The requirements, methodology, equipment,
monitoring locations, criteria and protocols for the monitoring and audit of
noise impacts during construction of the Project are presented in this section.
Noise measurements should be carried out in
accordance with the guidelines given in Annex
– General Calibration and Measurement Procedures of Technical Memorandum on Noise from Construction Work other than
Percussive Piling (GW-TM).
Whilst the Noise Control Ordinance (NCO) does not provide for the statutory
control of construction activities occurring on weekdays during normal working
hours (ie Monday to Saturday inclusive 0700-1900
hours), a daytime standard of Leq(30min)
75dB(A) as stipulated in Annex 5 of the Technical
Memorandum on Environmental Impact Assessment Process (EIAO-TM) will be adopted as the noise criterion for all residential
dwellings; while a daytime standard of Leq(30min)
70dB(A) will be adopted for all educational institutions during normal school
days and Leq(30min) 65dB(A) during
examination periods.
The construction
noise levels will be measured in terms of A-weighted equivalent continuous
sound pressure level (Leq) measured in
decibels dB(A).
Leq(30min) should be used as the
monitoring parameter for the time period between 0700-1900 hours on normal
weekdays.
Supplementary
information for data auditing, two statistical sound levels L10 and
L90; the levels exceeded for 10 and 90 percent of the time
respectively, should also be recorded during the monitoring for reference. A sample data record sheet is shown in Annex
C for reference.
Noise measurements
should generally not be made in the presence of fog, rain, wind with a steady
speed exceeding 5ms-1 or wind with gusts exceeding 10ms-1. The wind speed should be checked with a
portable wind speed meter capable of measuring the wind speed in ms-1.
As referred to the GW-TM, sound level meters in compliance with the International Electrotechnical
Commission Publications 651:1979 (Type 1) and 804:1985 (Type 1) Specifications
should be used for carrying out the noise monitoring. Immediately prior to and following each
noise measurement the accuracy of the sound level meter should be checked using
an acoustic calibrator generating a known sound pressure level at a known
frequency. Measurements may be
accepted as valid only if the calibration levels from before and after the
noise measurement agree to within 1.0 dB.
The ET should ensure that the equipment is
maintained in a good working order in accordance with the manufacturer's
recommendations with sufficient spare equipment available in the event of
breakdown to maintain the planned monitoring programme.
The ET is responsible for the provision of
the monitoring equipment and will ensure that sufficient noise measuring
equipment and associated instrumentation are available for carrying out the
baseline monitoring and impact monitoring.
All the equipment and associated instrumentation will be clearly
labelled.
Representative locations were selected to
monitor the noise levels from the construction of the Project. The noise monitoring stations are listed
in Table 4.1 and presented in Figure
4.1.
Table 4.1 Noise
Monitoring Stations for
Construction Noise
Monitoring Station |
Description |
KMYLS1 |
|
JCCAH1 |
Jockey Club Care & Attention Home |
The status and locations of noise
sensitive receivers (NSRs) may change after issuing
this Manual and the location of the noise monitoring station may need to be
adjusted accordingly. If such
changes occur, the ET should propose an updated monitoring location for the
agreement from the ER, IEC and EPD.
When alternative monitoring location is proposed,
the following criteria, as far as practicable, should be followed:
·
At
locations close to the major site activities which are likely to have noise
impacts;
·
Close
to the NSRs; and
·
For
monitoring locations located in the vicinity of the NSRs,
care should be taken to minimise disturbance to the occupants during
monitoring.
The monitoring station will normally be at
a point 1 m from the exterior of the NSR building façade and at a height of
approximately 1.2 m above ground or at the height that has the least obstructed
view of the construction activities in relation to the NSR. If access to the normal monitoring
position cannot be obtained, an alternative position will be chosen, and a
correction to the measurements should be made, if appropriate. For instance, a correction of +3 dB(A) should be made to free-field measurements. The ET should agree with the ER, IEC,
EPD and the owners/occupants of the premises on the monitoring position. Once the positions for the monitoring
stations are chosen, the baseline monitoring and the impact monitoring should
be carried out at the same positions.
The ET
should carry out baseline noise monitoring prior to the commencement of any
construction works. The baseline
monitoring should be measured for a continuous period of at least 14
consecutive days at a minimum logging interval of 30 minutes for daytime and 15
minutes (as three consecutive Leq(5min) readings) for evening, holidays
and night-time.
Before
commencing the baseline monitoring, ET should inform the Contractor, IEC, ER
and the EPD of the baseline monitoring schedule programme such that relevant
parties could conduct on-site audit to ensure accuracy of the baseline
monitoring results.
During the
baseline monitoring, there should not be any construction activities in the
vicinity of the monitoring stations.
Any non-Project related construction activities in the vicinity of the
stations during the baseline monitoring should be noted and the source(s) and
location(s) be recorded.
In case the
baseline monitoring could not be carried out at any of the designated
monitoring locations during the baseline monitoring period, the ET should carry
out the monitoring at alternative location which could effectively represent
the baseline conditions at the impact monitoring locations. The alternative baseline monitoring
locations should be agreed with the ER and IEC and approved by EPD.
In
exceptional cases, when insufficient baseline monitoring data or questionable
results are obtained, the ET should liaise with the ER, IEC and EPD to agree on
an appropriate set of data to be used as a baseline reference.
Noise monitoring should be carried out at
all the designated monitoring stations.
An initial guide on the monitoring is to obtain one set of 30-minute
measurement at each station between 0700 and 1900 hours on normal weekdays at a
frequency of once a week when construction activities are underway.
If construction works are extended to include
works during the hours between 1900 and 0700 hours, or on general holidays and
Sundays, applicable Construction Noise Permits (CNPs)
will be obtained by the Contractor under the NCO requirements, and the frequency and scope of monitoring will be
determined by EPD in the capacity of the Noise
Control Authority (NCA).
4.7
Environmental
Quality Performance Limits
Action and Limit (A/L) Levels provide an
appropriate framework for the interpretation of monitoring results. Interpretation of monitoring results is
undertaken through checking them against the Action and Limit (A/L) Levels
defined in Table 4.2.
Table 4.2 Action
and Limit Level for Construction Noise Monitoring
Time
Period |
Action
Level |
Limit
Level |
0700 – 1900
hours on normal weekdays |
When one
documented complaint is received from any one of the sensitive receivers |
75 dB(A)(Note) |
Note: (1)
Acceptable Noise Levels for Area Sensitivity Rating of
A/B/C. Limit Level is reduced to 70dB(A) for schools
and 65dB(A) during school examination periods. (2)
If works are to be carried out during restricted hours,
the conditions stipulated in the construction noise permit issued by the NCA
have to be followed. |
To account for cases where ambient noise
levels, as identified by baseline monitoring, approach or exceed the stipulated
Limit Level prior to commencement of construction, a Maximum Acceptable Impact
Level, which incorporates the baseline noise level and the identified
construction noise Limit Level, might be defined upon agreement with the
EPD. This amended level will,
therefore, be greater than 75 dB(A) and will represent
the maximum acceptable noise level at a specific monitoring station.
For compliance checking, after taking into
account any adjustments agreed with EPD, comparison with either the Limit or
the Maximum Acceptable Impact Level will represent the governing criteria for
noise impact assessment during impact monitoring.
The ET should compare the impact
monitoring results with the noise criteria as defined in Table 4.2. In cases
where exceedance of these criteria occurs, actions
should be carried out in accordance with the Action Plan shown in Table 4.3.
Table 4.3 Event
and Action Plan for Construction Noise
Event |
Action |
|||
|
ET |
IEC |
ER |
Contractor |
Action Level |
1.
Notify IEC and Contractor; 2.
Carry out investigation; 3.
Report the results of investigation to the IEC, ER and Contractor; 4.
Discuss with the Contractor and formulate remedial measures; 5.
Increase monitoring frequency to check mitigation effectiveness. |
1.
Review the analysed results submitted by the ET; 2.
Review the proposed remedial measures by the Contractor and advise the ER
accordingly; 3.
Supervise the implementation of remedial measures. |
1.
Confirm receipt of notification of failure in writing; 2.
Notify Contractor; 3.
Require Contractor to propose remedial measures for the analysed
noise problem; 4.
Ensure remedial measures are properly implemented. |
1.
Submit noise mitigation proposals to IEC; 2.
Implement noise mitigation proposals. |
Limit Level |
1. Identify source; 2. Inform IEC and ER: 3. Repeat measurements to confirm findings; 4.
Increase monitoring frequency; 5. Carry out analysis of Contractor's working
procedures to determine possible mitigation to be implemented; 6. Inform IEC,
ER and EPD the causes and actions taken for the exceedances; 7. Assess
effectiveness of Contractor's remedial actions and keep IEC, EPD and ER
informed of the results; 8. If exceedance stops, cease additional monitoring. |
1. Discuss amongst ER, ET, and Contractor on the
potential remedial actions; 2. Review Contractors
remedial actions whenever necessary to assure their effectiveness and advise
the ER accordingly; 3. Supervise the
implementation of remedial measures. |
1. Confirm receipt of notification of failure in
writing; 2. Notify
Contractor; 3. Require
Contractor to propose remedial measures for the analysed
noise problem; 4. Ensure
remedial measures properly implemented; 5. If exceedance continues, consider what portion of the work
is responsible and instruct the Contractor to stop that portion of work until
the exceedance is abated. |
1. Take immediate action to avoid further exceedance; 2. Submit
proposals for remedial actions to IEC within 3 working days of notification; 3. Implement the
agreed proposals; 4. Resubmit
proposals if problem still not under control; 5. Stop the
relevant portion of works as determined by the ER until the exceedance is abated. |
It is necessary to undertake regular
environmental audits and site inspections to ensure those recommended
mitigation measures were properly implemented. The requirements of the environmental
audit programme were set out in Section 8
of the Manual.
The audit programme will verify the
implementation status and evaluate the effectiveness and stability of the
mitigation measures.
4.10.1
Construction Phase
In order to reduce the noise impact of
construction site activities on nearby NSRs, the
following mitigation measures have been considered:
·
Good
Site Practice;
·
Use
of quiet PME;
·
Use
of acoustic enclosure;
·
Adoption
of movable noise barriers, and
·
Scheduling
of PME/construction activities.
Good Site Practices
Good site practices and noise management can
considerably reduce the impact of construction site activities on nearby Noise
Sensitive Receivers (NSRs). The noise benefits
of these practices can vary according to specific site conditions and
operations. The following site practices should be followed during the
construction of the Project:
·
Only
well-maintained plant should be operated on-site and plant should be serviced
regularly during the construction program;
·
Silencers
or mufflers on construction equipment should be utilized and should be properly
maintained during the construction program;
·
Mobile
plant, if any, should be sited as far from NSRs as
possible;
·
Machines
and plant (such as trucks) that may be in intermittent use should be shut down
between work periods or should be throttled down to a minimum;
·
Plant
known to emit noise strongly in one direction should, wherever possible, be
orientated so that the noise is directed away from the nearby NSRs;
·
Material
stockpiles and other structures should be effectively utilised, wherever
practicable, in screening noise from on-site construction activities; and
·
The
contractor should liaise with the school regarding the examination
periods. Noisy construction
activities, including piling, excavation and earth-breaking works, will be
carried out outside the examination periods.
Use of Quiet Powered Mechanical Equipment
(PME)
The use of quiet PME was considered to be
a practicable means to mitigate the construction noise impact. Quiet
plant is defined as a PME having actual SWL lower than the value specified in
the GW-TM.
Use of Acoustic Enclosure
Temporary acoustic
enclosure is a common and effective means to mitigate the noise impact arising
from operation of certain small size PMEs. A frame
covered with noise insulation materials (sound insulation materials with a
superficial surface density of at least 7 kg/m2 or sound absorbing
materials of at least 50mm and average absorption coefficient between 125 Hz
and 4000 Hz of 0.4) could at least 5 dB(A) reduction
for plant items such as hand-held breaker and circular wood saw. The locations of the temporary acoustic
enclosure should be adjusted wherever and whenever necessary to protect the
noise sensitive receivers, the enclosures should have no openings or gaps.
Adoption of Movable Noise Barriers
The use of noise
barriers will be an effective means to mitigate the noise impact arising from
the construction works, particularly for low-rise NSRs.
For the low-rise nature of the NSRs, movable noise
barriers of 3 to 5 m high (depending on the size of the plant that
requires to be screened) with skid footing should be used and located within a
few metres of stationary plant and mobile plant such that the line of sight to
the NSR is blocked by the barriers. The length of the barriers should be
at least five times greater than its height. These movable noise barriers could
produce at least 5 dB(A) noise reduction for mobile
plant such as backhoe and roller as well as large scale plant such as crane.
With reference to A Practical Guide for the Reduction of Noise from
Construction Works, the noise barrier material should have a superficial
surface density of at least 7 kg/m2 and have no openings or gaps.
Scheduling of Construction Works
To
further alleviate the construction noise impacts, only one group of PME (Group
A or B) will be operated during road drainage, utilities and water mains works
at work site of slip road A and also during site works like road resurfacing
and remarking A and B. All noisy
construction activities should be suspended at work site of slip road A and
flyover A during examination period of the
4.10.2
Operational Phase
Notwithstanding the prediction that the NSRs will not be subject to adverse noise impact during the
operational phase of the Project, noise monitoring should be carried out during
the first year after opening to ensure noise compliance.
The ET should
prepare and deposit to EPD, at least 6 months before the operation of the works
under the Project, a monitoring plan for the purpose of assessing the accuracy
of traffic noise predictions by comparing the project noise impact predictions
with the actual impacts. The
monitoring plan should contain information on the monitoring locations,
monitoring schedules, methodology of noise monitoring including noise
measurement procedures, traffic counts and speed checks, and methodology of
comparison with the predicted levels. The ET should implement the monitoring
plan in accordance with the deposited monitoring plan unless with prior
justification. Monitoring details
and results including the comparison between the measured noise levels and the
predicted levels should be recorded in a report to be deposited with EPD within
one month of the completion of the monitoring. The report should be certified by the ET
Leader and the Project Proponent before deposit with EPD.
The traffic noise
levels should be measured twice at 6-month intervals within the first year upon
completion of the Project.
Measurements should be made in terms of the A-weighted L10
over 3 half hour periods during the peak traffic hour,
other parameters including Leq should also
be taken for reference.
As shown in Table 4.4 and Figure 4.1, two designated
monitoring stations are selected for the operational noise monitoring. The status and locations of noise
sensitive receivers may change after this Manual is issued. If such cases exist, the ET Leader
should propose updated monitoring locations and seek approval from the ER and
IEC and agreement from EPD of the proposal.
Table 4.4 Noise
Monitoring Stations for Operational Traffic Noise
Monitoring Station |
Description |
KMYLS1 |
|
JCCAH1 |
Jockey Club Care & Attention Home |
The monitoring
locations should be selected according to the following criteria:-
·
they should be at NSRs in
the vicinity of recommended direct technical remedies; preferably, there should
be one representative monitoring locations near each types of noise screening
element (ie vertical barrier, cantilever barrier and
enclosure);
·
one high floor and one medium floor monitoring points should
be chosen at each location as far as practicable; and
·
selected monitoring
locations should allow monitoring to be done twice within one year after
implementation of the mitigation measures during operation of the Project.
The status and
location of NSRs may change after issuing this
manual. If such case exists, the ET Leader should propose updated monitoring
locations and seek approval from EPD and agreement from the ER and the IEC
before baseline monitoring commences.
When alternative
monitoring locations are proposed, the monitoring locations should be chosen
based on the following criteria:-
·
alternative location should be similarly exposed to
potential noise impacts;
·
it should be close to the NSRs;
and
·
should be located so as
to minimise disturbance to the occupants.
The operational
noise monitoring should be carried out at a distance of 1 m from the openable window and 1.2 m above the floor level of the
noise sensitive receivers identified.
The ET Leader should agree with the IEC on any necessary corrections
adopted.
·
one set of measurements during the morning traffic
peak hour on a normal weekday;
·
one set of measurements during the evening traffic
peak hour on a normal weekday;
·
a concurrent census of traffic flow and percentage
heavy vehicles should be conducted for the far-side and near-side of the road
and the existing road network in the vicinity of each measurement points;
·
average vehicle speed estimated for far-side and
near-side of the road and the existing road network in the vicinity of each
measuring points; and
·
the two sets of monitoring data should be obtained within
the first your of operation.
Measured noise
levels should be compared with the predicted noise levels by applying
appropriate conversion corrections to allow for the traffic conditions at the
time of measurement. A sample data
record sheet for traffic noise monitoring during operational phase is shown in Annex
C for reference.
The measured/
monitored noise levels should be compared with the predicted results and the
predicted traffic flow conditions (calculated noise levels based on concurrent
traffic census obtained). In case
discrepancies are observed, explanation should be given to justify the
discrepancies.