anticipated to comply with the construction noise criterion of 75 dB(A) throughout the construction period.  Noise monitoring during the construction stage is recommended to ensure compliance with the relevant noise criteria.  The potential cumulative noise impacts from the contemporary occurrence of the Phase IIC works have been considered, and the assessment result indicates that the cumulative construction noise level at the NSRs complies with the construction noise criterion of 75 dB(A).

 

The predicted operational noise levels at the representative NSRs are expected to comply with the daytime criteria based on the assessment using a set of specified maximum SWLs for the fixed plant to be installed at the Proposed Beach Development.  Attenuation measures, if required, will be provided to the fixed plant for achieving the guaranteed noise levels during the detailed design stage, and therefore operational phase noise monitoring is not required.

 



([1]) British Standard 5228, Noise and Vibration Control on Construction and Open Sites - Part 1. Code of Practice for Basic Information and Procedures for Noise and Vibration Control