TABLE OF CONTENTS

 

 

5          water quality Impact.. 5-1

5.1         Introduction. 5-1

5.2         Environmental Legislation, Plans, Standards, and Guidelines. 5-1

5.3         Water Sensitive Receivers. 5-3

5.4         Description of the Environment 5-4

5.5         Assessment Methodologies. 5-6

5.6         Identification and Evaluation of Environmental Impacts. 5-6

5.7         Cumulative Impacts from Concurrent Project 5-11

5.8         Recommended Water Quality Mitigation Measures. 5-11

5.9         Evaluation of Residual Impacts. 5-17

5.10       EM&A Requirements. 5-17

5.11       Conclusions. 5-17

 

LISTS OF FIGURES

NEX1062/S/SHD/ACM/Z10/170        Locations of Water Sensitive Receivers



5                  water quality Impact

5.1              Introduction

5.1.1          This section presents an assessment of the potential water quality impacts associated with construction and operation of the Project. Recommendations for mitigation measures have been provided to minimize the identified water quality impacts.

5.2              Environmental Legislation, Plans, Standards, and Guidelines

Environmental Impact Assessment Ordinance (EIAO)

5.2.1          The Technical Memorandum on Environmental Impact Assessment Process (EIAO-TM) was issued by Environmental Protection Department (EPD) under Section 16 of the EIAO.  It specifies the assessment method and criteria that are to be followed in an EIA Study. Reference sections in the EIAO-TM provide the details of assessment criteria and guidelines that are relevant to the water quality impact assessment, including:

¡¤         Annex 6 ¨C Criteria for Evaluating Water Pollution

¡¤         Annex 14 ¨C Guidelines for Assessment of Water Pollution

 

Water Quality Objective

5.2.2         The Water Pollution Control Ordinance (WPCO) provides the major statutory framework for the protection and control of water quality in Hong Kong.  According to the Ordinance and its subsidiary legislation, Hong Kong waters are divided into ten Water Control Zones (WCZs).  Corresponding statements of Water Quality Objectives (WQOs) are stipulated for different water regimes (marine waters, inland waters, bathing beaches subzones, secondary contact recreation subzones and fish culture subzones) in the WCZs based on their beneficial uses. The Project site is located within the North Western WCZ. The WQOs for the North Western WCZ are listed in Table 5.1.  These WQOs were used as the water quality assessment criteria for the Project.

Table 5.1     Summary of Water Quality Objectives for North Western WCZ

Parameters

Objectives

Sub-Zone

Offensive Odour, Tints

Not to be present

Whole zone

Visible foam, oil scum, litter

Not to be present

Whole zone

Dissolved Oxygen (DO) within 2 m of the seabed

Not less than 2.0 mg/L for 90% of the sampling occasions during the whole year

Marine waters

Depth-averaged DO

Not less than 4.0 mg/L

Tuen Mun (A), Tuen Mun (B) and Tuen Mun (C) Subzones, Water Gathering Ground Subzones and other inland waters

Not less than 4.0 mg/L for 90 % of the sampling occasions during the whole year

Marine waters

pH

To be in the range of 6.5 - 8.5, change due to human activity not to exceed 0.2

Marine waters excepting Bathing Beach Subzones

To be in the range of 6.5 ¨C 8.5

Tuen Mun (A), Tuen Mun (B) and Tuen Mun (C) Subzones and Water Gathering Ground Subzones

To be in the range of 6.0 ¨C9.0

Other inland waters

To be in the range of 6.0 ¨C9.0 for 95% samples collected during the whole year and waste discharges shall not cause the natural pH range to be extended by more than 0.5 units

Bathing Beach Subzones

Salinity

Change due to human activity not to exceed 10% of ambient

Whole zone

Temperature

Change due to human activity not to exceed 2 oC

Whole zone

Suspended solids (SS)

Waste discharge not to raise the natural ambient level by 30%, nor cause the accumulation of suspended solids which may adversely affect aquatic communities

Marine waters

Not to cause the annual median to exceed 20 mg/L

Tuen Mun (A), Tuen Mun (B) and Tuen Mun (C) Subzones and Water Gathering Ground Subzones

Not to cause the annual median to exceed 25 mg/L

Inland waters

Unionized Ammonia (UIA)

Annual mean not to exceed 0.021 mg/L as unionized form

Whole zone

Nutrients

Shall not cause excessive algal growth

Marine waters

Total Inorganic Nitrogen (TIN)

Annual mean depth-averaged inorganic nitrogen not to exceed 0.3 mg/L

Castle Peak Bay Subzone

Annual mean depth-averaged inorganic nitrogen not to exceed 0.5 mg/L

Marine waters excepting Castle Peak Bay Subzone

Bacteria

Not exceed 610 per 100ml, calculated as the geometric mean of all samples collected in one calendar year

Secondary Contact Recreation Subzones

Should be less than 1 per 100 ml, calculated as the running median of the most recent 5 consecutive samples taken between 7 and 21 days.

Tuen Mun (A) and Tuen Mun (B) Subzones and Water Gathering Ground Subzones

Not exceed 1000 per 100 ml, calculated as the running median of the most recent 5 consecutive samples taken between 7 and 21 days

Tuen Mun (C) Subzone and other inland waters

Not exceed 180 per 100 ml, calculated as the geometric mean of all samples collected from March to October inclusive. Samples should be taken at least 3 times in one calendar month at intervals of between 3 and 14 days.

Bathing Beach Subzones

Colour

Not to exceed 30 Hazen units

Tuen Mun (A) and Tuen Mun (B) Subzones and Water Gathering Ground Subzones

Not to exceed 50 Hazen units

Tuen Mun (C) Subzone and other inland waters

5-Day Biochemical Oxygen Demand (BOD5)

Not to exceed 3 mg/L

Tuen Mun (A), Tuen Mun (B) and Tuen Mun (C) Subzones and Water Gathering Ground Subzones

Not to exceed 5 mg/L

Inland waters

Chemical Oxygen Demand (COD)

Not to exceed 15 mg/L

Tuen Mun (A), Tuen Mun (B) and Tuen Mun (C) Subzones and Water Gathering Ground Subzones

Not to exceed 30 mg/L

Inland waters

Toxins

Should not cause a risk to any beneficial uses of the aquatic environment

Whole zone

Waste discharge shall not cause the toxins in water significant to produce toxic carcinogenic, mutagenic or teratogenic effects in humans, fish or any other aquatic organisms.

Whole zone

Phenol

Quantities shall not sufficient to produce a specific odour or more than 0.05 mg/L as C6 H5OH

Bathing Beach Subzones

Turbidity

Shall not reduce light transmission substantially from the normal level

Bathing Beach Subzones

Source:   Statement of Water Quality Objectives (North Western Water Control Zone)

 

Technical Memorandum on Effluents Discharge Standards

5.2.3          Discharges of effluents are subject to control under the WPCO.  The Technical Memorandum on Standards for Effluents Discharged into Drainage and Sewerage Systems, Inland and Coastal Waters (TM-DSS), issued under Section 21 of the WPCO, gives guidance on permissible effluent discharges based on the type of receiving waters (foul sewers, storm water drains, inland and coastal waters). The limits control the physical, chemical and microbial quality of effluent.  Any sewage from the proposed construction and operational activities must comply with the standards for effluent discharged into the foul sewers, inshore waters and marine waters of the North Western WCZ provided in the TM-DSS.

Practice Note

5.2.4          A practice note for professional persons has been issued by the EPD to provide guidelines for handling and disposal of construction site discharges. The ProPECC PN 1/94 ¡°Construction Site Drainage¡± provides good practice guidelines for dealing with ten types of discharge from a construction site.  These include surface runoff, groundwater, boring and drilling water, bentonite slurry, water for testing and sterilisation of water retaining structures and water pipes, wastewater from building construction, acid cleaning, etching and pickling wastewater, and wastewater from site facilities.  Guidelines given in the ProPECC PN 1/94 should be followed as far as possible during construction to minimize the water quality impact due to construction site drainage.

5.3              Water Sensitive Receivers

Water Sensitive Receivers

5.3.1          The key Water Sensitive Receivers (WSRs) near the Project site have been identified as follows:

¡¤         Existing Tai Ho Wan (WSR 1);

¡¤         Inland watercourses in the vicinity (WSR 3);

¡¤         Channelized watercourse/ditch near Siu Ho Wan Sewerage Treatment Works (SHWSTW) (WSR 4), Tai Ho Offtake and Pigging Station (WSR 5) and Siu Ho Wan Water Treatment Works (WSR 6);  and

¡¤         The Brothers Marine Park (WSR 2).

5.3.2          The indicative locations of these WSRs are shown in Figure No. NEX1062/S/SHD/ACM/Z10/170.  Some watercourses / channelized watercourses / ditches are generally draining from the hillside in the southeast towards the Project site.  Together with the drainage within the Project site, these watercourses / channelized watercourses / ditches will eventually discharge to the marine water via the existing box culvert.

5.4              Description of the Environment

Marine Water

5.4.1          North Western WCZ is situated in the Pearl River Estuary and is strongly influenced by the freshwater flows from Guangdong Province. Ebb tide currents are flowing to the southeast whilst the flood tide currents are to the northwest.

5.4.2          A summary of the marine water quality data collected at the monitoring stations, namely NM1, NM2 and NM3 in the central area of North Western WCZ which are located in the vicinity of the Project, is given in Table 5.2.  These monitoring stations are indicated in Figure No. NEX1062/S/SHD/ACM/Z10/170.  According to the EPD¡¯s publication ¡°Marine Water Quality in Hong Kong 2015¡±, full compliance of the depth-averaged DO levels was recorded at these stations, except NM1. Non-compliance of TIN levels at NM2 and NM3 might be associated with the higher background level of the discharges from Pearl River, and other local discharges.  The bottom DO and UIA levels recorded in these monitoring stations fully complied with the relevant WQOs.

Table 5.2    Summary Statistics of Marine Water Quality of North Western Water WCZ Collected by EPD in 2015

Parameter

Lantau Island

Pearl Island

Pillar Point

WPCO WQO
(in marine waters)

NM1

NM2

NM3

Temperature

(oC)

23.7

(16.9 ¨C 27.4)

24.0
(16.9 ¨C 27.8)

24.2

(17.0 ¨C 27.7)

Not more than 2oC in daily temperature range

Salinity

29.9

(25.2 ¨C 31.7)

28.1
(18.9 ¨C 31.3)

27.9

(21.0 ¨C 31.3)

Not to cause more than 10% change

Dissolved Oxygen  (DO)

(mg/l)

Depth average

5.4

(3.7 ¨C 7.2)

5.7
(4.3 ¨C 7.4)

5.6

(4.3 ¨C 7.3)

Not less than 4 mg/l for 90% of the samples

Bottom

5.2

(2.5 ¨C 7.3)

5.4

(3.2 ¨C 7.3)

5.3

(3.0 ¨C 7.4)

Not less than 2 mg/l for 90% of the samples

Dissolved Oxygen (DO)

(% Saturation)

Depth average

75

(53 ¨C 90)

79
(62 - 92)

78

(62 ¨C 91)

-

Bottom

72

(36 ¨C 92)

75
(46 - 91)

74

(44 ¨C 91)

-

pH

7.8

(7.7 ¨C 8.0)

7.8
(7.6 - 8.0)

7.8

(7.6 ¨C 8.0)

6.5 - 8.5 (¡À 0.2 from natural range)

Suspended Solids (SS)

(mg/L)

8.0

(1.3 ¨C 22.0)

6.6

(2.7 ¨C 20.3)

10.8

(4.2 ¨C 30.3)

Not more than 30% increase

Ammonia Nitrogen (NH3-N) (mg/L)

0.107

(0.016 ¨C 0.177)

0.106

(0.014 ¨C 0.180)

0.110

(0.013 ¨C 0.203)

-

Unionised Ammonia (UIA) (mg/L)

0.003

(<0.001 ¨C 0.006)

0.003
(<0.001 - 0.009)

0.003

(<0.001 ¨C 0.008)

Not more than 0.021 mg/l for annual mean

Nitrite Nitrogen (NO2-N) (mg/L)

0.052

(0.016 ¨C 0.130)

0.066
(0.017 - 0.131)

0.070

(0.018 ¨C 0.153)

-

Nitrate Nitrogen (NO3-N) (mg/L)

0.286

(0.127 ¨C 0.723)

0.421
(0.133 - 1.230)

0.429

(0.137 ¨C 0.963)

-

Total Inorganic Nitrogen  (TIN) (mg/L)

0.44

(0.27 ¨C 0.84)

0.59
(0.29 - 1.36)

0.61

(0.31 ¨C 1.09)

Not more than 0.5 mg/l for annual mean

Total Nitrogen (TN)

(mg/L)

0.71

(0.56 ¨C 1.06)

0.86
(0.52 - 1.61)

0.88

(0.55 ¨C 1.28)

-

Orthophosphate Phosphorus (PO4) (mg/L)

0.022

(0.008 ¨C 0.031)

0.024
(0.013 - 0.039)

0.025

(0.011 ¨C 0.040)

-

Total Phosphorus (TP)

(mg/L)

0.05

(0.03 ¨C 0.07)

0.05
(0.03 - 0.08)

0.06

(0.04 ¨C 0.09)

-

Chlorophyll-a

(µg/L)

1.6

(0.4 ¨C 4.6)

1.8
(0.4 ¨C 5.8)

1.7

(0.7 ¨C 4.1)

-

E. coli

(cfu/100 mL)

97

(7 ¨C 510)

31
(2 - 220)

59

(10 ¨C 220)

-

Faecal Coliforms

(cfu/100mL)

200

(48 ¨C 650)

70

(4 ¨C 340)

130

(23 ¨C 580)

-

Notes:

(1)      Data source: Marine Water Quality in Hong Kong in 2015 (EPD).

(2)      Data presented are annual arithmetic means of depth-averaged results except for E.coli and faecal coliforms that are annual geometric means.

(3)      Data in brackets indicate the ranges

Tai Ho Wan and Inland Watercourse /Channelized Watercourse/Ditch

5.4.3          The catchments of existing Tai Ho Wan and inland watercourses / channelized watercourses / ditches located in the vicinity of the Project site are shown in Figure No. NEX1062/S/SHD/ACM/Z10/170.  The upstream sections of these watercourses are mainly collecting the runoff from the hillside with no major pollution source. In dry season, most of these watercourses are expected to be dry, whereas in the wet seasons, the water flows in these watercourses mostly would be rainwater with low pollution levels. Site inspections and water sampling at these watercourses were conducted in 21 July 2016 representing the wet season.  It was observed during the site inspections that most of these watercourses were dried out or had a very low flow (with water depth of less than 3 cm).  Since there were steep slopes and construction sites for Tuen Mun Chek Lap Kok Link within the study area, only limited accesses are available and practical for conducting water sampling.  Due to the low water flow and site constraints, water sampling was only practical to be carried out at three stations (namely Stations S1, S2 and S3 respectively) as shown in Figure No. NEX1062/S/SHD/ACM/Z10/170. The shortest distance of S1 to the Scheme Boundary is about 73m. The associated sampling results are shown in Table 5.3. 

Table 5.3    Water Quality Monitoring Data for Inland Watercourses

Parameter

Unit

Averaged Value of 2 Consecutive Measurements

Station S1

Station S2

Station S3

pH Value

-

7.73

7.43

7.93

Temperature

¡ãC

30.80

27.65

30.15

Salinity

ppt

0.10

0.00

15.50

Turbidity

NTU

3.33

5.01

4.42

Dissolved Oxygen

mg/L

7.67

9.03

8.30

Dissolved Oxygen - % Saturation

%

102.85

113.60

107.15

5.5              Assessment Methodologies

5.5.1          The assessment area includes all areas within 500 m from the Project boundary, and covers relevant WSRs that have a bearing on the environmental acceptability of the Project within the North Western WCZ.  Since the Project involved only land-based works and no marine works would be required, a 500m assessment area is therefore considered adequate. The assessment area was further extended to cover other areas such as stream courses, existing and planned drainage system as well as other water system(s) in the vicinity, which may be affected by the Project and have a bearing on the environmental acceptability of the Project.

5.5.2          The WSRs that may be affected by the Project have been identified.  Potential sources of water quality impact that may arise during the construction works and operational activities were described and quantified, where applicable, including point discharges and non-point sources to surface water runoff, sewage from workforce and future users as well as industrial wastewater in accordance with the requirement stipulated in Section 4 (vii) of Appendix D of the Study Brief.  This task included identifying pollutants from point discharges and non-point sources that could affect the quality of surface water runoff.  All the identified sources of potential water quality impact were then evaluated and their impact significance determined. The need for mitigation measures to reduce any identified adverse impacts on water quality to acceptable levels was also determined.

5.6              Identification and Evaluation of Environmental Impacts

Construction Phase

5.6.1          The Project will only involve land-based construction works with neither marine works nor works at streams and/or watercourses to be undertaken. Also, no diversion, reconstruction and re-alignment of streams and watercourses, as well as existing box culvert will be required for the Project.  Potential sources of water quality impact associated with the construction of the Project have been identified and include:

¡¤         General construction activities

¡¤         Construction site runoff;

¡¤         Construction works near channelized watercourse/ditch;

¡¤         Accidental spillage;

¡¤         Sewage effluent from construction workforce; and

¡¤         Groundwater from Contaminated Areas, Contaminated Site Runoff and Wastewater from Land Decontamination.

General Construction Activities

5.6.2          The land-based construction works could have the potential to cause water pollution.  Various types of construction activities may generate wastewater. These include general cleaning and polishing, wheel washing, dust suppression and utility installation. These types of wastewater would contain high concentrations of suspended solids (SS). Various construction works may also generate debris and rubbish such as packaging, construction materials and refuse.  Uncontrolled discharge of site effluents, rubbish and refuse generated from the construction works would lead to deterioration in water quality.

5.6.3          Considering that excavation and piling works involved for the Project would generate approximately 21,826m3 land-based sediment, which require disposal of at the designated disposal areas. As mentioned in Section 7.5.19, the excavated sediments will be loaded onto the barge at public barging point, where the exact location will be determined by the contractor(s). Therefore, no installation of temporary support facility and dredging or excavation is expected. Notwithstanding the above, accidental release of excavated sediment during transport to the disposal areas by barges, will increase the SS and contaminant level of receiving water and deteriorate water quality.

5.6.4          Adoption of the guidelines and good site practices for handling and disposal of construction discharges as specified in Section 5.8 would minimize the potential impacts.

Construction Site Runoff

5.6.5          Surface runoff generated from the construction site may contained increased loads of SS and contaminants. Potential pollution sources of site runoff may include:

¡¤         Runoff and erosion of exposed bare soil and earth, drainage channel, earth working area and stockpiles;

¡¤         Release of any bentonite slurries, concrete washings and other grouting materials with construction runoff or storm water;

¡¤         Wash water from dust suppression sprays and wheel washing facilities; and

¡¤         Fuel, oil and lubricants from maintenance of construction vehicles and equipment.

5.6.6          During rainstorms, site runoff would wash away the soil particles on work areas and areas with the topsoil exposed.  The construction runoff is generally characterized by high concentrations of SS.  Release of uncontrolled site runoff would increase the SS levels, turbidity and cause depletion of dissolved oxygen levels in the nearby water environment.  Site runoff may also wash away contaminants and therefore cause water pollution.

5.6.7          Windblown dust would be generated from exposed soil surfaces in the works areas.  It is possible that windblown dust would fall directly onto the nearby water bodies when a strong wind occurs.  Dispersion of dust within the works areas may increase the SS levels in surface runoff causing a potential impact to the nearby sensitive receivers.

5.6.8          Total construction area of about 0.3087 km2, involving SHD Replanning Works, construction of SHO, western access and local assesses outside the proposed podium deck would generate surface runoff during construction phase. For worst case scenario assessment, it is assumed that all works area is 100% active and paved.

5.6.9          According to the ¡°DSD Stormwater Drainage Manual¡±, annual rainfall in Hong Kong is around 2,200mm. However, the EPD study namely "Update on Cumulative Water Quality and Hydrological Effect of Coastal Developments and Upgrading of Assessment Tool (Update Study)¡± suggested that only rainfall events of sufficient intensity and volume would give rise to runoff and that runoff percentage is about 44% and 82% for dry and wet season, respectively.  Therefore, only 1,386mm of 2,200mm annual rainfall would be considered as effective rainfall that would generate runoff (i.e. 1386mm=2200mm¡Á(82%+44%)/2). 

5.6.10       More surface runoff would be generated from the paved area than from the unpaved area.  Making reference to the ¡°DSD Stormwater Drainage Manual¡±, about 0.9 as the runoff coefficient for paved areas is assumed.  The average daily runoff generated from the construction area is estimated to be about 1,055 m3/day (= 0.9 ¡Á 1386mm/year ¡Á 0.3087km2). Given that SHD, with an area of about 0.3 km2 is an existing facility and any runoff generated would be discharged to existing drainage system, hence adverse water quality impact is not expected. 

5.6.11       It is also anticipated that with the implementation of appropriate measures to control runoff and drainage from the construction site, disturbance of water bodies would be avoided and deterioration in water quality would be minimal.  Thus, unacceptable impacts on the water quality are not expected, provided that the relevant mitigation measures as specified in Section 5.8 are properly implemented.

Construction Works near Channelized Watercourse / Ditch

5.6.12       As mentioned in Section 6.6.1, upgrading and reprovision of sewerage network would be required for this Project, with a rising main size of 200mm dia. which is the same size of the existing rising main and a standby 200mm dia. rising main for conveying the flow from the on-site pumping station to public sewerage system.  Pollution of inland waters may occur due to potential release of construction wastes and wastewater from the adjacent works area. Construction wastes and wastewater are generally characterized by high concentration of SS and elevated pH.  Adoption of good housekeeping and mitigation measures would reduce the generation of construction wastes and potential water quality impact. The implementation of measures to control site run-off will be adopted for the works adjacent to the inland channelized watercourse/ditch in order to prevent run-off with high levels of SS from entering the water environment. With the implementation of Best Management Practices and provision of mitigation measures as specified in ProPECC Note PN 1/94 ¡°Construction Site Drainage¡± and ETWB TC (Works) No. 5/2005 ¡°Protection of natural streams / rivers from adverse impacts arising from construction works¡± where applicable (as detailed in Section 5.8) , it is anticipated that water quality impacts would be minimised.

Accidental Spillage

5.6.13       The use of chemicals such as engine oil and lubricants, and their storage as waste materials has the potential to create impacts on the water quality if spillage occurs and enters adjacent water environment.  Waste oil may infiltrate into the surface soil layer, or runoff into the nearby water environment, increasing hydrocarbon levels.  The potential impacts could however be mitigated by practical mitigation measures and good site practices (as given in Section 5.8).

Sewage Effluent from Construction Workforce

5.6.14       During the construction of the Project, the workforce on site will generate sewage effluents, which are characterized by high levels of BOD, ammonia and E. coli counts. Based on the DSD Sewerage Manual, the sewage production rate for construction workers is estimated at 0.35 m3 per worker per day. For every 100 construction workers working simultaneously at the construction site, about 35 m3 of sewage would be generated per day. Potential water quality impacts upon the local drainage and fresh water system may arise from these sewage effluents, if uncontrolled.

5.6.15       However, this temporary sewage can be adequately treated by interim sewage treatment facilities, such as portable chemical toilets. Provided that sewage is not discharged directly into storm drains or inland waters adjacent to the construction site, temporary sanitary facilities would be used and properly maintained, and mitigation measures as recommended in Section 5.8 are adopted as far as practicable, it is unlikely that sewage generated from the sites would have a significant water quality impact. 

Groundwater from Contaminated Areas, Contaminated Site Runoff and Wastewater from Land Decontamination

5.6.16       It is identified that some of the construction works areas might have land contamination issues.  Proper land contamination remediation and mitigation measures are proposed in Section 8.  Any contaminated material disturbed, or material which comes into contact with the contaminated material, has the potential to be washed with site runoff into drainage system.  Any wastewater discharge from land decontamination processes could also adversely affect the nearby water environment.  Excavated contaminated materials would be properly stored, housed and covered to avoid generation of contaminated runoff. Open stockpiling of contaminated materials will not be allowed. Any contaminated site runoff and wastewater from land decontamination activities will be properly treated and disposed in compliance with the requirements of the TM-DSS.  Mitigation measures for contaminated site runoff and wastewater from land decontamination are recommended in Section 5.8.  With proper implementation of the recommended mitigation measures, the potential water quality impacts arising from the land decontamination works would be minimised. 

5.6.17       Groundwater pumped out or from dewatering process during excavation works in the contaminated areas might be potentially contaminated. Any contaminated groundwater will be either properly treated or properly recharged into the ground in compliance with the requirements of the TM-DSS. No direct discharge of contaminated groundwater will be adopted. Mitigation measures and monitoring requirements for contaminated groundwater discharge / recharge are recommended in Section 5.8. With proper implementation of the recommended mitigation measures, no unacceptable water quality would be expected from the groundwater generated from contamination areas.

Operational Phase

5.6.18       Potential sources of water quality impact associated with the operation of the Project include:

¡¤         Sewage and wastewater discharge;

¡¤         Emergency Discharge from Sewage Pumping Station;

¡¤         Surface and road runoff from SHO and Reprovisioned SHD; and

¡¤         Accidental spillage of chemicals.

Sewage and Wastewater Discharge

5.6.19       Sewage effluent generated from the operation of SHO and Reprovisioned SHD and wastewater discharged from the train washing, heavy cleaning and maintenance facilities in Reprovisioned SHD would be the key potential sources of water pollution. With reference to the assessment of sewerage and sewage treatment implications for the Project provided in Section 6, the average sewage flow from the SHO and Reprovisioned SHD is estimated to be about 1,229m3 per day.  Adequate sewerage and sewage treatment facilities will be provided for the Project development to avoid direct discharge of sewage and wastewater to the nearby drainage system and water environment. Assessment on the sewerage and sewage treatment implications for the Project is provided in Section 6.

Emergency Discharge from Sewage Pumping Station

5.6.20       New Sewage Pumping Station (SPS) including two duty and one standby pump is proposed under the Project as shown in Drawing No. NEX1062/S/SHD/ACM/Z10/181.  The normal operation of this new SPS would actually have beneficial effect through the enhancement of the efficiency of the sewerage system.  In order to minimize the consequences of pump and/or power failure, various precautionary measures as recommended in Sections 6.6.3 to 6.6.5 will be incorporated in the design of the proposed SPS.  The recommended precautionary measures is summarized below:

¡¤         Provision of twin rising mains (Section 6.6.1 refers);

¡¤         Provision of two duty pumps and one standby pump at SPS (Section 6.6.3 refers);

¡¤         Provision of dual-feed power supply (Section 6.6.3 refers);

¡¤         Provision of emergency storage tank with 1-hour ADWF capacity (Section 6.6.3 refers);

¡¤         Provision of either ductile iron (DI) pipes or high-density polyethylene pipe (HDPE) and fittings with sufficient strength to resist the pumping pressure and external load. Thrust blocks, supports or relevant fittings should also be provided to avoid pipe bursting and leakage (Section 6.6.4 refers);

¡¤         Provision of Main Control System (MCS) to provide real-time notification of alert signal in emergency situation (Section 6.6.5 refers);

¡¤         Provision of regular inspection, routine maintenance and repair from qualified personnel (Section 6.6.5 refers);

¡¤         Provision of on-site staff for 24-7 emergency repair service in case of emergency situations (Section 6.6.5 refers) to allow for resumption of pumping system operation within 1 hour after emergency repair in the event of any incident;

¡¤         Tankering away, if necessary, would be conducted as a last resort for proper disposal at public sewage treatment works to maximize buffer for emergency storage as far as practicable, in cases where the broken-down plant cannot be recovered in time to prevent the outflow of raw sewage (Section 6.6.5 refers); and

¡¤         Preparation of Operation and Maintenance (O&M) Manual to standardize operation and maintenance procedures (Section 6.6.5 refers).

5.6.21       With incorporation of the recommended preventive measures and no emergency discharge outlet at the sewage pumping station, no emergency sewage discharge during the operation of SHO and Reprovisioned SHD is anticipated, and thus the potential water quality impact in the extremely remote event that emergency sewage discharge does occur would be minimized.

Surface and Road Runoff from SHO and Reprovisioned SHD

5.6.22       Surface and road runoff to be generated from the Project is known as non-point source pollution. A small amount of oil, grease and grit may be deposited on the surfaces of the road / rail network within the site and these pollutants could be washed into the nearby drainage system during rainfall events. Surface runoff generated from other paved or developed areas within the development sites may also contain debris, refuse, dust from the roof of buildings and cleaning agents used for washing streets and building façade, which may also affect the quality of the nearby receiving water environment, if uncontrolled.

5.6.23       The ultimate Reprovisioned SHD and partial SHO will be located underneath the podium deck of SHD Topside Development.  Upon completion for each phase of SHD Topside Development, only positive impact with no worsen situation than current condition, in term of surface runoff production is expected.  The surface runoff collected from the podium deck of SHD Topside Development would be conveyed by its drainage system, then to downpipes in the utilities riser and subsequent manholes and gravity drains and finally be discharged to the existing box culverts to the marine waters.  Surface runoff generated from the podium deck has been assessed in the SHD Topside Development EIA, while surface runoff associated with the operation of this Project would only be generated from partial SHO, western access and local accesses outside the podium deck.  As such, an area of about 0.0087 km2 is anticipated to generate surface runoff when in operation. 

5.6.24       The average daily runoff generated from the area of SHO and Reprovisioned SHD is estimated to be about 30 m3/day (= 0.9 ¡Á 1386mm/year ¡Á 0.0087km2).  Pollution loading was calculated and tabulated in Table 5.4 below. The water quality as well as hydrology and flow regime impacts, if any, would be limited and localized due to only about 30 m3/day surface runoff with insignificant addition pollution loadings will be generated, and hence no adverse impacts would be expected.

 

Table 5.4    Pollution Loading from Surface Run-off

Paved Area

(km2)

Rainfall Intensity (mm/year)

Average Daily Runoff (m3/day)

1-Silt Trap Removal Efficiency

Pollutant Concentration (mg/L)(1)

Loading (kg/day)

BOD5

TN

TP

BOD5

TN

TP

0.0087

1386

30

0.8

22.5

2.0

0.2

0.54

0.048

0.0048

Notes:

(1)    Data source: Update on Cumulative Water Quality and Hydrological Effect of Coastal Developments and Upgrading of Assessment Tool ¨C Pollution Loading Inventory Report (EPD).

5.6.25       Storm water control measures including Best Management Practices (BMPs), would be implemented within the development site as described in Section 5.8.  It is expected that with proper implementation of the recommended measures, the water quality impact due to the non-point source pollution from the Project would be minimized.

Accidental Spillage of Chemicals

5.6.26       A number of chemicals such as paints, lubricants and used batteries would be stored onsite and be used for maintenance activities in SHO and Reprovisioned SHD. Adverse water quality impacts arising from chemical spillage can be minimised by appropriate storage management and drainage system design as recommended in Section 5.8.

5.7              Cumulative Impacts from Concurrent Project

5.7.1          The construction of the Project potentially overlap with the construction period of other nearby concurrent projects as identified in Section 2.5.  However, with incorporation of the recommended mitigation measures during the construction and operational phases of this Project, the water quality impact generated from the Project would be localized and no adverse cumulative water quality impacts would be expected.

5.8              Recommended Water Quality Mitigation Measures

Construction Phase

General Construction Activities and Construction Site Runoff

5.8.1          Control of potential pollution of nearby water bodies during the construction phase of the Project should be achieved by measures to:

¡¤         prevent or minimise the likelihood of pollutants (generated from construction activities) being in contact with rainfall or runoff; and

¡¤         abate pollutants in the stormwater surface runoff prior to the discharge of surface runoff to the nearby water bodies.

Construction Site Runoff

5.8.2          It is important that Best Management Practices (BMPs) of mitigation measures in controlling water pollution and good site management, as specified in the ProPECC PN 1/94 ¡°Construction Site Drainage¡± are followed, where applicable, to prevent runoff with high level of SS from entering the surrounding waters.

5.8.3          All effluent discharged from the construction site should comply with the standards stipulated in the TM-DSS. The following measures are recommended to protect water quality of the nearby water, and when properly implemented should be sufficient to adequately control site discharges so as to avoid water quality impacts.

5.8.4          Surface and road runoff from construction sites should be discharged into storm drains via adequately designed sand/silt removal facilities such as sand traps, silt traps and sedimentation basins.  Channels or earth bunds or sand bag barriers should be provided on site during construction works to properly direct stormwater to such silt removal facilities. Perimeter channels should be provided on site boundaries where necessary to intercept storm runoff from outside the site so that it will not wash across the site. Catchpits and perimeter channels should be constructed in advance of site formation works and earthworks.

5.8.5          Silt removal facilities, channels and manholes should be maintained and the deposited silt and grit should be removed regularly, at the onset of and after each rainstorm to prevent local flooding.  Any practical options for the diversion and re-alignment of drainage should comply with both engineering and environmental requirements in order to provide adequate hydraulic capacity of all drains. 

5.8.6          Construction works should be programmed to minimize soil excavation works in rainy seasons (April to September).  If soil excavation cannot be avoided in these months or at any time of year when rainstorms are likely, for the purpose of preventing soil erosion, temporary exposed slope surfaces should be covered e.g. by tarpaulin, and temporary access roads should be protected by crushed stone or gravel, as excavation proceeds.  Intercepting channels should be provided (e.g. along the crest / edge of excavation) to prevent storm runoff from washing across exposed soil surfaces.  Arrangements should always be in place in such a way that adequate surface protection measures can be safely carried out well before the arrival of a rainstorm.

5.8.7          Earthworks final surfaces should be well compacted and the subsequent permanent work or surface protection should be carried out immediately after the final surfaces are formed to prevent erosion caused by rainstorms.  Appropriate drainage like intercepting channels should be provided where necessary.

5.8.8          Measures should be taken to minimize the ingress of rainwater into trenches. If excavation of trenches in wet seasons is necessary, they should be dug and backfilled in short sections.  Rainwater pumped out from trenches or foundation excavations should be discharged into storm drains via silt removal facilities.

5.8.9          If bentonite slurries are required for any construction works, they should be reconditioned and reused wherever practicable to minimise the disposal volume of used bentonite slurries.  Temporary enclosed storage locations should be provided on-site for any unused bentonite that needs to be transported away after the related construction activities are completed. Requirements as stipulated in ProPECC Note PN 1/94 should be closely followed when handling and disposing bentonite slurries.

5.8.10       Open stockpiles of construction materials (e.g. aggregates, sand and fill material) on sites should be covered with tarpaulin or similar fabric during rainstorms. 

5.8.11       Manholes (including newly constructed ones) should always be adequately covered and temporarily sealed so as to prevent silt, construction materials or debris from getting into the drainage system, and to prevent storm runoff from getting into foul sewers.  Discharge of surface runoff into foul sewers must always be prevented in order not to unduly overload the foul sewerage system.

5.8.12       Good site practices should be adopted to remove rubbish and litter from construction sites so as to prevent the rubbish and litter from spreading from the site area.  It is recommended to clean the construction sites on a regular basis.  Also, as discussed in Section 7.5.21 and 7.5.22, the following mitigation measures related to the transportation of the sediment should be implemented to minimize the potential water quality impact:

¡¤         Loading of the excavated sediment to the barge shall be controlled to avoid splashing and overflowing of the sediment slurry to the surrounding water.

¡¤         The barge transporting the sediments to the designated disposal sites shall be equipped with tight fitting seals to prevent leakage and shall not be filled to a level that would cause overflow of materials or laden water during loading or transportation.  

¡¤         Monitoring of the barge loading shall be conducted to ensure that loss of material does not take place during transportation. Transport barges or vessels shall be equipped with automatic self-monitoring devices as specified by the Director of Environmental Protection (DEP). 

5.8.13       There is a need to apply to EPD for a discharge licence for discharge of effluent from the construction site under the WPCO.  The discharge quality must meet the requirements specified in the discharge licence.  All the runoff and wastewater generated from the works areas should be treated so that it satisfies all the standards listed in the TM-DSS.  The beneficial uses of the treated effluent for other on-site activities such as dust suppression, wheel washing and general cleaning etc., can minimise water consumption and reduce the effluent discharge volume.  If monitoring of the treated effluent quality from the works areas is required during the construction phase of the Project, the monitoring should be carried out in accordance with the relevant WPCO licence.

Water for Bored Piling Works

5.8.14       Water used in ground boring and drilling for site investigation or rock / soil anchoring should be re-circulated as far as practicable after sedimentation. When there is a need for final disposal, the wastewater should be discharged into storm drains via silt removal facilities.

Wheel Washing Water

5.8.15       Wash-water from wheel washing facility should have been treated by silt removal facilities before discharging into storm drains. Treated wash-water could be used as dust suppression measures as far as practicable. The section of access road between the wheel washing bay and the public road should be paved to reduce vehicle tracking of soil and to prevent silty water from entering public road and drains.

Construction Works near Channelized Watercourse/Ditch

5.8.16       For minimization of potential water quality impacts from the works to nearby inland channelized watercourse/ditch near SHWSTW, the practices outlined in ProPECC Note PN 1/94 ¡°Construction Site Drainage¡± and ETWB TC (Works) No.5/2005 ¡°Protection of natural streams / rivers from adverse impacts arising from construction works¡± should be adopted where applicable.  Relevant mitigation measures are listed below:

¡¤         The use of less or smaller construction plants may be specified in works area close to the inland water bodies.

¡¤         Temporary storage of material (e.g. equipment, filling materials, chemicals and fuel) and temporary stockpile of construction materials should be located well away from watercourse/ditch when carrying out of the construction works.

¡¤         Stockpiling of construction materials and dusty materials should be covered and located away from any watercourse/ditch.

¡¤         Construction debris and spoil should be covered up and / or disposed of as soon as possible to avoid being washed into the nearby water receivers.

¡¤         Construction activities, which generate large amount of wastewater, should be carried out in a distance away from the watercourse/ditch, where practicable.

¡¤         Construction effluent, site run-off and sewage should be properly collected and / or treated.

Accidental Spillage of Chemicals

5.8.17       Contractor must register as a chemical waste producer if chemical wastes would be produced from the construction activities.  The Waste Disposal Ordinance (Cap 354) and its subsidiary regulations in particular the Waste Disposal (Chemical Waste) (General) Regulation, should be observed and complied with for control of chemical wastes. The Contractor is also recommended to develop management procedures for chemicals used and prepare an emergency spillage handling procedure to deal with chemical spillage in case of accident occurs.

5.8.18       Any service shop and maintenance facilities should be located on hard standings within a bunded area, and sumps and oil interceptors should be provided.  Maintenance of vehicles and equipment involving activities with potential for leakage and spillage should only be undertaken within the areas appropriately equipped to control these discharges.

5.8.19       Disposal of chemical wastes should be carried out in compliance with the Waste Disposal Ordinance.  The Code of Practice on the Packaging, Labelling and Storage of Chemical Wastes published under the Waste Disposal Ordinance details the requirements to deal with chemical wastes.  General requirements are given as follows:

¡¤         Suitable containers should be used to hold the chemical wastes to avoid leakage or spillage during storage, handling and transport.

¡¤         Chemical waste containers should be suitably labelled, to notify and warn the personnel who are handling the wastes, to avoid accidents.

¡¤         Storage area should be selected at a safe location on site and adequate space should be allocated to the storage area.

Sewage Effluent from Construction Workforce

5.8.20       No discharge of sewage to the storm water system and marine water will be allowed. Adequate and sufficient portable chemical toilets should be provided in the works areas to handle sewage from construction workforce.  A licensed waste collector should be employed to clean and maintain the chemical toilets on a regular basis.

5.8.21       Notices should be posted at conspicuous locations to remind the workers not to discharge any sewage or wastewater into the surrounding environment.  Regular environmental audit of the construction site should be conducted to provide an effective control of any malpractices and achieve continual improvement of environmental performance on site.

Groundwater from Contaminated Areas, Contaminated Site Runoff and Wastewater from Land Decontamination

5.8.22       Remediation of contaminated land should be properly conducted following the recommendations of Land Contamination Assessment to be conducted in future. Any excavated contaminated material and exposed contaminated surface should be properly housed and covered to avoid generation of contaminated runoff. Open stockpiling of contaminated materials should not be allowed.  Any contaminated runoff or wastewater generated from the land decontamination processes should be properly collected and diverted to wastewater treatment facilities (WTF) as necessary.  The WTF shall deploy suitable treatment processes (e.g. oil interceptor / activated carbon) to reduce the pollution level to an acceptable standard and remove any prohibited substances (such as total petroleum hydrocarbon) to an undetectable range. All treated effluent from the wastewater treatment system shall meet the requirements as stated in TM-DSS and should be either discharged into the foul sewers or tankered away for proper disposal.

5.8.23       No direct discharge of groundwater from contaminated areas should be adopted.  Prior to any excavation works within the potentially contaminated areas, the baseline groundwater quality in these areas should be reviewed based on the past relevant site investigation data and any additional groundwater quality measurements to be performed with reference to Guidance Note for Contaminated Land Assessment and Remediation and the review results should be submitted to EPD for examination. If the review results indicated that the groundwater to be generated from the excavation works would be contaminated, this contaminated groundwater should be either properly treated or properly recharged into the ground in compliance with the requirements of the TM-DSS. If wastewater treatment is to be deployed for treating the contaminated groundwater, the wastewater treatment unit shall deploy suitable treatment processes (e.g. oil interceptor / activated carbon) to reduce the pollution level to an acceptable standard and remove any prohibited substances (such as total petroleum hydrocarbon) to an undetectable range. All treated effluent from the wastewater treatment plant shall meet the requirements as stated in the TM-DSS and should be either discharged into the foul sewers or tankered away for proper disposal.

5.8.24       If deployment of wastewater treatment is not feasible for handling the contaminated groundwater, groundwater recharging wells should be installed as appropriate for recharging the contaminated groundwater back into the ground. The recharging wells should be selected at places where the groundwater quality will not be affected by the recharge operation as indicated in section 2.3 of TM-DSS.  The baseline groundwater quality should be determined prior to the selection of the recharge wells, and submit a working plan to EPD for agreement.  Pollution levels of groundwater to be recharged shall not be higher than pollutant levels of ambient groundwater at the recharge well. Groundwater monitoring wells should be installed near the recharge points to monitor the effectiveness of the recharge wells and to ensure that no likelihood of increase of groundwater level and transfer of pollutants beyond the site boundary. Prior to recharge, free products should be removed as necessary by installing the petrol interceptor.  The Contractor should apply for a discharge licence under the WPCO through the Regional Office of EPD for groundwater recharge operation or discharge of treated groundwater.

Operational Phase

Sewage and wastewater discharge

5.8.25       Sewage effluents generated from the operation of Reprovisioned SHD and SHO should be properly collected and diverted to public sewers for proper treatment and disposal.  Wastewater generated by train washing, heavy cleaning and maintenance facilities should be collected and diverted to the depot sewerage system. Standard oil/grit interceptors/chambers should be provided where necessary to remove the oil, lubricants, grease, silt and grit from wastewater generated from train washing, heavy cleaning and maintenance facilities before discharge to the depot sewerage system.  Discharge of any effluent to the public sewers will be subject to control under the WPCO and the relevant dischargers shall apply to EPD for a discharge licence for discharge of commercial and industrial effluent and the discharge quality must satisfy all the standards listed in the TM-DSS and meet the requirements specified in the discharge licence. Assessment of the sewage and sewerage implications for this Project is presented in Section 6.

5.8.26       The practices outlined in ProPECC PN 5/93 for handling, treatment and disposal of operational stage effluent should also be adopted where applicable.

Emergency Discharge from Sewage Pumping Station

5.8.27       In order to minimise the consequences of pump and/or power failure, the following precautionary measures will be incorporated in the design of the SPS (Sections 6.6.1 to 6.6.5 refer):

¡¤         Provision of twin rising mains;

¡¤         Provision of two duty pumps and one standby pump at SPS;

¡¤         Provision of dual-feed power supply;

¡¤         Provision of emergency storage tank with 1-hour ADWF capacity;

¡¤         Provision of either ductile iron (DI) pipes or high-density polyethylene pipe (HDPE) and fittings with sufficient strength to resist the pumping pressure and external load. Thrust blocks, supports or relevant fittings should also be provided to avoid pipe bursting and leakage;

¡¤         Provision of Main Control System (MCS) to provide real-time notification of alert signal in emergency situation;

¡¤         Provision of regular inspection, routine maintenance and repair from qualified personnel;

¡¤         Provision of on-site staff for 24-7 emergency repair service in case of emergency situations to allow for resumption of pumping system operation within 1 hour after emergency repair in the event of any incident;

¡¤         Tankering away, if necessary, would be conducted as a last resort for proper disposal at public sewage treatment works to maximize buffer for emergency storage as far as practicable, in cases where the broken-down plant cannot be recovered in time to prevent the outflow of raw sewage; and

¡¤         Preparation of Operation and Maintenance (O&M) Manual to standardize operation and maintenance procedures.

Best Storm Water Management Practices and Storm Water Pollution Control Plan

5.8.28       Mitigation measures including Best Management Practices (BMPs) to reduce storm water pollution arising from the Project are as follows.

Design Measures

5.8.29       Exposed surface shall be avoided within the SHO and Reprovisioned SHD to minimise soil erosion.  Reprovisioned SHD will be fully decked to avoid runoff, while majority area of the SHO will be decked, whereas the area outside the podium deck would be hard paved.

5.8.30       The drainage system should be designed to avoid flooding.

Devices and Facilities

5.8.31       Screening facilities such as standard gully grating and trash grille, with spacing which is capable of screening large substances such as fallen leaves and rubbish should be provided at the inlet of drainage system. 

5.8.32       Road gullies with standard design and silt traps and oil interceptors should be incorporated during the detailed design to remove particles present in stormwater runoff, where appropriate. 

Administrative Measures

5.8.33       Good management measures such as regular cleaning and sweeping of road surface are suggested. The road surface cleaning should also be carried out prior to occurrence rainstorm.

5.8.34       Manholes, as well as stormwater gullies, ditches provided at the development sites should be regularly inspected and cleaned (e.g. monthly).  Additional inspection and cleansing should be carried out before forecast heavy rainfall.

Accidental Spillage of Chemicals

5.8.35       Chemical should be properly stored on site within bunded area and separate drainage system should be provided as appropriate to avoid any spilled chemicals from entering the storm drain in case of accidental spillage. Also, adequate tools for cleanup of spilled chemicals should be provided on site and appropriate training shall be provided to staffs to further prevent potential adverse water quality impacts.

5.9              Evaluation of Residual Impacts

5.9.1          With the full implementation of the recommended mitigation measures for the construction and operational phases of the proposed Project, no residual impact on water quality are anticipated.

5.10           EM&A Requirements

5.10.1       It is recommended that regular site inspections during the construction phase should be undertaken to inspect the construction activities and works areas in order to ensure the recommended mitigation measures are properly implemented. Details of the audit requirements are provided in the stand-alone EM&A Manual for the Project.

5.11           Conclusions

Construction Phase

5.11.1       The key issue from the land-based construction activities would be the potential release of construction site runoff from surface works areas, wastewater from general construction activities, pollution to nearby watercourse/ditch, accidental spillage and sewage from construction workforce, as well as the potential groundwater from contaminated areas, if any, contaminated site runoff and wastewater from land decontamination. Minimisation of water quality deterioration could be achieved through implementing adequate mitigation measures. Regular site inspections should be undertaken routinely to inspect the construction activities and works areas in order to ensure the recommended mitigation measures are properly implemented.

Operational Phase

5.11.2       The key source of potential impact on water quality during the operational phase will be the sewage and wastewater generated from the SHO and Reprovisioned SHD. However, no adverse water quality impact associated with the operational phase would be anticipated, provided that adequate sewerage and sewage treatment facilities are properly implemented to accommodate all the sewage effluents.

5.11.3       In view of the potential adverse effect of emergency discharge from sewage pumping station, various precautionary measures are proposed to be incorporated in the design of the SPS to avoid consequences of pump and/or power failure to the maximum practicable extent.   With the incorporation of the precautionary measures, no emergency sewage discharge during the operation of SHO and Reprovisioned SHD is anticipated and the potential water quality impact in the unlikely event that discharge does occur would be minimised.

5.11.4       Another source of potential impact during the operational phase will be the runoff or non-point source pollution from the partial SHO, western access and local accesses outside the podium deck as well as accidental spillage of chemical.  Storm water control measures including adequate storm drainage system with suitable pollutant removal devices and best storm water management practices are recommended for the Project to minimise the non-point source pollution. Proper storage and management, as well as the provision of a separate drainage system are recommended to avoid pollution from chemical spillage. With proper implementation of the recommended mitigation measures, it is anticipated that the water quality impacts associated with the non-point source discharge and chemical spillage would be minimised.