3.
NOISE
3.1.1
Noise impact is likely to arise
from some of the activities during construction phase of the Project. The EIA
recommended a number of mitigation measures that should be implemented to
reduce potential impacts to acceptable limits. A monitoring programme is
recommended for baseline conditions and during the construction phase to
evaluate the performance of the proposed measures.
3.1.2
This section of the Manual
lists all the recommended mitigative and preventive measures in the EIA for the
control of construction noise, and the requirements for baseline and construction
phase noise monitoring.
3.1.3
No
adverse noise impact is expected during operation phase, hence noise monitoring
during operation phase is considered not necessary.
3.2.1
The
construction noise level shall be measured in terms of the A-weighted
equivalent continuous sound pressure level (Leq). Leq(30 min) shall
be used as the monitoring parameter for the time period between 0700-1900 hours
on normal weekdays.
3.2.2
As
supplementary information for data auditing, statistical results such as L10
and L90 shall also be obtained for reference. A sample data record
sheet is shown in Appendix B for reference.
3.3.1
As
referred to in the Technical Memorandum (TM) issued under the Noise Control
Ordinance (NCO), sound level meters in compliance with the International
Electrotechnical Commission Publications 651: 1979 (Type 1) and 804: 1985 (Type
1) specifications shall be used for carrying out the noise monitoring. Immediately
prior to and following each noise measurement, the accuracy of the sound level
meter shall be checked using an acoustic calibrator generating a known sound
pressure level at a known frequency. Measurements may be accepted as valid only
if the calibration level from before and after the noise measurement agree to
within 1.0 dB.
3.3.2
Noise
measurements shall not be made in the presence of fog, rain, wind with a steady
speed exceeding 5ms-1 or wind with gusts exceeding 10ms-1.
The wind speed shall be checked with a portable wind speed meter capable of
measuring the wind speed in ms-1.
3.3.3
The
ET Leader is responsible for the provision of the monitoring equipment. He
shall ensure that sufficient noise measuring equipment and associated
instrumentation are available for carrying out the baseline monitoring, regular
impact monitoring and ad hoc
monitoring. All the equipment and associated instrumentation shall be clearly
labelled.
3.4.1
The
locations of noise monitoring stations are shown in Table 3.1 and Figure
3.1. In case works is
required for restricted hours, monitoring locations may also include those
relevant to the application of Construction Noise Permit (CNPs) as advised by
EPD.
3.4.2
The
status and locations of Noise Sensitive Receivers (NSRs) may change after
issuing this manual. In this case, the ET Leader shall propose updated
monitoring stations and seek approval from ER and agreement from the ICE and
EPD of the proposal.
Noise
Monitoring Stations for Baseline and Construction Monitoring
Noise Monitoring Stations |
NSR ID |
General Description |
N1 |
NSR 1 |
Wing Jan Kindergarten |
N2 |
NSR 2 |
Village house at No.84
Hang Hau Tsuen |
N3 |
NSR 3 |
Village house at No. 88
Hang Hau Tsuen |
Notes:
All monitoring stations shall be proposed by
the Environmental Team Leader and verified by the Independent Environmental
Checker before submitting to EPD prior to commencement of any monitoring.
3.4.3
When
alternative monitoring stations are proposed, the monitoring locations should
be chosen based on the following criteria:
(a)
at
locations close to the major site activities which are likely to have noise
impacts;
(b)
close
to the noise sensitive receivers (N.B. For the purposes of this section, any
domestic premises, hotel, hostel, temporary housing accommodation, hospital,
medical clinic, educational institution, place of public worship, library,
court of law, performing art centre should be considered as noise sensitive
receiver); and
(c)
for
monitoring locations located in the vicinity of the sensitive receivers, care
should be taken to cause minimal disturbance to the occupants during
monitoring.
3.4.4
The
monitoring station shall normally be at a point 1m from the exterior of the
sensitive receivers building facade and be at a position 1.2m above the ground.
If there is problem with access to the normal monitoring position, an
alternative position may be chosen, and a correction to the measurements shall
be made. For reference, a correction of +3dB(A) shall be made to the free field
measurements.
3.4.5
The
ET Leader shall agree with the ER and IEC on the monitoring position and the
corrections adopted. Once the positions for the monitoring stations are chosen,
the baseline monitoring and the impact monitoring shall be carried out at the
same positions.
3.5.1
The
ET Leader shall carry out baseline noise monitoring prior to the commencement
of the construction works. The baseline monitoring shall be carried out
continuously for a period of at least two weeks (14 consecutive days) at
interval of 5 minutes. The A-weighted noise level Leq, L10 and L90 shall be recorded.
A schedule on the baseline monitoring shall be submitted to the ER and IEC for
approval before the monitoring starts.
3.5.2
There
shall not be any construction activities in the vicinity of the stations during
the baseline monitoring. In exceptional cases, when insufficient baseline
monitoring data or questionable results are obtained, the ET Leader shall
liaise with IEC to agree on an appropriate set of data to be used as a baseline
reference and submit to the EPD for approval.
3.6.1
Noise
monitoring shall be carried out at all the designated monitoring station in Table
3.1 during the construction phase of the Project. The monitoring
frequency shall depend on the scale of the construction activities. The
following is an initial guide on the regular monitoring frequency for each
station on a per week basis when noise generating activities are underway:
•
one
set of Leq (30min) between 0700-1900 hours on normal weekdays.
3.6.2
The
Action and Limit Levels for construction noise are given in Table
3.2 and the Event/Action Plan in Table 3.3.
3.7
Event and Action Plan for
Construction Noise
3.7.1
In
case of non-compliance with the construction noise criteria, more frequent
monitoring as specified in the Action Plan in Table 3.3 shall be
carried out. This additional monitoring shall be continued until the recorded
noise levels are rectified or proved to be irrelevant to the construction
activities. The ET shall provide full documentation of his investigation on the
cause of the non-compliance and whether it can be traced to activities other
than those caused by the project, to the satisfaction of the ER and the IEC.
Action and Limit Levels for
Construction Noise
Time
Period |
Action |
Limit |
0700-1900
hrs on normal weekdays |
When
one documented complaint is received |
75* dB(A) |
* Reduced
to 70 dB(A) for schools and 65 dB(A) during school examination periods.
Table 3.3 Event/Action Plan for
Construction Noise Monitoring
EVENT
|
ACTION
|
|||
ET Leader
|
IEC |
ER |
Contractor |
|
Action Level |
1. Notify
IEC, Contractor and ER 2. Carry
out investigation and identify source 3. Report
the results of investigation to the IEC, Contractor and ER 4. Discuss
with the Contractor and formulate remedial measures 5. Increase
monitoring frequency 6. Check
compliance to Action/Limit Levels after application of mitigation measures |
1. Review
the analysed results submitted by the ET Leader 2. Review
the proposed remedial measures by the Contractor and advise the ER & ET accordingly 3. Supervise
the implementation of remedial measures |
1. Confirm
receipt of notification of complaint in writing 2. Notify
Contractor 3. Check
monitoring data submitted by the ET 4. Require
Contractor to propose remedial measures for the analysed noise problem 5. Ensure
remedial measures are properly implemented |
1.
Submit noise mitigation proposals to ER and IEC within three working days
of notification 2. Liaise
with the ER to ensure the effectiveness of the agreed mitigation 3. Amend
proposal if required 4. Implement
noise mitigation proposals |
Limit Level |
1. Notify
IEC, ER, EPD and Contractor 2. Identify
Source 3. Repeat
measurement to confirm findings 4. Increase
monitoring frequency 5. Carry
out analysis of Contractor’s working procedures to determine possible mitigation
to be implemented 6. Inform
IEC, ER and EPD the causes & actions taken for the exceedances 7. Assess
effectiveness of Contractor’s remedial actions and keep IEC, EPD and ER
informed of the results 8. If
exceedance stops, cease additional monitoring |
1. Check
monitoring data submitted by ET 2. Discuss
amongst ER, ET Leader and Contractor on the potential remedial actions 3. Review
Contractor’s remedial actions whenever necessary to assure their
effectiveness and advise the ER & ET accordingly 4. Supervise
the implementation of remedial measures |
1. Confirm
receipt of notification of exceedance 2. Notify
Contractor 3. Check
monitoring data submitted by the ET 4. Require
Contractor to propose remedial measures for the analysed noise problem 5. Discuss
with ET, IEC and Contractor on proposed remedial actions to be implemented 6. Ensure
remedial measures are properly implemented 7. Assess
the effectiveness of the remedial actions and keep the Contractor informed 8. If
exceedance continues, consider what portion of the work is responsible and
instruct the Contractor to stop that portion of work until the exceedance is
abated |
1. Take
immediate action to avoid further exceedance 2. Submit
proposals for remedial actions to ER within 3 working days of notification 3. Liaise
with the ER to ensure the effectiveness of the agreed mitigation 4. Amend
proposal if required 5. Implement
the agreed proposals 6. Resubmit
proposals if problem still not under control 7. Stop
the relevant portion of works as determined by the ER until the exceedance is
abated |
Construction Phase
3.8.1
The predicted noise levels showed that construction works
would give rise to daytime noise impacts to most of the Representative NSRs.
The following types of mitigation measures are recommended.
Level 1 Mitigation - Use of Quiet Plant
3.8.2
The use of quiet plant (also
referred as silenced equipment) can provide significant reduction in noise
level. Quiet plant is defined as PME whose actual sound power level is less
than the value specified in the TM-GW for the same piece of equipment. The
common source of these information is from international standard /
certification, e.g. BS 5228. To allow the Contractor some flexibility to select
equipment to suit actual needs, it is considered too restrictive to specify
which specified silenced equipment to be used for the construction works.
Hence, it is preferable and practical to specify the noise performance
specification of the plant on site in terms of the sound power level so that
the Contractor is allowed some flexibility. It should be noted that various
types of silenced equipment can be found in
3.8.3
The use of quiet plant is
considered to be the most effective ways of alleviating construction noise
impact. The Contractor should use quiet plant with sound power level lower than
that stipulated in the TM-GW as the Level 1 mitigation for construction noise.
3.8.4
The use of mini or lower power
rating equipment (e.g. mini excavator) should also be considered where
practical. This technique would be feasible and practical at some locations
given the limited space available for using large size construction equipment
and the small scale works involved.
3.8.5
The Contractor should take note
of ETWB TCW No. 19/2005 – “Environmental Management on Construction Sites”
which sets out the policy and procedures requiring contractors to, among
others, adopt Quality Powered Mechanical Equipment (QPME).
3.8.6
A list of quiet powered mechanical equipment (PME)
recommended for use during construction phase is tabulated below in Table
3.4.
Quiet Powered Mechanical
Equipment Recommended for Use during Construction Phase
Powered Mechanical Equipment |
Power Rating / Size, Weight |
Reference |
SWL, dB(A) |
Excavator, loader |
52 kW |
BS5228 C.3-97 |
105 |
Dump truck |
450 kW, 50 t |
BS5228 C.9-39 |
103 |
Crane |
62 kW |
BS5228 C.7-114 |
101 |
Vibratory roller |
9 kW |
BS5228 C.3-115 |
102 |
Concrete lorry mixer |
22 kW, 6 m3 |
BS5228 C.6-23 |
100 |
Vibratory poker |
2 kW |
BS5228 C.6-32 |
100 |
Asphalt paver / spreader |
90 kW, 13 t |
BS5228 C.8-24 |
101 |
Road roller |
10 t |
BS5228 C.8-25 |
96 |
3.8.7
With the use of quiet plant,
most of the Representative NSRs still exceed the noise standard and will still
require further mitigation measures.
Level
2 Mitigation - Use of Temporary Noise Barriers
3.8.8
Since most of the NSRs within
the Project area are typically low-rise tin-sheeted village houses of not more
than 2 storeys (all are less than 5 m tall), it would be effective to have
noise screening structures or temporary noise barriers purposely-built along
the site boundary to provide additional protection to NSRs close to the
construction site boundary. This could be in the form of purposely-built site
hoarding constructed from appropriate materials with a minimum superficial
density of 7 kg/m2. Noise barrier should be provided for noisy
construction activities that would be undertaken close (about 30 m or less) to
NSRs. The noise barrier should have a vertical height of at least 3 m or
(depending on the height of the NSRs to be protected) a height ensuring that
the operating equipment can be shielded from the view of the NSRs. The
temporary noise barrier should have no gaps or opening at joints. The
Contractor should regularly inspect and maintain the noise barrier to ensure
its effectiveness.
3.8.9
For the construction works which
have the potential to exceed the noise standards on nearby NSR and whose line
of sight cannot be effectively blocked by the temporary noise barrier, movable
(mobile) barriers should be provided. This may also be applicable in situation
where construction of a temporary noise barrier may not be possible due to site
/ space constraints, for example blocking village or emergency vehicle access.
Movable barriers of at least 2.5 m height with a small cantilevered upper
portion and skid footing can be located within a few meters of stationary plant
(e.g. generator) and within about 5 m or more of a mobile equipment (e.g.
excavator), such that the line of sight to the NSR is blocked by the barriers.
Good
Site Practices
3.8.10 In general, potential construction noise impact can be minimised or
avoided by imposing a combination of the following good site practices as
mitigation measures:
(a) Only well-maintained plant should be operated on-site and plant should be serviced regularly during the construction period.
(b) Construction plant should be sited away from NSRs.
(c) Machines and plant that may be in intermittent use should be shut down between works periods or should be throttled down to a minimum.
(d) Equipment known to emit sound strongly in one direction should be orientated such that the noise is directed away from nearby NSRs.
(e) Material stockpiles and other structures (such as site offices) should be effectively utilised to shield on-site construction activities.
(f) Stationary equipment should be located within the channel when weather conditions permit (e.g. dry season).
(g) The Contractor shall devise, arrange methods of working and carrying out the works in such manner as to minimise noise impacts on the surrounding environment, and shall provide experienced personnel with suitable training to ensure that these measures are implemented properly.
(h) In the event that new schools are built near the works area, the Contractor should minimise construction noise exposure to the schools (especially during examination periods). The Contractor should liaise with the school and the Examination Authority to ascertain the exact dates and times of all examination periods during the course of the contract and to avoid noisy activities during these periods.
Public Relation Strategy
3.8.11 Having a good public relation with the local communities during the
construction phase is indispensable for a smooth implementation of the Project.
Prior to commencement of the construction, visits to the affected villages,
local communities and property owners should be carried out. The purpose of the
visits is to advise the public the following information in relation to the
Project:
·
the implementation programme of the works;
·
the planned construction activities that will be involved;
·
the possible impacts arising from the works;
·
the measures to avoid or mitigate any adverse impacts;
·
the monitoring programme to check the efficiency of the
measures; and
·
the communication channels between the local communities and
the project office.
3.8.12 To maintain an effective communication channel with the public, a
24-hour hotline system should be established by the project office for the
Contractor to receive any enquiry and complaint lodged by the public in respect
of the Project. Upon receipt of enquiry / complaint, the Contractor (or its
Environmental Team) should investigate the causes of the incident and take the
appropriate action to rectify the situation. Periodic newsletters, information
leaflets, notices or other means of communication should be provided to the
affected villages, communities, and residents advising them the current
progress, the schedule of works in future, the potential environmental impacts
arising from the works and the corresponding mitigation measures. It is
considered that such a close relation between the local communities and the
project site office could ensure speedy resolution of any environmental
non-compliance and maintain an environmental standard acceptable to the local
communities during construction.
3.8.13 Further
mitigation is recommended for NSRs 3, 4, 6 & 10 by restricting concurrent
usage of several equipment at the same time during excavation and construction
of the channel lining, crossings.
3.8.14 Table 3.5 summarises the mitigation
measures proposed for the construction works. All these construction noise
mitigation measures should be implemented by the Contractor during the
construction stage of the works. The location of the temporary noise barriers and
mobile noise barriers should be further reviewed by the Contractor during the
construction stage based on the latest construction programme and contemporary
conditions, including any changes with respect to NSRs. The Contractor should
design, construct, operate and maintain the mitigation measures throughout the
construction stage and as required by the Engineer. Before commencement of the
works, the Contractor should submit to the Engineer for approval (as part of
their method statement) details of the mitigation measures to be employed under
the works. The Contractor’s proposed mitigation measures should also be
certified by the ET Leader and verified by the IEC to ensure the intended noise
reduction effectiveness can be achieved.
3.8.15 If the above measures are not
sufficient to restore the impacts to acceptable levels upon the advice of ET
Leader, the Contractor shall liaise with the ET Leader on some other mitigation
measures, endorsed by IEC and propose to ER for approval, and implement the
mitigation measures.
3.8.16 The implementation schedule for the
recommended mitigation measures is presented in Appendix A.
Summary of Proposed Construction Noise Mitigation Measures
Proposed
Mitigation Measures |
Location |
Timing /
Duration |
Implementation
Agent |
Specific Requirements |
Use of quiet equipment including
QPME |
All construction works / sites |
During the construction period |
Contractor |
Some examples of quiet plant and
QPME are shown in Table 3.4. Contractor can propose other suitable alternative
equipment with similar or lower sound power level. |
Use of temporary noise barrier
(purpose-built site hoarding) and/or movable (mobile) noise barrier |
The temporary noise barrier shall be
located as per Figure 4.2 (of the EIA) or wherever noisy construction works
are being carried out close (30m or less) to NSRs |
During the construction period |
Contractor |
Barriers should be of at least 3 m
high or able to shield construction equipment from NSR’s view. These
barriers should be constructed of appropriate material with a minimum
superficial density of 7 kg/m2, with no gaps or openings. Also,
regular inspection and maintenance should be carried out. Where barriers cannot block line of
sight, mobile barrier of 2.5 m high with a cantilevered upper portion should
be provided. |
Good site practices |
All construction works / sites |
During the construction period |
Contractor |
----- |
Public relation strategy |
All construction works / sites |
During the construction period |
Project office (Engineer) /
Contractor |
Maintain a 24-hour hotline for
enquiry and complaint, periodic communication with affected parties. |
Restrict concurrent usage of several
construction equipment at the same time |
For construction works in close
proximity to NSRs 3, 4, 6 &10 |
During the construction period |
Contractor |
Contractor to propose details or
other suitable alternatives to the Engineer and ET Leader for approval. |