ANNEX - GENERAL CALIBRATION AND MEASUREMENT PROCEDURES
1. | Instrumentation For the purpose of this Technical Memorandum sound level meters shall comply with International Electrotechnical Commission Publications 651:1979 (Type 1) and 804:1985 (Type 1), and other noise measuring and analysis instrumentation shall be of a comparable professional quality. Standard acoustical principles and practices shall be followed in the measurement and analysis of the noise under investigation. |
||||||||||||||
2. | Calibration Procedures Immediately prior to and following each noise measurement the accuracy of the sound level meter shall be checked using an acoustic calibrator generating a known sound pressure level at a known frequency. Measurements may be accepted as valid only if the calibration levels from before and after the noise measurement agree to within 1.0 dB. |
||||||||||||||