3.1
In this section, the requirements,
methodology, equipment, monitoring locations, criteria and protocols for the
monitoring and audit of airborne noise impacts during the construction and
operation phases of the Project are presented.
Noise Parameters and Criteria
3.2
The
construction noise level should be measured in terms of the A-weighted equivalent
continuous sound pressure level (Leq). Leq (30 minutes) should
be used as the monitoring parameter for the time period between 0700 and 1900
hours on normal weekdays.
3.3
Supplementary
information for data auditing and statistical results such as L10
and L90 should also be obtained for reference. A sample data
record sheet is shown in Appendix B for
reference.
3.4
Whilst the
Noise Control Ordinance (NCO) does not provide for the statutory control of
construction activities occurring on weekdays during normal working hours (i.e.
Monday to Saturday inclusive 0700-1900 hours), the daytime criterion of Leq(30
minute) 75dB(A) stipulated in Annex 5 of the Technical Memorandum on
Environmental Impact Assessment Process (EIAO-TM) is adopted as the compliance
criterion for all residential dwellings; and the daytime standards of Leq(30
minute) 70dB(A) and Leq (30 minute) 65dB(A) are adopted for
all educational institutions during normal school days and examination periods,
respectively.
3.5
The NCO
provides statutory controls on general construction works during restricted
hours (i.e. 1900-0700 hours Monday to Saturday and at any time on Sundays and
public holidays). The Acceptable Noise Levels (ANLs)
during restricted hours are dependent on the Area Sensitivity Rating of the NSRs.
The relevant ANLs are provided in Table 3.1.
Table 3.1
Acceptable Noise Levels (ANLs)
Time Period |
Area Sensitivity Rating, dB(A) |
||
A |
B |
C |
|
All days during the evening (1900-2300 hours) and
general holidays (including Sundays) during the day and evening (0700-2300
hours) |
60 |
65 |
70 |
All days during the night-time (2300-0700) |
45 |
50 |
55 |
Monitoring Equipment and Methodology
3.6
As referred
to the requirements of the Technical Memorandum (TM) issued under the NCO,
sound level meters in compliance with the International Electrotechnical
Commission Publications 651: 1979 (Type 1) and 804: 1985 (Type 1)
specifications should be used for carrying out the noise monitoring.
Immediately prior to and following each noise measurement the accuracy of the
sound level meter should be checked using an acoustic calibrator generating a
known sound pressure level at a known frequency. Measurements may be
accepted as valid only if the difference between calibration levels obtained before
and after the noise measurement is less than 1.0 dB.
3.7
Noise
measurements should not be made in the presence of fog, rain, wind with a
steady speed exceeding 5ms-1 or wind with gusts exceeding 10ms-1.
The wind speed should be checked with a portable wind speed meter capable of
measuring wind speeds in m/s.
3.8
The ET
Leader is responsible for the provision of the monitoring equipment. He should
ensure that sufficient noise measuring equipment and associated instrumentation
are available for carrying out the baseline monitoring, regular impact
monitoring and ad hoc monitoring. All the equipment and associated
instrumentation should be clearly labelled.
Noise Monitoring Locations
3.9
Based on the
EIA study, the designated locations for construction noise monitoring are listed
in Table 3.2 and shown in Figure
Nos. NOL/ERL/
Table 3.2 Noise Monitoring Stations during Construction Phase
Identification
No. |
NSR
ID in EIA Report |
Construction
Noise Monitoring Station |
CN1 |
MP3 |
No. 166 Mai Po San Tsuen |
CN2 |
MP2 |
Mai Po San Tsuen Village
House |
CN3 |
NT2 |
Yau Tam Mei Village House |
CN4 |
NT3 |
Yau Tam Mei Village House |
CN5 |
TP1 |
|
CN6 |
TP2 |
|
CN7 |
SS9 |
House 93, Seasons Villas |
CN8 |
SS10 |
DD110 |
CN9 |
SS7 |
Leung |
CN10 |
SS11 |
Leung |
CN11 |
SS4 |
Leung |
CN12 |
SS1 |
630 Sheung Tsuen |
CN13 |
TU2 |
No. 489H Tse |
CN14 |
TU1 |
Tse |
CN15 |
PH3 |
No. 305B, Sheung Tsuen San Tsuen Village House |
CN16 |
PH1 |
DD 114 |
CN17 |
SM2 |
Tsuen Wan |
CN18 |
SM1 |
Sau Shan House, Cheung Shan Estate |
CN19 |
SY1 |
No. 168, Yau Ma Hom Resite Village |
CN20 |
KC2 |
No.
1, Ha |
CN21 |
ML1 |
Po |
CN22 |
- |
Block
I, Lai Chi Kok Reception Centre |
CN23 |
NC13 |
HKIVE Haking Wong Waterfront Annex |
CN24 |
NC17 |
|
CN25 |
NC11 |
Tack Ching Girls' Secondary School |
CN26 |
NC9 |
|
CN27 |
NC6 |
Cheong |
CN28 |
NC2 |
Tower 6, Harbour Green |
CN29 |
MK1 |
|
CN30 |
WK3 |
|
CN31 |
WK4 |
Tower 6, |
CN32 |
WK8 |
Tower 3, The Waterfront |
CN33 |
WK14 |
|
CN34 |
WK7a |
Tsim Sha Tsui Fire Station |
3.10
The status
and location of noise sensitive receivers may change after this manual is
issued. In such event, and if changes to the monitoring locations are
considered necessary, the ET Leader should propose alternative monitoring
locations and seek agreement from the IEC on the proposal. When
alternative monitoring locations are proposed, the monitoring locations should
be chosen based on the following criteria:
§
Monitoring at sensitive receivers
close to the major site activities that are likely to have noise impacts;
§
Monitoring close to the noise
sensitive receivers as defined in the Technical Memorandum; and
§
Assurance of minimal disturbance to
the occupants during monitoring in the vicinity of sensitive receivers.
3.11
The
monitoring station should normally be at a point
Baseline Monitoring
3.12
The ET should
carry out baseline noise monitoring prior to the commencement of the
construction works. The baseline noise levels should be measured for a
continuous period of at least 14 consecutive days at a minimum logging interval
of 30 minutes for daytime (between 0700 and 1900 hours of normal weekdays) and
15 minutes (as three consecutive Leq, (5 minutes) readings) for
evening time (between 1900 and 2300 hours on normal weekdays), general holidays
including Sundays (between 0700 and 2300 hours) and night-time (between 2300
and 0700 on all days). The Leq, L10 and L90 should
be recorded at the specified interval. A schedule for the baseline
monitoring should be submitted to the IEC for approval before the monitoring
starts.
3.13
There should
not be any construction activities in the vicinity of the monitoring stations
during the baseline monitoring. Any non-project related construction
activities in the vicinity of the monitoring stations during the baseline
monitoring should be noted and the source and location of such activities should be recorded.
3.14
In
exceptional cases, when baseline monitoring data obtained are insufficient or
questionable, the ET Leader should liaise with the IEC and EPD to agree on an
appropriate set of data to be used as the baseline reference.
Impact Monitoring
3.15
Noise
monitoring should be carried out at all the designated monitoring stations when
there are Project-related construction activities being undertaken within a
radius of 300m from the monitoring stations. The monitoring frequency should
depend on the scale of the construction activities. An initial guide on
the monitoring is to obtain one set of 30-minute measurement at each station
between 0700 and 1900 hours on normal weekdays at a frequency of once a week
when construction activities are underway.
3.16
Any General
construction work carried out during restricted hours is controlled by
Construction Noise Permit (CNP) under the NCO.
3.17
If a school is
located near the construction activities, noise monitoring should be carried
out at the monitoring stations for the school during school examination
periods. The ET Leader should liaise with the school administration and the Hong
Kong Examinations and Assessment Authority to ascertain the exact dates and
times of all examinations during the construction phase of the Project.
3.18
In the case
of non-compliance with the construction noise criteria, more frequent
monitoring, as specified in Event and Action Plan in Table 3.4 should be carried out. This additional monitoring should
be continued until the recorded noise levels show that the non-compliance is rectified
or proved to be irrelevant to the Project-related construction activities.
Event and Action Plan
3.19
The Action and Limit levels for construction noise are
defined in Table 3.3. Should
non-compliance of the noise quality criteria occur, actions in accordance with
the Event and Action Plan in Table 3.4
should be taken.
Table 3.3 Action and Limit Levels for Construction Noise
Time Period |
Action |
Limit |
0700-1900 hours on normal weekdays |
When one documented complaint is
received |
75 dB(A) for residential premises |
70 dB(A) for school and 65 dB(A) during examination period |
3.20
To account for cases in which ambient noise levels, as identified
by baseline monitoring, approach or exceed the stipulated Limit Levels prior to
the commencement of construction, a Maximum Acceptable Impact Level, which
incorporates the baseline noise levels and the identified construction noise
Limit Level, may be defined and agreed with EPD. The amended level will be
greater than 75 dB(A) and will represent the maximum acceptable noise level at
a specific monitoring station. Correction factors for the effects of acoustic
screening and/or architectural features of NSRs may also be applied as
specified in the TM.
Table 3.4 Event and Action Plan for Construction Noise Monitoring
ACTION |
||||
ET |
IEC |
ER |
CONTRACTOR |
|
Action
Level |
1.
Notify IEC, ER and Contactor 2.
Carry out investigation 3.
Report the results of
investigation to the IEC, ER and Contactor 4.
Discuss jointly with the ER and
Contractor and formulate remedial measures 5.
Increase monitoring frequency to
check mitigation effectiveness |
1.
Review the analysed results
submitted by the ET 2.
Review the proposed remedial
measures by the Contractor and advise the ER accordingly 3.
Supervise the implementation of
remedial measures |
1.
Confirm receipt of notification of
failure in writing 2.
Notify Contractor 3.
Require Contractor to propose
remedial measures for the analysed noise problem 4.
Ensure remedial measures are
properly implemented |
1.
Submit noise mitigation proposals
to ER with copy to IEC and ET 2.
Implement noise mitigation
proposals |
Limit
Level |
1.
Notify IEC, ER, EPD and Contractor 2.
Identify source 3.
Repeat measurement to confirm
findings 4.
Increase monitoring frequency 5.
Carry out analysis of Contractor’s
working procedures to determine possible mitigation to be implemented 6.
Inform IEC, ER, EPD the causes and
actions taken for the exceedances 7.
Assess effectiveness of
Contractor’s remedial actions and keep IEC, EPD and ER informed of the
results 8.
If exceedance stops, cease
additional monitoring |
1.
Discuss amongst ER, ET and
Contractor on the potential remedial actions 2.
Review Contractor’s remedial
actions whenever necessary to assure their effectiveness and advise the ER
accordingly 3.
Supervise the implementation of
remedial measures |
1.
Confirm receipt of notification of
failure in writing 2.
Notify Contractor 3.
Require Contractor to propose
remedial measures for the analysed noise problem 4.
Ensure remedial measures are
properly implemented 5.
If exceedance continues, consider
what portion of the work is responsible and instruct the Contractor to stop
that portion of work until the exceedance is abated |
1.
Take immediate action to avoid
further exceedance 2.
Submit proposals for remedial
actions to ER with copy to IEC and ET 3.
Implement the agreed proposals 4.
Revise and resubmit proposals if
problem still not under control 5.
Stop the relevant portion of works
as determined by the ER until the exceedance is abated |
Operational
Noise – Fixed Plant
Maximum Permissible Sound Power Levels of Fixed Plant
3.21
The maximum permissible sound power levels of the identified
fixed noise sources of the Project were predicted in the EIA report. The specified sound power levels should
be implemented and refined by the Contractor as appropriate to ensure that the
noise impact associated with the fixed plant operations would comply with the
noise standards stipulated in the EIAO-TM and NCO.
Commissioning Test
3.22
Prior to the operation of the Project, the Contractor should
conduct noise commissioning tests for all major fixed noise sources. The test should be carried out by a
qualified person possessing at least 7 years of noise control experience and a
corporate membership of Hong Kong Institute of Acoustics or equivalent. The noise commissioning test report
should be submitted to the ET Leader and IEC for approval.
Operational Noise – Railway Operation
Noise Parameters and Criteria
3.23
To ensure that the operational airborne railway noise levels
comply with the noise standards stipulated in the NCO, the ET should carry out railway
noise commissioning tests at the potentially worst affected NSRs identified in
the EIA study before the operation of the Project.
3.24
The IND-TM stipulates the
appropriate acceptable noise levels (ANL) for airborne railway noise. The ANLs are dependent on area
sensitivity rating (ASR) of the noise sensitive receivers and are shown in Table 3.5.
3.25
EIAO-TM also stipulates a maximum
noise level of 85 dB(A) applying to the period from 2300 to 0700 hours.
Table 3.5 Operational Airborne Railway Noise Criteria
|
Air-borne Railway Noise
Criteria, dB(A) |
|||||
NSRs Description |
Day and Evening (0900 to 2300 hrs) |
Night-time Period |
||||
A |
B |
C |
A |
B |
C |
|
Churches/temples, schools, medical clinics, libraries and courts |
60 |
65 |
70 |
[a] |
||
Domestic premises, hotels and
hospitals |
60 |
65 |
70 |
50 |
55 |
60 |
Note:
[a]
No sensitive use during this period.
Monitoring Equipment and Methodology
3.26
The
monitoring equipment and methodology for operational airborne noise monitoring
should be same as those recommended for construction noise monitoring.
Noise Monitoring Locations
3.27
Based on the
EIA study, the potentially worst affected locations were designated for operational
airborne noise monitoring as listed in Table 3.6 and illustrated in Figure
No. NOL/ERL/300C/XRL/ENS/M62/215.
Table 3.6 Noise Monitoring Stations during Operation Phase
Identification
No. |
NSR
ID in EIA Report |
ASR |
Operational
Noise Monitoring Station |
ON1 |
SS7 |
B |
Leung |
ON2 |
SS10 |
B |
DD110 |
ON3 |
SS15 |
B |
Leung |
3.28
The status
and location of noise monitoring locations may change after issuing this
manual. If such cases exist, the ET Leader should propose updated
monitoring locations and seek approval from the ER and agreement from the IEC
and EPD on the proposal. When alternative monitoring locations are
proposed, the monitoring locations should be chosen based on the following
criteria:
§
Monitoring at sensitive receivers
close to the major operation activities which are likely to have noise impacts;
§
Monitoring close to the noise
sensitive receivers as defined in the Technical Memorandum; and
§
Assurance of minimal disturbance to
the occupants during monitoring in the vicinity of sensitive receivers.
3.29
The
monitoring station should normally be at a point
Commissioning Test
3.30
One set of 30-minute
measurement at each monitoring station should be conducted during the daytime
and evening period (0700 - 2300 hours), and night-time (2300 – 0100 hours).
Noise measurements of the A-weighted equivalent continuous sound pressure level
(Leq) should be made. Leq (30 minutes) should be
used as the monitoring parameter. Supplementary information for data
auditing, statistical results, such as Lmax, L10 and L90
should also be obtained for reference.
Construction Phase
3.31
The EIA report indicates that construction activities would
cause noise exceedances at a few NSRs, and therefore, appropriate mitigation
measures and good site practices are recommended. The Contractor should be
responsible for the design and implementation of these measures. The
implementation schedule for the recommended mitigation measures is presented in
Appendix A.
3.32
In the event of exceedances or complaints, the Contractor
should review the effectiveness of these mitigation measures and propose,
design and implement alternative or additional measures as appropriate. The Contractor should liaise with the ET
Leader on alternative or additional mitigation measures, provide them to ER for
approval, and implement the mitigation measures.
Operation Phase
3.33
The mitigation measures recommended for the operation of the
Project is presented in Appendix A. These measures should be reviewed and
refined by the ET Leader if there are any major design changes during the detailed
design phase such that the recommended measures are adequate for alleviating
the potential operational noise impacts from SSS and ERS.