9.1.1.1
Section
9 of the EIA Report presents the assessment of potential landfill gas (LFG) hazard
to the Project.
9.2.1.1
Relevant legislation and associated guidance notes
applicable to the assessment of the LFG hazards include:
·
Section 1.1(f)
in Annex 7 of the Technical Memorandum on EIAO (EIAO-TM);
·
Section 3.3 in
Annex 19 of the EIAO-TM;
·
Landfill Gas
Hazard Assessment for Development Adjacent to Landfills
(ProPECC PN 3/96);
·
Landfill Gas
Hazard Assessment Guidance Note (1997) (EPD/TR8/97, Guidance Note).
9.2.1.2
ProPECC PN 3/96 and
the Guidance Note provide an assessment framework to be followed when
evaluating the risks related to developments described under Section 6.5,
Chapter 9 of the Hong Kong Planning Standards and Guidelines. ProPECC PN 3/96 and
Guidance Note apply to all developments proposed within a Landfill Consultation
Zone, which is the area of land surrounding the landfill boundary as defined by
a line running parallel to and 250 m away from the edge of the waste if this
can be identified or, if not, the recognized landfill site boundary.
9.2.1.3
In accordance with aforementioned
framework, the following tasks have been undertaken to assess potential
LFG hazard associated with the closed and restored Ngau Tam Mei landfill (NTML)
to potentially sensitive elements of the Project area situated within the NTML
Consultation Zone.
·
A review of
background information (including landfill gas monitoring data) and studies
related to the NTML including sections 14 (Landfill Gas Hazard Assessment) and
Section 15 (Impacts on the Restored Ngau Tam Mei Landfill) of approved EIA, AEIAR-143/2009 for the Hong Kong Section of Guangzhou - Shenzhen - Hong Kong
Express Rail Link;
·
Identification
of the nature and extent of the source, including the likely concentrations and
/ or amounts of hazardous emissions with potential to impact the Project;
·
Identification
of possible subsurface pathways and the nature of these pathways through which
hazardous emissions must traverse if they are to reach the development;
·
Identification
of potentially sensitive receivers / elements of the development that maybe
susceptible to landfill gas ingress/accumulation;
·
Qualitative
assessment of the degree of risk which the hazardous emissions may pose to aspects
of the development taking account of each source-pathway-target combination;
and
·
A description of
possible precautionary measures (if needed) during construction and operation
phases assuming development constraints are surmountable, and identification of
any monitoring requirements during construction and operation.
9.3.1
Criteria
9.3.1.1
In accordance with the Landfill Gas Hazard
Assessment Guidance Note, risk associated with landfill gas may be evaluated by
assessment of the following three criteria:
·
Source –
location, nature and likely quantities/ concentrations of landfill gas with
potential to affect the development;
·
Pathway – the
ground and groundwater conditions through which landfill gas must pass in order to reach the development; and
·
Target –
elements of a development that may be sensitive to the effects of landfill
gas.
9.3.2.1
The classification of the Source (i.e., Ngau Tam
Mei Landfill) is undertaken as follows:
Minor
|
Landfill sites at which gas controls have been installed
and proven to be effective by comprehensive monitoring which has demonstrated
that there is no migration of gas beyond the landfill boundary (or any
specific control measures) and at which control of gas does not rely solely
on an active gas extraction system or any other single control measure which
is vulnerable to failure; or old landfill sites where the maximum
concentration of methane within the waste, as measured at several locations
across the landfill and on at least four occasions over a period of at least
3 months (preferably longer), is less than 5% by volume (v/v).
|
Medium
|
Landfill site at which some form of gas control has been
installed (e.g. lined site or one where vents or barriers have been retrospectively
installed) but where there are only limited monitoring data to demonstrate
its efficacy to prevent migration of gas; or a landfill site where
comprehensive monitoring has demonstrated that there is no migration of gas
beyond the landfill boundary but where the control of gas relies solely on an
active gas extraction system or any other single control system which is
vulnerable to failure.
|
Major
|
Recently filled landfill site at which there is little or
no control to prevent migration of gas or at which the efficacy of the gas
control measures has not been assessed; or any landfill site at which
monitoring has demonstrated that there is significant migration of gas beyond
the site boundary.
|
9.3.2.2
The “significance” of migration is assessed by
reference to the concentration, frequency and location at which gas is detected
at routinely monitored locations, especially those peripheral
to the area of waste deposition. Any
concentration of methane or carbon dioxide > 5% v/v above background levels
in any monitoring well outside the landfill boundary may indicate significant
migration. Concentrations > 1% v/v
methane or 1.5% v/v carbon dioxide (above background) indicate less than
adequate control of the gas at source.
9.3.2.3
If monitoring data demonstrates that there is no
migration of gas and little danger of gas controls failing (e.g., if these
comprise solely of passive measures such as a liner) it can be assumed that the
site represents a "Minor" Source.
Where there is no gas migration but this may be
as a result of a single, "vulnerable" control measure (e.g., an
active extraction system with no warning of failure), the site should be
regarded as a "Medium" or even a "Major" Source depending
on the other factors (e.g., size of site and age of waste). Where the
effectiveness of gas controls has not been proven by off-site monitoring,
assessment always errs on the side of caution and is undertaken on the same
basis as if the controls were not in place.
9.3.2.4
The reliability of the monitoring to assess the
efficacy of gas control needs to take account of the design, number and
locations of monitoring points and the frequency and duration over which
monitoring has been undertaken. Monitoring should have been undertaken under
different weather conditions including periods of low or falling atmospheric
pressure.
9.3.3.1
The broad classification is as follows:
Very short / direct
|
Path
length <50m for unsaturated permeable strata and fissured rock or <
100m for man-made conduits
|
Moderately short / direct
|
Path
length of 50-100m for unsaturated permeable soil or fissured rock or 100-250m
for man-made conduits
|
Long / indirect
|
Path
length of 100-250m for unsaturated permeable soils and fissured rock
|
9.3.3.2
Factors affecting the extent of gas migration
such as soil permeability or spacing and direction of the fissures/joints,
vadose zone thickness and the topography and nature of ground over the
potential pathway need to be considered.
If a preferential pathway from the landfill to the development area exists the pathway is classified as "direct/short"
even if it is longer than 100m.
9.3.4.1
Target sensitivities are classified as follows:
High sensitivity
|
Buildings
or structures with ground level or below ground rooms/voids or into which
services enter directly from the ground and to which members of the general public have unrestricted access or which contain
sources of ignition. This would
include any developments where there is a possibility of additional
structures being erected directly on the ground on an ad hoc basis and thereby
without due regard to the potential risks.
|
Medium sensitivity
|
Buildings,
structures or service voids where there is access
only by authorized, well trained personnel, such as the staff of utility
companies, who have been briefed on the potential hazards relating to
landfill gas and the specific safety procedures to be followed or deep excavations.
|
Low sensitivity
|
Buildings/structures
which are less prone to gas ingress by virtue of their foundation design
(such as those with a raised floor slab). Shallow excavations and
developments which involve essentially outdoor activities but where evolution
of gas could pose potential problems.
|
9.3.5
Risk Categorization
9.3.5.1
Having determined the categories of source,
pathway and target, qualitative assessment of overall risk is made by reference
to Table 9.1. The potential implications associated with the
various qualitative risk categories are summarized in Table 9.2.
Table 9.1 Classification
of Risk Category
Source
|
Pathway
|
Target Sensitivity
|
Risk Category
|
Major
|
Very short / direct
|
High
|
Very
High
|
Medium
|
High
|
Low
|
Medium
|
Moderately
short / direct
|
High
|
High
|
Medium
|
Medium
|
Low
|
Low
|
Long / indirect
|
High
|
High
|
Medium
|
Medium
|
Low
|
Low
|
Medium
|
Very short
/ direct
|
High
|
High
|
Medium
|
Medium
|
Low
|
Low
|
Moderately short / direct
|
High
|
High
|
Medium
|
Medium
|
Low
|
Low
|
Long /
indirect
|
High
|
Medium
|
Medium
|
Low
|
Low
|
Very Low
|
Minor
|
Very short / direct
|
High
|
High
|
Medium
|
Medium
|
Low
|
Low
|
Moderately
short / direct
|
High
|
Medium
|
Medium
|
Low
|
Low
|
Very Low
|
Long / indirect
|
High
|
Medium
|
Medium
|
Low
|
Low
|
Very
Low
|
Table 9.2 Summary of
General Categorization of Risk
Category
|
Level of Risk
|
Implication
|
A
|
Very High
|
A less
sensitive form of development should be considered otherwise extensive
engineering measures, alarm systems and emergency action plans are likely to be
required.
|
B
|
High
|
Significant
engineering measures will be required to protect the planned development.
|
C
|
Medium
|
Engineering
measures will be required to protect the proposed development.
|
D
|
Low
|
Some
precautionary measures will be required to ensure that the planned
development is safe.
|
E
|
Very Low
|
No
precautionary measures are required.
|
9.3.5.2
Five generic forms of protection are used for
mitigation of hazards to a development. These
correspond to the risk levels set out in Table 9.3 with the terms used defined in Table 9.4.
Table 9.3 Generic
Protection Measures for Planning Stage Categorization
Category
|
Generic Protection Measures
|
A
|
Active
control of gas, barriers and detection systems
|
B
|
Active
control of gas, including barriers and detection systems (1)
|
C
|
Semi active
controls. Detection systems in some
situations
|
D
|
Passive
Control
|
E
|
No precautionary
measures required.
|
Note (1): The gas protection measures required to
allow the safe development of a Category A risk development will need to be
more extensive than those for a Category B risk development.
Table 9.4 Definition
of Control Terms
Terms
|
Definition
|
Active
|
Control of
gas by mechanical means e.g. ventilation to dilute gas, or extraction of gas
from the development site using fans or blowers.
|
Semi active
|
Use of wind
driven cowls and other devices which assist in the ventilation of gas but do
not rely on electrically powered fans.
|
Passive
|
Provision
of barriers to the movement of gas e.g. membranes in floors or walls, or in
trenches, coupled with high permeability vents such as gravel in trenches or
a clear void/permeable layer below structures.
|
Detection
|
Electronic
systems which can detect low concentrations of gas in the atmosphere and can
be linked to alarms and/or telemetry systems.
|
9.4.1.1
The closed and restored Ngau Tam Mei Landfill is
located to the southwest of The Project (Figure 9.1) with a small portion of
the planned development node lying within Ngau Tam Mei Landfill Consultation
Zone. In general, if a proposed
development is to be located within the Consultation Zone of a landfill, the Project
Proponent is required to undertake a landfill gas hazard assessment and submit
a report to the Environmental Protection Department (EPD) for vetting.
9.4.1.2
Where a proposed development or elements of a
development are of higher sensitivity, Landfill Gas Hazard Assessment (LFGHA)
is required to provide preliminary technical input for formulating and
evaluating development options by ascertaining the risk acceptability for
development within or in close proximity to a landfill
site.
9.4.1.3
Whilst development details are not finalized,
the Recommended Outline Development Plan indicates the affected area is planned
for development of an electricity substation with no public access.
9.4.1.4
A phased approach is adopted to qualitatively
assess landfill gas hazard risk and outline a range of possible mitigation
measures for consideration in the substation building design to afford an
appropriate level of protection dependent upon the calculated risk.
9.5.1.1
Infiltration of water into a landfill causes
gases to be generated as decomposition of organic materials occurs. Once
biodegradation has started the oxygen is soon exhausted and as no replenishment
of the free oxygen is available, the waste mass becomes anaerobic. During anaerobic fermentation methanogens
generate methane and carbon dioxide, the primary constituents of landfill
gas. A typical composition of LFG is
about 60% by volume of methane and 40% by volume of carbon dioxide, although
these percentages can vary widely depending on the site conditions. Also present are trace quantities of hydrogen sulphide, nitrogen and gaseous hydrocarbons.
9.5.1.2
Due to the high variability in the settings of
biodegradation, waste composition, and individual site characteristics, the
rate of degradation and the volume of landfill gas produced per unit of waste
can vary greatly. The generation of LFG is dependent on numerous environmental
conditions including temperature, pH, substrate availability, moisture content
and oxygen content.
9.5.2.1
Whilst methane has relatively low solubility in
water, is colourless and odourless,
and generally of little influence in groundwater quality, it occurs in gaseous
form in the unsaturated zone. The gas, which is also an asphyxiant, is highly
flammable and can be explosive when all the following conditions exist at the
same time:
·
Its
concentration in air is between 5% of the Lower Explosive Limit (LEL) and 15%
of the Upper Explosive Limit (UEL);
·
the gas is in a
confined space; and
·
a source of
ignition exists.
9.5.2.2
The relationship between methane and oxygen
where flammable mixtures can occur is shown in Plate 9.1 (from 30 CFR § 57.22003, MSHA
Illustration 27).
Plate 9.1 Flammability
Levels of Methane and Oxygen
9.5.2.3
Carbon dioxide, the other major component of
landfill gas is an asphyxiating gas and causes adverse health effects at
relatively low concentrations. The
long-term Occupational Exposure Limit (OEL) is 0.5% (v/v). Like methane, it is odourless
and colourless and its presence (or absence) can only
be confirmed by using appropriately calibrated portable detectors.
9.5.2.4
Gas density.
Methane is lighter than air whereas carbon dioxide is heavier than
air. Typical mixtures of landfill gas
are likely to have a density close to or equal to that of air. However, site conditions may result in a
ratio of methane to carbon dioxide which may make the gas mixture lighter or
heavier than air. As a result, landfill
gas may accumulate in either the base or top of any voids or confined spaces.
9.5.3.1
Given the potentially flammability, asphyxiant
properties and gaseous density of LFG, potential hazard arises in the event that LFG is able to migrate from the landfill
and accumulate in confined spaces such as building basements, underground car
parks, lift shafts, pumping stations, and maintenance chambers etc. For the same reasons, temporary structures
such as site huts and any other unventilated enclosures erected during
construction stage may also be exposed to landfill gas hazards.
9.5.4.1
Methane will migrate along pressure gradients
from areas where it is present at higher pressures to areas where it is present
at lower pressures. The primary mechanism for significant methane migration in
subsurface unsaturated soils is pressure-driven flow. Diffusion also occurs but
at rates too low to result in unacceptable indoor air concentrations under
reasonably likely scenarios.
9.5.4.2
The ability for landfill gas to migrate beyond
the waste boundary varies according to the type of landfill construction
details, presence of gas and leachate control measures, restoration details and
permeability of the ground through which gas must travel. Factors such as changes in atmospheric
pressure can also encourage gas migration.
9.5.4.3
If gas is able to
intercept any buried service routes especially where the utility has been laid
in an open conduit or the trench excavation has been backfilled around the
utility line with coarse gravel; these may also be susceptible to potential
hazards and/or they may act as preferential gas migration pathways.
9.6
Quantitative Assessment of Potential
Risk
9.6.1.1
Ngau Tam Mei Landfill occupies approximately
1.7ha and was formed in a natural stream valley generally oriented northeast to
southwest. A review of information
suggests that waste disposal occurred on an informal basis as early as 1963,
with more formal waste placement occurring between 1973 and 1975 resulting in
approximately 90,000m3 of waste disposed of prior to landfill
closure.
9.6.1.2
The landfill was configured as two platforms; an
upper platform between +32mPD and +36mPD which gently slopes from northeast to
southwest while the lower platform is between elevations +24mPD and +26mPD,
with a slightly steeper slope towards the southwest. The toe of the landfill is approximately
+16mPD.
9.6.1.3
Landfill restoration works in 1999 consisted of
placement of a “high integrity” capping system over the two platforms; minor
modifications to the existing leachate management system to provide for
collection and transport to an off-site treatment facility; installation of a
passive landfill gas (LFG) ventilation system; and on-going monitoring of
groundwater, leachate levels and landfill gas. The leachate management system
consists of a simple piping network installed at the base of the landfill, and
a concrete chamber near the toe of the lower slope. The landfill gas management system consists
of nine vertical passive vent pipes (VV-1 to VV-9) installed to depths to
3.0-9.0m across the upper platform and horizontal pipes installed in relatively
shallow trenches with vertical passive vent risers aligned around the perimeter
of the upper platform, along the toe of the upper slope and diagonally across
and down the lower slope. The network of
passive horizontal trenches and vertical risers around the perimeter of the
upper platform likely have a limited depth of waste beneath.
9.6.1.4
The passive venting system acts as the primary
control will minimize build-up of LFG pressure within the landfill and hence
reduce the potential for sub-surface off-site migration. Under the North-west New Territories
Landfills and Gin Drinkers Bay Landfill Restoration Contract No. EP/SP/30/95A
LFG a monitoring programme is in place which acts as
a secondary control to monitor the effectiveness of the passive venting system
and provide an early warning of any off-site migration of LFG. The locations of
LFG and groundwater monitoring wells are presented on Figure 9.3.
9.6.1.5
From the landfill gas monitoring data provided
for the period July 2019-June 2021, no methane is detected in any of the
monitoring wells within the waste boundary or outside the waste boundary. The majority of
wells are located to the west and south of the landfill and the nearest gas
monitoring wells to the Project boundary are monitoring wells A451 and DH408
located within the northern portion of the landfill. A451 is located at the top of the slope to
the east of waste boundary while DH408 is located close to the toe of the slope
to the west of waste boundary.
9.6.1.6
Averaged and ranged landfill gas monitoring data
for monitoring well A451 and DH408 over the 24 monitoring events between July
2019 and June 2021 is summarized in Table
9.5. Full monitoring data presented in Appendix 9.1.
Table 9.5 Summarized LFG monitoring data for A451
and DH408 July 2019- June 2021
Well
|
Parameter
|
July 2019-June 2021 Average
|
July 2019- June 2021
Range
|
A451
|
Methane
|
<0.1%
|
-
|
Carbon
Dioxide
|
6.13%
|
0.8-9.9%
|
Oxygen
|
14.48 %
|
8.8-20.6%
|
DH408
|
Methane
|
<0.1%
|
-
|
Carbon
Dioxide
|
2.25%
|
<0.1-6.1%
|
Oxygen
|
17.80%
|
12.9-20.7%
|
9.6.1.7
As shown in the monitoring data, there is no
evidence of accumulation of methane in any of the monitoring wells suggesting
that methane production within the waste mass is extremely low and/or that
pressure heads are insufficient to drive any lateral migration of gas beyond
the waste mass. Elevated carbon dioxide
concentrations are occasionally recorded an in the
absence of background soil gas concentrations for reference, a
conservative assumption is that the potential for off-site migration of
landfill gas cannot be eliminated.
9.6.1.8
Typical landfill gas production phases are shown
in Plate 9.2. The phase duration will
vary according to specific landfill conditions such as composition of the
waste, the restoration of the landfill, and the provision of landfill gas and
leachate management systems (Crawford and Smith 1985).
9.6.1.9
Based upon the timeline of historic operations
alone, gas production at Ngau Tam Mei Landfill may be in the latter stages of
Phase IV or beyond with end of methane production if the
majority of the organic matter has been degraded.
Plate 9.2 Production
phases of typical landfill gas (USEPA 1997)
9.6.2
Classification
of Source
9.6.2.1
NTML can be considered an ‘old landfill’ site
where the maximum concentration of methane within the waste, as measured at
(ongoing) monthly intervals as demonstrated by EPD data from August 2019 to
July 2021 is <0.1% by volume. Whilst
detections of carbon dioxide greater than 5% v/v have occasionally been measured
in A451 located outside the site’s eastern boundary and in DH408 located close
to the toe of the slope to the west of waste boundary but within the site
boundary; given the age of the landfill and likely phase of gas production,
volumes of gas evolution resulting in a pressure gradient and lateral migration
of gas are not anticipated to be significant especially as passive venting
creates a preferential vertical gas migration pathway from the landfill.
9.6.2.2
Assessment suggests that there is no serious LFG
migration problem therefore the restored NTML can be classified as a “Minor”
Source.
9.6.3.1
Potential pathways through which landfill gas
may migrate include; transmission along natural
pathways such as fissures or joints in rock; man-made pathways such as through
permeable backfill in utilities trenches; or a combination of both.
9.6.3.2
Recent groundwater monitoring data indicates the
thickness of the unsaturated zone of the subsurface through which gas may
migrate.
Table 9.6 Depth (m) to groundwater measured from
the wellhead cover
Well /Date
|
17-8-19
|
6-11-19
|
19-2-20
|
14-5-20
|
14-8-20
|
18-11-20
|
5-2-21
|
18-5-21
|
A458
|
4.33
|
6.99
|
8.57
|
9.18
|
4.02
|
8.09
|
8.94
|
9.45
|
DH403
|
16.12
|
17.04
|
19.12
|
19.94
|
19.52
|
19.31
|
20.22
|
20.71
|
DH404A
|
8.4
|
10.53
|
13.04
|
13.85
|
12.25
|
12.85
|
13.98
|
14.54
|
DH405
|
6.33
|
7.33
|
8.73
|
9.23
|
7.64
|
8.29
|
8.74
|
9.19
|
DH407
|
24.15
|
23.28
|
25.07
|
26.07
|
26.4
|
26.15
|
Dry
|
Dry
|
DH408
|
20.98
|
20.66
|
22.19
|
Dry
|
22.76
|
22.66
|
Dry
|
Dry
|
GW1
|
18.13
|
18.47
|
20.5
|
21.28
|
21.62
|
20.47
|
21.05
|
21.92
|
9.6.3.3
Whilst the gauged depths to groundwater show
that a considerable unsaturated zone thickness exists, a review of the
geological situation shows that the majority of NTML is underlain by coarse ash
crystal tuff that is slightly metamorphosed. No faults or fissures are
identified below the landfill. Gas permeability of the rock mass is
negligible and will be controlled by the fracture / fissure pattern, therefore
the rate of movement of gas will be slow and any build-up of gas could only
occur over a long period of time.
9.6.3.4
Whilst mapped information identifies
unconsolidated superficial debris flow deposits above the rock at the location
where the Project area encroaches the consultation zone, although these
superficial deposits are anticipated to be more gas permeable, any gas would
need to pass through rock first, therefore natural migration pathways are
classified as “Long and Indirect”. No man-made pathways are identified. Figure
9.2 illustrated the superficial geology
in the vicinity of Ngau Tam Mei Landfill.
9.6.4.1
Construction Phase - Preliminary development
plans within the Landfill Consultation Zone are to construct an
electrical substation (G5.4). Landfill
restoration facilities within NTML will remain unaffected. Whilst
excavation is expected and this may create confined spaces within trenches
where risk of exposure of LFG can increase, given the pathway assessment,
risk is likely to be negligible. Furthermore, construction work within the
consultation zone would be undertaken by trained workers with risk assessment,
safety supervision and implementation of safe construction methodologies acting
to mitigate identified risks.
Furthermore, construction will mainly be undertaken in an outdoor
environment therefore, in general the sensitivity of this group is considered
“Low”.
9.6.4.2
Operation Phase - To facilitate further
assessment of hazards, the Guidance Note suggests consideration of the intended
use and contents, provision and reliability of ventilation and frequency of use
of each at risk area.
9.6.4.3
By nature, an electrical substation is a restricted
access facility which the public will not have access to. Moderately sensitive elements of the
proposed development may include transformer rooms / capacitors / cable rooms
at ground level where access is only by authorized, well trained personnel
where training can include familiarization with potential hazards associated
with LFG and specific safety procedures to be followed. Low sensitivity
elements of the development may include a car park and security post (if
any). Based on these assumptions the
target is conservatively classified as “Moderately Sensitive”.
9.6.5.1
On the basis of the source,
pathways and targets identified above, a source-pathway-target analysis has
been undertaken and is presented according to EPD’s assessment framework in Table
9.7.
9.6.5.2
This classification is intended only as preliminary
guidance on the nature of protective works anticipated for the development, and a more
detailed investigation and reassessment at the development stage will allow
targeted and more accurate design of protective measures.
Table 9.7 Source-Pathway-Target Analysis
Minor Source
|
Long / Indirect Pathway
|
Target Sensitivity – Low for Construction Phase /Medium for Operation
Phase
|
Risk Category
|
NTML can be
considered an ‘old landfill’ site where the maximum concentration of methane
within the waste, as measured at (ongoing) monthly intervals as demonstrated
by EPD data from August 2019 to July 2021 is <0.1% by volume. Whilst detections of carbon dioxide greater
than 5% v/v have occasionally been measured in A451 located outside the
site’s eastern boundary and in DH408 located close to the toe of the slope to
the west of waste boundary but within the site boundary; given the age of the
landfill and likely phase of gas production, volumes of gas evolution
resulting in a pressure gradient and lateral migration of gas are not
anticipated to be significant especially as passive venting creates a
preferential vertical gas migration pathway from the landfill.
Assessment
suggests that there is no serious LFG migration problem therefore the
restored NTML can be classified as a “Minor” Source.
|
The majority of NTML is underlain by coarse ash crystal
tuff that is slightly metamorphosed. No faults or fissures are identified
below the landfill. Gas permeability of the rock mass is
negligible and will be controlled by the fracture / fissure pattern,
therefore the rate of movement of gas will be slow and any build-up of gas
could only occur over a long period of time.
Whilst mapped information identifies unconsolidated
superficial debris flow deposits above the rock at the location where the Project
area encroaches the consultation zone, although these superficial deposits
are anticipated to be more gas permeable, any gas would need to pass through
rock first, therefore natural migration pathways are classified as “Long and
Indirect”. No man-made pathways are identified between the
landfill and the planned development.
|
Construction
Phase - Whilst foundation construction may entail excavation which may create
confined spaces where risk of exposure of LFG can increase; given the
pathway assessment, risk is likely to be negligible. Furthermore,
construction work would be undertaken by trained workers with risk
assessment, safety supervision and implementation of safe construction
methodologies acting to mitigate identified risks. Construction Phase target are classified as “Low’ Sensitivity
|
Source Pathway
Receptor linkages classify the overall risk during construction phase to be “Very
Low”.
|
Operation Phase - By nature,
an electrical substation is a restricted access facility which the public
will not have access to. Moderately
sensitive elements of the proposed development may include transformer rooms
/ capacitors / cable rooms at ground level.
Low sensitivity elements of the development may include a car park and
security post (if any).
Based on these
assumptions the target sensitivity during operation is classified as “Medium”
|
Source Pathway
Receptor linkages classify the overall risk during operation phase to be
“Low”.
For a low risk development Some precautionary measures will be
required to ensure that the planned development is safe. The gas protection
measures may be located on the boundary of the development closest to the
landfill.
Generic measures
may be limited to passive gas control such as provision of barriers to the
movement of gas or high permeability vents such as no-fines gravel in
trenches or voids/permeable layers below structures.
|
9.7.1.1
For a “Low” risk situation, some precautionary
measures will be required to ensure that the planned development within the
consultation zone is safe. Generic
measures are presented in the following sections.
9.7.2
Protection Measures during
Construction
9.7.2.1
During construction phase, the risk was classified
as very low (insignificant) that no precautionary measures are required.
9.7.3.1
During the operation phase of the development, if
further groundworks or construction works are planned, the same landfill gas
precautionary measures as those recommended for the construction stage should
be followed.
9.7.3.2
Using the prescribed methodology and evaluation of
possible migration pathways to an as yet detailed design; an overall low risk
categorization is derived; therefore some passive
engineering measures require consideration for incorporating into the design to
ensure the development with the consultation zone remains safe during
operation.
9.7.3.3
For this situation (development of an electricity
substation), generic passive precautionary measures may include utility
protection measures for services passing through the consultation zone,
creation of a subsurface preferential gas venting pathway or construction of a
subsurface gas barrier and venting of manholes and above ground terminations.
In ground venting or gas barrier protection measures may be located on the
boundary of the development closest to the landfill. Dependent upon the
orientation of the development and detailed design, utilities penetrating a
ground floor slab on grade may require sealing.
9.7.3.4
Implementation of a combination of these generic
measures should effectively mitigate landfill gas hazard.
9.7.3.5
Utility Protection Design Measures - For all
service runs, the aim should be to provide a protective barrier at the point
where the trenches pass through the perimeter of the consultation zone such
that trench excavations do not form a route for gas migration. The void around any service ducts, pipes or cables within conduits at the point where the
trench passes through the perimeter of the consultation zone should be filled
with gas resistant mastic. Service runs
within the consultation zone may remain “unprotected” since risk will be
minimized by the protection measures installed at the perimeter of the
consultation zone and as the general public may not
have access to such underground features.
9.7.3.6
All ducts, manholes and chambers to utility
services should be sealed from the surrounding ground to prevent gas entry and
provided with vented covers to allow any gas that enters to dissipate to
atmosphere.
9.7.3.7
The service run should be designated as a “special
route” and utility companies should be informed to that effect so that they may
implement precautionary measures.
Precautionary measures should include ensuring that staff members are
aware of the potential hazards of working in confined spaces such as manholes
and service chambers, and that appropriate monitoring procedures are in place
to prevent hazards due to asphyxiating atmospheres in confined spaces. Detailed
guidance on entry into confined spaces is given in Code of Practice on Safety
and Health at Work in Confined Spaces (Labour
Department, Hong Kong).
9.7.3.8
Structure Protection Design Measures - Passive
control measures may be used in low risk situations
for low gas concentrations at relatively low emissions rates and where venting
to atmosphere is unlikely to cause a hazard or nuisance due to dilution in
ambient air.
9.7.3.9
Passive control measures for structures with ground
level or below ground rooms or other voids should be considered in the detailed
design:
·
For sub-surface
building services/utilities, generic protection measures should include U-bends
fitted to water pipes and sewers which are not always fully filled to effectively
seal off the conduit and prevent gas-phase transport.
·
For building
services penetrating the ground floor slab, collar seals should be installed to
prevent gas ingress via the penetration.
·
Vent pipes or
gridded manhole covers may be used to avoid build-up of gas in underground
utility manholes.
9.7.4
Guidance for Entry into Service Rooms / Voids,
Manholes and Chambers
9.7.4.1
Any service voids, manholes or chambers which
are large enough to permit access to personnel should be subject to entry
safety procedures. Works in confined
spaces are controlled by the Factories and Industrial Undertakings (Confined
Spaces) Regulation of the Factories and Industrial Undertakings Ordinance and
the Safety Guide to Working in Confined Spaces should be followed to ensure
compliance with the Regulation.
9.7.4.2
In general, when work is being undertaken in
confined spaces, sufficient approved resuscitation equipment, breathing
apparatus and safety torches should be made available. Persons involved in or supervising such work
should be trained and practiced in the use of such equipment. A permit-to-work system for entry into
confined spaces should be developed by an appropriately qualified person and the system
should be consistently employed. The
safety measures recommended in Chapter 8 of the Landfill Gas Hazard Assessment
Guidance Note should also be strictly followed.
9.8.1.1
No monitoring is required during the construction
phase of the Project.
9.8.1.2
Monitoring for landfill gases shall be conducted
during the operation phases of the Project. It is recommended that pre-entry monitoring
should be undertaken, where applicable, in accordance with the requirements of
the Factories and Industrial Undertaking (Confined Spaces) Regulation. For excavations of 1m depth or more, landfill
gas should be monitored before entry and periodically during the works. If drilling is required, the procedures for
safety management and working procedures described in the EPD’s Landfill Gas
Hazard Assessment Guidance Note should be adopted.
9.8.1.3
The monitoring programme
and detailed actions should be submitted to EPD for approval in the detailed
design stage. The proposed parameters, locations and
frequency of landfill gas monitoring for various phases of Project are detailed
in the EM&A Manual.
9.9
Conclusion
9.9.1.1
A small portion of the Project lying within Ngau
Tam Mei Landfill Consultation Zone. Quantitative landfill gas hazard is
conservatively assessed as “Very Low” for the construction phase and “Low” for
the operation phase. Some precautionary measures will be required to ensure
that the planned development is safe.
9.9.1.2
Generic measures may be limited to passive gas
control such as provision of barriers to the movement of gas or high
permeability vents such as no-fines gravel in trenches between the landfill and
development,
9.9.1.3
The designer of the building works should
undertake detailed design of the mitigation measures during the detailed design
stage. Provided that the construction
and operation phase protection measures are appropriately designed and properly
implemented, safety will be safeguarded and landfill
gas impacts will be mitigated.